ENGINEERING GUIDE Specification Sheets | Submittal Data | Manuals
ENGINEERING GUIDE Table of Contents
Company Overview
Diesel Product Line Specification Sheets
IT4 Diesel Product Line Specification Sheets
Gaseous Product Line Specification Sheets
ASCO Transfer Switches
Component Information Sheets
Manuals
Warranty Information
Our Purpose Blue Star is committed to working with our customers to continually develop and improve our products to ensure customers are able to provide state of the art, compliant products to the markets they serve. Most importantly, we are committed to providing secure and rewarding lives for our coworkers and community. We believe that the customer is our boss and that we will build the best company and products through the tireless pursuit of understanding and responding to the needs of our customers.
Quality Policy At Blue Star, we strive to produce products that are the highest quality in the power generation industry. Our products are built with top quality components and designed with excellence, reliability, and safety in mind. Our experienced staff is dedicated to ensuring that everything we make will meet or exceed customer expectations. We are also absolutely committed to continually advancing our products and listening to our customers.
Custom Products Blue Star’s ability to adapt a unit to your unique specifications is what sets us apart. Our company has thrived on the principle of providing the customer a unit that fits, not one that doesn’t. We are the company that is with you all the way: from design, through system engineering, to the installation of your unit. Our experience gives you industry leading power solutions.
ENGINEERING GUIDE Specification Sheets | Diesel Product Line 60 Hz 1800 RPM
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD30-02 30 kWe / 25 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
284PSL1708
283PSL1707
283PSL1707
283PSL1707
283PSL5251
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
30
30
30
30
30
AMPS
125
104
90
45
36
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
25
25
25
25
25
AMPS
104
87
75
38
30
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1000W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD30-02 1
Diesel Product Line 30 kWe / 25 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4024TF281
Bore - in. (cm) x Stroke - in. (cm):
Type:
Compression Ratio:
Aspiration: Cylinder Arrangement:
4-Cycle Turbo Charged 4 Cylinder Inline
146 (2.4) 3.4 (8.6) x 4.1 (10.5) 20.5:1
Rated RPM: Max HP Stby (kWm):
1800 49.0 (36.0)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
1,026 (552)
963 (517)
Gas Volume at Stack Temp: CFM (m³/min)
283 (8.1)
261 (7.38)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0 (7.5)
30.0 (7.5)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
24.0 (91.8)
24.8 (91.8)
Heat Rejection to Coolant: BTUM (kW)
1,423 (24.9)
1,309 (22.9)
Heat Radiated to Ambient: BTUM (kW)
470 (8.21)
396 (6.85)
Aspirating: CFM (m³/min)
106 (3.0)
99.0 (2.8)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
2,606 (74.0)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
2,606 (74.0)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
2.79 (10.6)
2.52 (9.54)
At 75% of Power Rating: gal/hr (lit/hr)
2.06 (7.8)
1.89 (7.15)
At 50% of Power Rating: gal/hr (lit/hr)
1.39 (5.26)
1.24 (4.69)
Fluids Capacity Total Oil System: gal (lit)
2.1 (8.0)
2.1 (8.0)
Engine Jacket Water Capacity: gal (lit)
0.68 (2.6)
0.68 (2.6)
System Coolant Capacity: gal (lit)
2.3 (8.7)
2.3 (8.7)
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD30-02 2
Diesel Product Line 30 kWe / 25 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
72 x 34 x 48 in
1375
Level 1
72 x 34 x 60 in
1675
Level 2
72 x 34 x 72 in
1850
Level 3
96 x 34 x 66 in
2050
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
69 dBA
72 dBA
Level 1
66 dBA
68 dBA
Level 2
64 dBA
66 dBA
Level 3
61 dBA
63 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD30-02 3
Diesel Product Line 30 kWe / 25 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (70 Gallon)
48 Hour (140 Gallon)
72 Hour (210 Gallon)
A
B
C
A
B
C
A
B
C
OPU
72.00
34.00
14.00
72.00
34.00
26.00
84.00
34.00
32.00
Level 1
72.00
34.00
14.00
72.00
34.00
26.00
84.00
34.00
32.00
Level 2
72.00
34.00
14.00
72.00
34.00
26.00
84.00
34.00
32.00
Level 3
96.00
34.00
10.00
96.00
34.00
34.00
96.00
34.00
26.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD30-02
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD40-03 40 kWe / 35 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
361CSL1601
361CSL1600
361CSL1600
361CSL1600
284PSL5253
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
40
40
40
40
40
AMPS
167
139
120
60
48
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
35
35
35
35
35
AMPS
146
122
105
53
42
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD40-03 1
Diesel Product Line 40 kWe / 35 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045TF280
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged 4 Cylinder Inline
275 (4.50) 4.19 (10.6) x 5.0 (12.7)
Max HP Stby (kWm):
19.0:1 1800 75.0 (56.0)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
945 (507)
918 (492)
Gas Volume at Stack Temp: CFM (m³/min)
448 (12.7)
424 (12.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0 (7.5)
30.0 (7.5)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
38 (144)
38 (144)
Heat Rejection to Coolant: BTUM (kW)
1,821 (31.9)
Heat Radiated to Ambient: BTUM (kW)
512 (9.0)
448 (7.8)
Aspirating: CFM (m³/min)
180 (5.09)
173 (4.9)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
4,760 (135)
Cooling System
1707 (29.9)
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
4,760 (135)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
4.13 (15.6)
3.82 (14.4)
At 75% of Power Rating: gal/hr (lit/hr)
3.25 (12.3)
2.99 (11.3)
At 50% of Power Rating: gal/hr (lit/hr)
2.21 (8.37)
2.11 (8.0)
Total Oil System: gal (lit)
3.88 (14.7)
3.88 (14.7)
Engine Jacket Water Capacity: gal (lit)
2.25 (8.52)
2.25 (8.52)
System Coolant Capacity: gal (lit)
5.38 (20.4)
5.38 (20.4)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD40-03 2
Diesel Product Line 40 kWe / 35 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
84 x 36 x 58 in
1800
Level 1
84 x 36 x 66 in
2200
Level 2
84 x 36 x 83 in
2375
Level 3
110 x 36 x 77 in
2525
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
75 dBA
79 dBA
Level 1
71 dBA
74 dBA
Level 2
69 dBA
72 dBA
Level 3
63 dBA
66 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD40-03 3
Diesel Product Line 40 kWe / 35 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (120 Gallon)
48 Hour (240 Gallon)
72 Hour (360 Gallon)
A
B
C
A
B
C
A
B
C
OPU
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 1
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 2
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 3
110.00
36.00
14.00
110.00
36.00
24.00
120.00
36.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD40-03
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD50-03 50 kWe / 45 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
361CSL1602
361CSL1601
361CSL1601
361CSL1601
361PSL1633
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
50
50
50
50
50
AMPS
208
174
151
75
60
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
45
45
45
45
45
AMPS
188
156
135
68
54
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD50-03 1
Diesel Product Line 50 kWe / 45 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045TF280
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged 4 Cylinder Inline
275 (4.5) 4.19 (10.6) x 5.0 (12.7)
Max HP Stby (kWm):
19.0:1 1800 75.0 (56.0)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
945 (507)
918 (492)
Gas Volume at Stack Temp: CFM (m³/min)
448 (12.7)
424 (12.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30 (7.5)
30 (7.5)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
38.0 (144)
38.0 (144)
Heat Rejection to Coolant: BTUM (kW)
1,821 (31.9)
Heat Radiated to Ambient: BTUM (kW)
512 (9.0)
448 (7.8)
Aspirating: CFM (m³/min)
180 (5.09)
173 (4.9)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
4,760 (135)
1707 (29.9)
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
4,760 (135)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
4.13 (15.6)
3.82 (14.4)
At 75% of Power Rating: gal/hr (lit/hr)
3.25 (12.3)
2.99 (11.3)
At 50% of Power Rating: gal/hr (lit/hr)
2.21 (8.37)
2.11 (8.0)
Total Oil System: gal (lit)
3.88 (14.7)
3.88 (14.7)
Engine Jacket Water Capacity: gal (lit)
2.25 (8.52)
2.25 (8.52)
System Coolant Capacity: gal (lit)
5.38 (20.4)
5.38 (20.4)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD50-03 2
Diesel Product Line 50 kWe / 45 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
84 x 36 x 59 in
1975
Level 1
84 x 36 x 66 in
2350
Level 2
84 x 36 x 83 in
2550
Level 3
110 x 36 x 77 in
2700
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
75 dBA
79 dBA
Level 1
71 dBA
74 dBA
Level 2
69 dBA
72 dBA
Level 3
63 dBA
66 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD50-03 3
Diesel Product Line 50 kWe / 45 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (120 Gallon)
48 Hour (240 Gallon)
72 Hour (360 Gallon)
A
B
C
A
B
C
A
B
C
OPU
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 1
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 2
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 3
110.00
36.00
14.00
110.00
36.00
24.00
110.00
36.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD50-03
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD60-02 60 kWe / 50 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
362CSL1604
361CSL1602
361CSL1602
361CSL1601
361PSL1633
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
60
60
60
60
60
AMPS
250
208
181
90
72
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
50
50
50
50
50
AMPS
208
174
150
75
60
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD60-02 1
Diesel Product Line 60 kWe / 50 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045TF280
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged 4 Cylinder Inline
275 (4.50) 4.19 (10.6) x 5.0 (12.7)
Max HP Stby (kWm):
19.0:1 1800 85.0 (76.0)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
1,074 (579)
1,024 (551)
Gas Volume at Stack Temp: CFM (m³/min)
679 (19.2)
645 (18.3)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0 (7.5)
30.0 (7.5)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
38.0 (144)
38.0 (144)
Heat Rejection to Coolant: BTUM (kW)
2,049 (35.9)
Heat Radiated to Ambient: BTUM (kW)
854 (14.9)
712 (12.5)
Aspirating: CFM (m³/min)
187 (5.29)
180 (5.09)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
4,760 (135)
4,760 (135)
Cooling System
1,878 (32.9)
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
4.59 (17.4)
4.21 (15.9)
At 75% of Power Rating: gal/hr (lit/hr)
3.56 (13.5)
3.28 (12.4)
At 50% of Power Rating: gal/hr (lit/hr)
2.48 (9.38)
2.35 (8.9)
Total Oil System: gal (lit)
3.88 (14.7)
3.88 (14.7)
Engine Jacket Water Capacity: gal (lit)
2.32 (8.5)
2.32 (8.5)
System Coolant Capacity: gal (lit)
5.4 (20.4)
5.4 (20.4)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD60-02 2
Diesel Product Line 60 kWe / 50 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
84 x 36 x 59 in
1975
Level 1
84 x 36 x 66 in
2350
Level 2
84 x 36 x 83 in
2550
Level 3
110 x 36 x 77 in
2700
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
75 dBA
79 dBA
Level 1
71 dBA
74 dBA
Level 2
69 dBA
72 dBA
Level 3
63 dBA
66 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD60-02 3
Diesel Product Line 60 kWe / 50 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (120 Gallon)
48 Hour (240 Gallon)
72 Hour (360 Gallon)
A
B
C
A
B
C
A
B
C
OPU
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 1
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 2
84.00
36.00
18.00
84.00
36.00
32.00
104.00
36.00
36.00
Level 3
110.00
36.00
14.00
110.00
36.00
24.00
120.00
36.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD60-02
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD80-02 80 kWe / 70 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
363CSL1607
362CSL1604
362CSL1604
362CSL1604
362PSL1635
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
80
80
80
80
80
AMPS
333
278
241
120
96
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
70
70
70
70
70
AMPS
292
243
211
105
84
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD80-02 1
Diesel Product Line 80 kWe / 70 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045HF285
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 4 Cylinder Inline
275 (4.5) 4.19 (10.6) x 5.0 (12.7)
Max HP Stby (kWm):
19.0:1 1800 126 (94.0)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
1,069 (576)
1,042 (561)
Gas Volume at Stack Temp: CFM (m³/min)
651 (18.4)
612 (17.3)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0 (7.5)
30.0 (7.5)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
48.0 (182)
48.0 (182)
Heat Rejection to Coolant: BTUM (kW)
2,990 (52.3)
Heat Rejection to CAC: BTUM (kW)
627 (11.8)
640 (11.2)
Heat Radiated to Ambient: BTUM (kW)
1,138 (19.9)
996 (17.4)
Aspirating: CFM (m³/min)
234 (6.62)
223 (6.31)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
6,541 (185)
6,541 (185)
Cooling System
2,855 (50.5)
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
6.6 (25.0)
6.04 (22.9)
At 75% of Power Rating: gal/hr (lit/hr)
5.37 (20.3)
4.93 (18.7)
At 50% of Power Rating: gal/hr (lit/hr)
3.96 (15.0)
3.63 (13.8)
Total Oil System: gal (lit)
3.43 (13.0)
3.43 (13.0)
Engine Jacket Water Capacity: gal (lit)
2.24 (8.5)
2.24 (8.5)
System Coolant Capacity: gal (lit)
5.4 (20.4)
5.4 (20.4)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD80-02 2
Diesel Product Line 80 kWe / 70 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
100 x 44 x 61 in
2400
Level 1
100 x 44 x 74 in
2925
Level 2
100 x 44 x 92 in
3175
Level 3
132 x 44 x 84 in
3425
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
76 dBA
80 dBA
Level 1
72 dBA
75 dBA
Level 2
70 dBA
73 dBA
Level 3
64 dBA
67 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD80-02 3
Diesel Product Line 80 kWe / 70 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (250 Gallon)
48 Hour (500 Gallon)
72 Hour (750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 1
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 2
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 3
132.00
44.00
18.00
132.00
44.00
30.00
165.00
44.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD80-02
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD100-01 100 kWe / 90 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
363PSL3133
362CSL1606
362CSL1606
362CSL1606
362PSL1636
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
100
100
100
100
100
AMPS
417
347
301
151
120
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
90
90
90
90
90
AMPS
375
312
271
135
108
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD100-01 1
Diesel Product Line 100 kWe / 90 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045HF285
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 4 Cylinder Inline
275 (4.5) 4.19 (10.6) x 5.0 (12.7)
Max HP Stby (kWm):
19.0:1 1800 158 (118)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
1,076 (580)
1,040 (560)
Gas Volume at Stack Temp: CFM (m³/min)
805 (22.8)
750 (21.2)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0(7.5)
30.0 (7.5)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
48.0 (182)
48.0 (182)
Heat Rejection to Coolant: BTUM (kW)
3,544 (62.0)
3,470 (60.7)
Heat Rejection to CAC: BTUM (kW)
1,127 (19.8)
1,002 (17.6)
Heat Radiated to Ambient: BTUM (kW)
1,281 (22.4)
1,153 (20.2)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
288 (8.15)
273 (7.73)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
6,640 (188)
6,640 (188)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
8.21 (31.1)
7.55 (28.6)
At 75% of Power Rating: gal/hr (lit/hr)
6.56 (24.8)
6.03 (22.8)
At 50% of Power Rating: gal/hr (lit/hr)
4.69 (17.8)
4.31 (16.3)
Total Oil System: gal (lit)
3.43 (13.0)
3.43 (13.0)
Engine Jacket Water Capacity: gal (lit)
2.24 (8.5)
2.24 (8.5)
System Coolant Capacity: gal (lit)
5.4 (20.4)
5.4 (20.4)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD100-01 2
Diesel Product Line 100 kWe / 90 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
100 x 44 x 61 in
2500
Level 1
100 x 44 x 74 in
3025
Level 2
100 x 44 x 92 in
3275
Level 3
132 x 44 x 84 in
3525
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
78 dBA
81 dBA
Level 1
75 dBA
78 dBA
Level 2
73 dBA
76 dBA
Level 3
68 dBA
71 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD100-01 3
Diesel Product Line 100 kWe / 90 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (250 Gallon)
48 Hour (500 Gallon)
72 Hour (750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 1
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 2
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 3
132.00
44.00
18.00
132.00
44.00
30.00
165.00
44.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD100-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
CD100-01 100 kWe / 90 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
363CSL3133
362CSL1606
362CSL1606
362CSL1606
362PSL1636
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
100
100
100
100
100
AMPS
417
347
301
151
120
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available for Mobile Applications]
kWe
90
90
90
90
90
AMPS
375
313
271
135
108
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
Based Digital Control
±
1.0% Voltage Regulation
Main
Oil
Pump & Filter
4
Pole, Rotating Field
Critical
Grade Silencer Mounted
Oil
Drain Extension w/ Valve
130˚C
Standby Temperature Rise
Battery
Charger 12V 6 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
CD100-01 1
Diesel Product Line 100 kWe / 90 kWe
Application Data Engine Manufacturer: Model:
Cummins QSB5-G4 NR3
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 4 Cylinder Inline
272 (4.5) 4.21 (10.7) x 4.88 (12.4)
Max HP Stby (kWm):
17.3:1 1800 160 (119)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
824 (440)
761 (405)
Gas Volume at Stack Temp: CFM (m³/min)
804 (22.7)
759 (21.4)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
40.8 (10.2)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
43.0 (163)
43.0 (163)
Heat Rejection to Coolant: BTUM (kW)
2,720 (47.6)
2,453 (42.9)
Heat Rejection to CAC: BTUM (kW)
1,596 (27.9)
1,606 (28.1)
Heat Radiated to Ambient: BTUM (kW)
1,423 (24.9)
1,281 (22.4)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
355 (10.0)
354 (10.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
6,330 (111)
6,330 (111)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
8.0 (30.3)
7.2 (27.3)
At 75% of Power Rating: gal/hr (lit/hr)
6.3 (23.8)
6.0 (22.7)
At 50% of Power Rating: gal/hr (lit/hr)
4.5 (17.0)
3.9 (14.8)
Total Oil System: gal (lit)
3.20 (12.1)
3.2 (12.1)
Engine Jacket Water Capacity: gal (lit)
2.25 (8.5)
2.25 (8.5)
System Coolant Capacity: gal (lit)
5.4 (20.4)
5.4 (20.4)
Fluids Capacity
Deration Factors Rated power available up to 3200 ft (975 m) standby and 4100ft (1250m) prime at ambient temperatures to 122oF (50˚C) standby and 104˚F (40˚C) prime. Consult factory for site conditions above these parameters.
CD100-01 2
Diesel Product Line 100 kWe / 90 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
100 x 44 x 61 in
2125
LEVEL 1
100 x 44 x 72 in
2675
LEVEL 2
100 x 44 x 90 in
2925
LEVEL 3
132 x 44 x 84 in
3150
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
82 dBA
84 dBA
Level 1
76 dBA
79 dBA
Level 2
73 dBA
76 dBA
Level 3
69 dBA
71 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
CD100-01 3
Diesel Product Line 100 kWe / 90 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (250 Gallon)
48 Hour (500 Gallon)
72 Hour (750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
100.00
44.00
26.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 1
100.00
44.00
26.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 2
100.00
44.00
26.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 3
132.00
44.00
18.00
132.00
44.00
30.00
165.00
44.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
CD100-1
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD125-02 125 kWe / 110 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
431CSL6204
363CSL1607
36CSL1607
363CSL1607
363PSL1658
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
125
125
125
125
125
AMPS
521
434
376
188
151
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
110
110
110
110
110
AMPS
458
382
331
166
132
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD125-02 1
Diesel Product Line 125 kWe / 110 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045HF285
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 4 Cylinder Inline
275 (4.5) 4.19 (10.6) x 5.0 (12.7)
Max HP Stby (kWm):
19.0:1 1800 197 (147)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
1076 (580)
1062 (572)
Gas Volume at Stack Temp: CFM (m³/min)
953 (27.0)
869 (24.6)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0 (7.5)
30.0 (7.5)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
48 (180)
48 (180)
Heat Rejection to Coolant: BTUM (kW)
4,098 (72.0)
3,643 (64.0)
Heat Rejection to CAC: BTUM (kW)
1,508 (26.5)
1,295 (22.8)
Heat Radiated to Ambient: BTUM (kW)
1,457 (25.5)
1,252 (21.9)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
341 (9.65)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
7,845 (222)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
311 (8.8) 7,845 (222)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
9.86 (37.3)
9.15 (34.7)
At 75% of Power Rating: gal/hr (lit/hr)
7.63 (28.9)
7.08 (26.8)
At 50% of Power Rating: gal/hr (lit/hr)
5.56 (21.1)
5.13 (19.4)
Total Oil System: gal (lit)
3.88 (14.7)
3.88 (14.7)
Engine Jacket Water Capacity: gal (lit)
2.25 (8.5)
2.25 (8.5)
System Coolant Capacity: gal (lit)
5.4 (20.4)
5.4 (20.4)
Fluids Capacity
Deration Factors Rated Power is available up to 7500 ft (2286 m) standby and 10,000 ft (3048 m) prime at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
JD125-02 2
Diesel Product Line 125 kWe / 110 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
100 x 44 x 61 in
2650
Level 1
100 x 44 x 74 in
3175
Level 2
100 x 44 x 92 in
3435
Level 3
132 x 44 x 84 in
3625
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
82 dBA
86 dBA
Level 1
79 dBA
82 dBA
Level 2
78 dBA
81 dBA
Level 3
69 dBA
72 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD125-02 3
Diesel Product Line 125 kWe / 110 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (250 Gallon)
48 Hour (500 Gallon)
72 Hour (750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
100.00
44.00
26.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 1
100.00
44.00
26.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 2
100.00
44.00
26.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 3
132.00
44.00
18.00
132.00
44.00
30.00
165.00
44.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD125-02
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD150-01 150 kWe / 140 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
431CSL6206
431CSL6202
431CSL6202
431CSL6202
431PSL6240
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
150
150
150
150
150
AMPS
625
521
452
226
181
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
140
140
140
140
140
AMPS
583
486
421
211
169
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 2000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD150-01 1
Diesel Product Line 150 kWe / 140 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6068HF285
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
415 (6.8) 4.19 (10.6) x 5.0 (12.7)
Max HP Stby (kWm):
19.0:1 1800 237 (177)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
981 (527)
981 (527)
Gas Volume at Stack Temp: CFM (m³/min)
1,158 (32.8)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0 (7.5)
30.0 (7.5)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
48.0 (182)
48.0 (182)
Heat Rejection to Coolant: BTUM (kW)
5,407 (94.6)
5,009 (87.7)
Heat Rejection to CAC: BTUM (kW)
1,708 (29.9)
1,508 (26.4)
Heat Radiated to Ambient: BTUM (kW)
2,135 (37.4)
1,992 (34.7)
1,104 (31.3)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
448 (12.7)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
10,683 (302)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
427 (12.1) 10,683 (302)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
11.8 (44.7)
10.9 (41.4)
At 75% of Power Rating: gal/hr (lit/hr)
9.4 (35.5)
8.5 (32.1)
At 50% of Power Rating: gal/hr (lit/hr)
6.9 (26.1)
6.2 (23.5)
Total Oil System: gal (lit)
5.02 (19.0)
5.02 (19.0)
Engine Jacket Water Capacity: gal (lit)
3.14 (11.9)
3.14 (11.9)
System Coolant Capacity: gal (lit)
6.10 (23.1)
6.10 (23.1)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD150-01 2
Diesel Product Line 150 kWe / 140 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
110 x 48 x 64 in
3350
Level 1
110 x 48 x 82 in
4000
Level 2
110 x 48 x 101 in
4315
Level 3
150 x 48 x 92 in
4450
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
81 dBA
85 dBA
Level 1
80 dBA
84 dBA
Level 2
79 dBA
83 dBA
Level 3
70 dBA
73 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD150-01 3
Diesel Product Line 150 kWe / 140 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (375 Gallon)
48 Hour (750 Gallon)
72 Hour (1125 Gallon)
A
B
C
A
B
C
A
B
C
OPU
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 1
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 2
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 3
150.00
48.00
18.00
150.00
48.00
36.00
230.00
48.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD150-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
CD150-01 150 kWe / 125 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
431CSL6206
431CSL6202
431CSL6202
431CSL6202
431PSL6240
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
150
150
150
150
150
AMPS
625
521
452
226
181
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available for Mobile Applications]
kWe
125
125
125
125
125
AMPS
521
434
376
188
151
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
Based Digital Control
±
1.0% Voltage Regulation
Main
Oil
Pump & Filter
4
Pole, Rotating Field
Critical
Grade Silencer Mounted
Oil
Drain Extension w/ Valve
130˚C
Standby Temperature Rise
Battery
Charger 12V 6 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 1800W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
CD150-01 1
Diesel Product Line 150 kWe / 125 kWe
Application Data Engine Manufacturer: Model:
Cummins QSB7-G2 NR3
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged CAC 6 Cylinder Inline
408 (6.69) 4.21 (10.7) x 4.88 (12.4)
Max HP Stby (kWm):
17.2:1 1800 234 (174)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
940 (504)
888 (476)
Gas Volume at Stack Temp: CFM (m³/min)
1268 (35.9)
1166 (33.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
40.8 (10.2)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
38.0 (144)
38.0 (144)
Heat Rejection to Coolant: BTUM (kW)
4,188 (73.3)
3,791 (66.3)
Heat Rejection to CAC: BTUM (kW)
1,966 (34.4)
1,752 (30.7)
Heat Radiated to Ambient: BTUM (kW)
2,561 (44.8)
2,135 (37.4)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
513 (14.5)
489 (13.8)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
9,870 (279)
9,870 (279)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
11.9 (45.0)
10.5 (39.7)
At 75% of Power Rating: gal/hr (lit/hr)
9.1 (34.4)
8.1 (30.7)
At 50% of Power Rating: gal/hr (lit/hr)
6.2 (23.5)
5.7 (21.6)
Total Oil System: gal (lit)
5.0 (18.9)
5.0 (18.9)
Engine Jacket Water Capacity: gal (lit)
2.7 (10.2)
2.7 (10.2)
System Coolant Capacity: gal (lit)
6.3 (23.8)
6.3 (23.8)
Fluids Capacity
Deration Factors Rated power available up to 5200 ft (1585 m) at ambient temperatures to 122oF (50˚C) standby and prime. Consult factory for site conditions above these parameters.
CD150-01 2
Diesel Product Line 150 kWe / 125 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
110 x 48 x 65 in
3050
LEVEL 1
110 x 48 x 82 in
3750
LEVEL 2
110 x 48 x 100 in
4050
LEVEL 3
150 x 48 x 92 in
4350
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
81 dBA
84 dBA
Level 1
80 dBA
83 dBA
Level 2
79 dBA
82 dBA
Level 3
70 dBA
73 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
CD150-01 3
Diesel Product Line 150 kWe / 125 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (375 Gallon)
48 Hour (750 Gallon)
72 Hour (1125 Gallon)
A
B
C
A
B
C
A
B
C
OPU
110.00
48.00
26.00
150.00
48.00
36.00
215.00
48.00
36.00
Level 1
110.00
48.00
26.00
150.00
48.00
36.00
215.00
48.00
36.00
Level 2
110.00
48.00
26.00
150.00
48.00
36.00
215.00
48.00
36.00
Level 3
150.00
48.00
18.00
150.00
48.00
36.00
215.00
48.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
CD150-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD200-01 200 kWe / 185 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
432CSL6210
431CSL6206
431CSL6206
431CSL6206
431PSL6243
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
200
200
200
200
200
AMPS
833
695
602
301
241
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
185
185
185
185
185
AMPS
771
643
557
278
223
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 2000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD200-01 1
Diesel Product Line 200 kWe / 185 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6068HFG85
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
415 (6.8) 4.19 (10.6) x 5.0 (12.7)
Max HP Stby (kWm):
17.0:1 1800 315 (235)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
905 (485)
905 (485)
Gas Volume at Stack Temp: CFM (m³/min)
1,515 (42.9)
1,370 (38.8)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.0 (10.0)
40.0 (10.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
70.0 (265)
70.0 (265)
Heat Rejection to Coolant: BTUM (kW)
5,402 (94.9)
4,764 (83.7)
Heat Rejection to CAC: BTUM (kW)
3,264 (57.3)
2,298 (40.4)
Heat Radiated to Ambient: BTUM (kW)
2,419 (42.3)
2,238 (39.2)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
618 (17.5)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
11,066 (313)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
519 (17.7) 11,066 (313)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
15.5 (58.5)
13.7 (51.8)
At 75% of Power Rating: gal/hr (lit/hr)
11.3 (42.9)
10.3 (39.0)
At 50% of Power Rating: gal/hr (lit/hr)
7.9 (30.0)
7.2 (27.4)
Total Oil System: gal (lit)
8.59 (32.5)
8.59 (32.5)
Engine Jacket Water Capacity: gal (lit)
3.14 (11.9)
3.14 (11.9)
System Coolant Capacity: gal (lit)
7.1 (29.3)
7.1 (29.3)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD200-01 2
Diesel Product Line 200 kWe / 185 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
110 x 48 x 64 in
3750
Level 1
110 x 48 x 82 in
4425
Level 2
110 x 48 x 101 in
4725
Level 3
150 x 48 x 92 in
4850
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
83 dBA
86 dBA
Level 1
81 dBA
85 dBA
Level 2
80 dBA
83 dBA
Level 3
71 dBA
74 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD200-01 3
Diesel Product Line 200 kWe / 185 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (375 Gallon)
48 Hour (750 Gallon)
72 Hour (1125 Gallon)
A
B
C
A
B
C
A
B
C
OPU
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 1
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 2
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 3
150.00
48.00
18.00
150.00
48.00
36.00
230.00
48.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD200-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
CD200-01 200 kWe / 175 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
432CSL6210
431CSL6206
431CSL6206
431CSL6206
431PSL6243
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
200
200
200
200
200
AMPS
833
695
602
301
241
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available for Mobile Applications]
kWe
175
175
175
175
175
AMPS
729
608
527
263
211
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
Based Digital Control
±
1.0% Voltage Regulation
Main
Oil
Pump & Filter
4
Pole, Rotating Field
Critical
Grade Silencer Mounted
Oil
Drain Extension w/ Valve
130˚C
Standby Temperature Rise
Battery
Charger 12V 6 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 1800W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
CD200-01 1
Diesel Product Line 200 kWe / 175 kWe
Application Data Engine Manufacturer: Model:
Cummins QSB7-G5 NR3
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
408 (6.69) 4.21 (10.7) x 4.88 (12.4)
Max HP Stby (kWm):
17.2:1 1800 324 (242)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
988 (531)
907 (486)
Gas Volume at Stack Temp: CFM (m³/min)
1,549 (43.8)
1,342 (38.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
40.8 (10.2)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
38 (144)
38 (144)
Heat Rejection to Coolant: BTUM (kW)
4,858 (85.0)
4,231 (74.0)
Heat Rejection to CAC: BTUM (kW)
2,786 (48.8)
2,499 (43.7)
Heat Radiated to Ambient: BTUM (kW)
2,135 (37.4)
2,117 (37.0)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
569 (16.1)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
17,492 (495)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
541 (15.3) 17,492 (495)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
15.5 (58.7)
13.3 (50.3)
At 75% of Power Rating: gal/hr (lit/hr)
11.6 (43.9)
10.6 (40.1)
At 50% of Power Rating: gal/hr (lit/hr)
9.0 (34.1)
7.8 (29.5)
Total Oil System: gal (lit)
5.0 (18.9)
5.0 (18.9)
Engine Jacket Water Capacity: gal (lit)
2.7 (10.2)
2.7 (10.2)
System Coolant Capacity: gal (lit)
6.3 (23.1)
6.3 (23.1)
Fluids Capacity
Deration Factors Rated power available up to 2400 ft (732 m) at ambient temperatures to 122oF standby and prime. Consult factory for site conditions above these parameters.
CD200-01 2
Diesel Product Line 200 kWe / 175 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
110 x 48 x 65 in
3275
LEVEL 1
110 x 48 x 82 in
3950
LEVEL 2
110 x 48 x 100 in
4250
LEVEL 3
150 x 48 x 92 in
4475
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
90 dBA
92 dBA
Level 1
89 dBA
91 dBA
Level 2
86 dBA
88 dBA
Level 3
74 dBA
76 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
CD200-01 3
Diesel Product Line 200 kWe / 175 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (375 Gallon)
48 Hour (750 Gallon)
72 Hour (1125 Gallon)
A
B
C
A
B
C
A
B
C
OPU
110.00
48.00
26.00
150.00
48.00
36.00
215.00
48.00
36.00
Level 1
110.00
48.00
26.00
150.00
48.00
36.00
215.00
48.00
36.00
Level 2
110.00
48.00
26.00
150.00
48.00
36.00
215.00
48.00
36.00
Level 3
150.00
48.00
18.00
150.00
48.00
36.00
215.00
48.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
CD200-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD250-02 250 kWe / 250 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4027
432CSL6210
432CSL6210
432CSL6210
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
250
250
250
250
250
AMPS
1042
868
753
376
301
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
250
250
250
250
250
AMPS
1042
868
753
376
301
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD250-02 1
Diesel Product Line 250 kWe / 250 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6090HF484
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
549 (9.0) 4.66 (11.8) x 5.35 (13.6)
Max HP Stby (kWm):
16.0:1 1800 422 (315)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
1,180 (638)
1,180 (638)
Gas Volume at Stack Temp: CFM (m³/min)
2,085 (59.0)
2,067 (58.5)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30 (7.5)
30 (7.5)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
74.0 (280)
74.0 (280)
Heat Rejection to Coolant: BTUM (kW)
5,943 (104)
5,371 (94)
Heat Rejection to CAC: BTUM (kW)
5,029 (88.0)
4,943 (86.5)
Heat Radiated to Ambient: BTUM (kW)
2,312 (40.5)
2,312 (40.5)
Air Requirements Aspirating: CFM (m³/min)
901 (25.5)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
15,333 (434)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
901 (25.5) 15,333 (434)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
19.6 (74.3)
18.4 (69.9)
At 75% of Power Rating: gal/hr (lit/hr)
17.0 (64.2)
15.9 (60.2)
At 50% of Power Rating: gal/hr (lit/hr)
12.0 (45.4)
11.3 (42.7)
Total Oil System: gal (lit)
8.2 (31.0)
8.2 (31.0)
Engine Jacket Water Capacity: gal (lit)
4.25 (16.0)
4.25 (16.0)
System Coolant Capacity: gal (lit)
13.2 (50.0)
13.2 (50.0)
Fluids Capacity
Deration Factors Rated Power is available up to 5500 ft (1677 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD250-02 2
Diesel Product Line 250 kWe / 250 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
120 x 54 x 77 in
4200
Level 1
120 x 54 x 90 in
5000
Level 2
120 x 54 x 107 in
5300
Level 3
160 x 54 x 98 in
5725
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
80 dBA
84 dBA
Level 1
78 dBA
82 dBA
Level 2
77 dBA
80 dBA
Level 3
68 dBA
71 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD250-02 3
Diesel Product Line 250 kWe / 250 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (475 Gallon)
48 Hour (950 Gallon)
72 Hour (1425 Gallon)
A
B
C
A
B
C
A
B
C
OPU
120.00
54.00
28.00
165.00
54.00
36.00
230.00
54.00
36.00
Level 1
120.00
54.00
28.00
165.00
54.00
36.00
230.00
54.00
36.00
Level 2
120.00
54.00
28.00
165.00
54.00
36.00
230.00
54.00
36.00
Level 3
160.00
54.00
20.00
165.00
54.00
36.00
230.00
54.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD250-02
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
CD250-01 250 kWe / 210 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4025
432CSL6210
432CSL6210
432CSL6210
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
250
250
250
250
250
AMPS
1042
868
753
376
301
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available for Mobile Applications]
kWe
210
210
210
210
210
AMPS
875
729
632
316
253
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
Based Digital Control
±
1.0% Voltage Regulation
Main
Oil
Pump & Filter
4
Pole, Rotating Field
Critical
Grade Silencer Mounted
Oil
Drain Extension w/ Valve
130˚C
Standby Temperature Rise
Battery
Charger 24V 5 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
CD250-01 1
Diesel Product Line 250 kWe / 210 kWe
Application Data Engine Manufacturer: Model:
Cummins QSL9-G2 NR3
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
543 (8.8) 4.49 (11.4) x 5.69 (14.5)
Max HP Stby (kWm):
17.8:1 1800 375 (280)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
1,065 (575)
1,000 (540)
Gas Volume at Stack Temp: CFM (m³/min)
2,090 (59.1)
1,985 (56.2)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
64.0 (242)
64.0 (242)
Heat Rejection to Coolant: BTUM (kW)
6,560 (115)
6,155 (108)
Heat Rejection to CAC: BTUM (kW)
3,490 (61.1)
3,370 (59.0)
Heat Radiated to Ambient: BTUM (kW)
2,312 (40.5)
1,942 (34.0)
Air Requirements Aspirating: CFM (m³/min)
775 (21.9)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
20,887 (591)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
770 (21.8) 20,887 (591)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
19.3 (73.1)
17.6 (66.6)
At 75% of Power Rating: gal/hr (lit/hr)
16.2 (61.3)
14.3 (54.1)
At 50% of Power Rating: gal/hr (lit/hr)
12.0 (45.4)
10.0 (37.9)
Total Oil System: gal (lit)
7.0 (26.5)
7.0 (26.5)
Engine Jacket Water Capacity: gal (lit)
2.9 (11.0)
2.9 (11.0)
System Coolant Capacity: gal (lit)
8.2 (31.0)
8.2 (31.0)
Fluids Capacity
Deration Factors Rated power available up to 2700 ft (823 m) at ambient temperatures to 104oF standby and prime. Consult factory for site conditions above these parameters.
CD250-01 2
Diesel Product Line 250 kWe / 210 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
120 x 54 x 71 in
4500
LEVEL 1
120 x 54 x 88 in
5400
LEVEL 2
120 x 54 x 106 in
5750
LEVEL 3
160 x 54 x 98 in
6350
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
83 dBA
86 dBA
Level 1
79 dBA
81 dBA
Level 2
78 dBA
80 dBA
Level 3
68 dBA
72 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
CD250-01 3
Diesel Product Line 250 kWe / 210 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (560 Gallon)
48 Hour (1120 Gallon)
72 Hour (1680 Gallon)
A
B
C
A
B
C
A
B
C
OPU
120.00
54.00
32.00
195.00
54.00
36.00
275.00
54.00
36.00
Level 1
120.00
54.00
32.00
195.00
54.00
36.00
275.00
54.00
36.00
Level 2
120.00
54.00
32.00
195.00
54.00
36.00
275.00
54.00
36.00
Level 3
160.00
54.00
22.00
195.00
54.00
36.00
275.00
54.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
CD250-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD275-02 275 kWe / 250 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4027
432CSL6210
432CSL6210
432CSL6210
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
275
275
275
275
275
AMPS
1146
955
828
414
331
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
250
250
250
250
250
AMPS
1042
868
752
376
301
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
12V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 12V 6 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD275-02 1
Diesel Product Line 275 kWe / 250 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6090HF484
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
549 (9.0) 4.66 (11.84) x 5.35 (13.6)
Max HP Stby (kWm):
16.0:1 1800 422 (315)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
1,180 (638)
1,180 (638)
Gas Volume at Stack Temp: CFM (m³/min)
2,085 (59.0)
2,067 (58.5)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0 (7.5)
30.0 (7.5)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
74.0 (280)
74.0 (280)
Heat Rejection to Coolant: BTUM (kW)
5,943 (104)
5,371 (94.0)
Heat Rejection to CAC: BTUM (kW)
5,029 (88.0)
4,943 (86.5)
Heat Radiated to Ambient: BTUM (kW)
2,312 (40.5)
2,312 (40.5)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
901 (25.5)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
15,333 (434)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
901 (25.5) 15,333 (434)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
19.6 (74.3)
18.4 (69.9)
At 75% of Power Rating: gal/hr (lit/hr)
17.0 (64.2)
15.9 (60.2)
At 50% of Power Rating: gal/hr (lit/hr)
12.0 (45.4)
11.3 (42.7)
Total Oil System: gal (lit)
8.2 (31.0)
8.2 (31.0)
Engine Jacket Water Capacity: gal (lit)
4.25 (16.0)
4.25 (16.0)
System Coolant Capacity: gal (lit)
13.2 (50.0)
13.2 (50.0)
Fluids Capacity
Deration Factors Rated Power is available up to 5500 ft (1677 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD275-02 2
Diesel Product Line 275 kWe / 250 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
120 x 54 x 77 in
4275
Level 1
120 x 54 x 90 in
5075
Level 2
120 x 54 x 107 in
5375
Level 3
160 x 54 x 98 in
5800
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
80 dBA
84 dBA
Level 1
78 dBA
82 dBA
Level 2
77 dBA
80 dBA
Level 3
68 dBA
71 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD275-02 3
Diesel Product Line 275 kWe / 250 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (475 Gallon)
48 Hour (950 Gallon)
72 Hour (1425 Gallon)
A
B
C
A
B
C
A
B
C
OPU
120.00
54.00
28.00
165.00
54.00
36.00
230.00
54.00
36.00
Level 1
120.00
54.00
28.00
165.00
54.00
36.00
230.00
54.00
36.00
Level 2
120.00
54.00
28.00
165.00
54.00
36.00
230.00
54.00
36.00
Level 3
160.00
54.00
20.00
165.00
54.00
36.00
230.00
54.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD275-02
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD300-02 300 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4029
433CSL6216
433CSL6216
432CSL6212
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
300
300
300
300
300
AMPS
1250
1042
903
452
361
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Prime Power Rating Not Avaialbe On This Model.
Standard Equipment Additional
Generator
Engine Radiator
Brushless
Single Bearing
UL
Blower
Fan & Fan Drive
Cooled Unit Mounted (50˚C)
Automatic
Voltage Regulator
cUL
2200 Listed
Starter
& Alternator
Listed
±
1.0% Voltage Regulation
Microprocessor
Oil
Pump & Filter
4
Pole, Rotating Field
Base
- Formed Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
100%
of Rated Load - One Step
Critical
Grade Silencer Mounted
Battery
Charger 12V 6 Amp
Governor
- Electronic Isochronous
12V
Battery System & Cables
5%
SAE
Flywheel Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Based Digital Control
Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
Colors - White / Tan / Gray
JD300-02 1
Diesel Product Line 300 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6090HFG86
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
549 (9.0) 4.66 (11.8) x 5.35 (13.6) 16.0:1 1800
Max HP Stby (kWm):
463 (345)
Exhaust System
Standby
Gas Temp. (Stack): °F (°C)
927 (497)
Gas Volume at Stack Temp: CFM (m³/min)
2,246 (63.6)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
30.0 (7.5)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
78.0 (295)
Heat Rejection to Coolant: BTUM (kW)
6,489 (114)
Heat Rejection to CAC: BTUM (kW)
5,641 (99.1)
Heat Radiated to Ambient: BTUM (kW)
3,244 (56.8)
Air Requirements Aspirating: CFM (m³/min)
936 (26.5)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
19,014 (538)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
22.1 (83.7)
At 75% of Power Rating: gal/hr (lit/hr)
17.8 (67.3)
At 50% of Power Rating: gal/hr (lit/hr)
13.1 (49.5)
Fluids Capacity Total Oil System: gal (lit)
8.2 (31.0)
Engine Jacket Water Capacity: gal (lit)
4.23 (16.0)
System Coolant Capacity: gal (lit)
13.2 (50.0)
Deration Factors Rated Power is available up to 2500 ft (762 m) at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
JD300-02 2
Diesel Product Line 300 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
125 x 66 x 81 in
5250
Level 1
125 x 66 x 105 in
6000
Level 2
125 x 66 x 115 in
6275
Level 3
180 x 66 x 104 in
6675
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
80 dBA
86 dBA
Level 1
79 dBA
83 dBA
Level 2
78 dBA
81 dBA
Level 3
68 dBA
72 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD300-02 3
Diesel Product Line 300 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (640 Gallon)
48 Hour (1280 Gallon)
72 Hour (1920 Gallon)
A
B
C
A
B
C
A
B
C
OPU
125.00
66.00
28.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 1
125.00
66.00
28.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 2
125.00
66.00
28.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 3
180.00
66.00
18.00
180.00
66.00
36.00
255.00
66.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD300-02
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
CD300-02 300 kWe / 270 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4029
433CSL6216
433CSL6216
432CSL6212
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
300
300
300
300
300
AMPS
1250
1042
903
452
361
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available for Mobile Applications]
kWe
270
270
270
270
270
AMPS
1125
938
813
406
325
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Brushless
Single Bearing
UL
Blower
Fan & Fan Drive
Cooled Unit Mounted (50˚C)
Automatic
Voltage Regulator
cUL
2200 Listed
Starter
& Alternator
Listed
±
1.0% Voltage Regulation
Microprocessor
Oil
Pump & Filter
4
Pole, Rotating Field
Base
- Formed Steel
Oil
Drain Extension w/ Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
105˚C
Prime Temperature Rise
Critical
of Rated Load - One Step
Battery
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Based Digital Control
Grade Silencer Mounted Charger 24V 5 Amp Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
CD300-02 1
Diesel Product Line 300 kWe / 270 kWe
Application Data Engine Manufacturer: Model:
Cummins QSL9-G7 NR3
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
543 (8.9) 4.49 (11.4) x 5.69 (14.5)
Max HP Stby (kWm):
16.1:1 1800 464 (346)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
977 (525)
919 (493)
Gas Volume at Stack Temp: CFM (m³/min)
2,341 (66.3)
2,200 (62.3)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
40.8 (10.2)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
72.0 (273)
72.0 (273)
Heat Rejection to Coolant: BTUM (kW)
8,262 (145)
7,469 (131)
Heat Rejection to CAC: BTUM (kW)
5,036 (88.1)
4,620 (80.9)
Heat Radiated to Ambient: BTUM (kW)
2,135 (37.4)
1,921 (33.6)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
898 (25.4)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
20,637 (584)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
867 (24.5) 20,637 (584)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
23.5 (89.0)
21.2 (80.3)
At 75% of Power Rating: gal/hr (lit/hr)
18.5 (70.0)
17.4 (65.9)
At 50% of Power Rating: gal/hr (lit/hr)
14.2 (53.7)
12.6 (47.7)
Total Oil System: gal (lit)
9.0 (34.1)
9.0 (34.1)
Engine Jacket Water Capacity: gal (lit)
2.91 (11.0)
2.91 (11.0)
System Coolant Capacity: gal (lit)
10.7 (40.5)
10.7 (40.5)
Fluids Capacity
Deration Factors Rated power available up to 1750 ft (533 m) at ambient temperatures to 104oF standby and prime. Consult factory for site conditions above these parameters.
CD300-02 2
Diesel Product Line 300 kWe / 270 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
120 x 54 x 72 in
4675
LEVEL 1
120 x 54 x 88 in
5450
LEVEL 2
120 x 54 x 106 in
5750
LEVEL 3
160 x 54 x 98 in
6375
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
84 dBA
87 dBA
Level 1
80 dBA
83 dBA
Level 2
79 dBA
82 dBA
Level 3
72 dBA
74 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
CD300-02 3
Diesel Product Line 300 kWe / 270 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (560 Gallon)
48 Hour (1120 Gallon)
72 Hour (1680 Gallon)
A
B
C
A
B
C
A
B
C
OPU
120.00
54.00
32.00
195.00
54.00
36.00
275.00
54.00
36.00
Level 1
120.00
54.00
32.00
195.00
54.00
36.00
275.00
54.00
36.00
Level 2
120.00
54.00
32.00
195.00
54.00
36.00
275.00
54.00
36.00
Level 3
160.00
54.00
22.00
195.00
54.00
36.00
275.00
54.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
CD300-02
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD350-01 350 kWe / 320 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
433CSL6216
433CSL6216
433CSL6216
433PSL6248
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
350
350
350
350
AMPS
1216
1054
527
421
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
320
320
320
320
AMPS
1112
963
482
385
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Structural Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
24V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 24V 5 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD350-01 1
Diesel Product Line 350 kWe / 320 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6135HF485
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
824 (13.5) 5.19 (13.2) x 6.49 (16.5)
Max HP Stby (kWm):
16.0:1 1800 538 (401)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
835 (446)
783 (417)
Gas Volume at Stack Temp: CFM (m³/min)
2,649 (75.0)
2,295 (64.9)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.0 (10.0)
40.0 (10.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
124 (470)
124 (470)
Heat Rejection to Coolant: BTUM (kW)
11,042 (193)
10,359 (181)
Heat Rejection to CAC: BTUM (kW)
6,033 (106)
5,237 (91.6)
Heat Radiated to Ambient: BTUM (kW)
3,984 (69.7)
3,643 (63.8)
Aspirating: CFM (m³/min)
1,165 (33.0)
1,059 (30.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
22,586 (639)
22,586 (639)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
26.4 (99.9)
23.2 (87.9)
At 75% of Power Rating: gal/hr (lit/hr)
19.3 (72.9)
17.4 (65.8)
At 50% of Power Rating: gal/hr (lit/hr)
13.7 (51.7)
12.5 (47.3)
Total Oil System: gal (lit)
15.9 (60.0)
15.9 (60.0)
Engine Jacket Water Capacity: gal (lit)
4.76 (18.0)
4.76 (18.0)
System Coolant Capacity: gal (lit)
23.0 (87.1)
23.0 (87.1)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD350-01 2
Diesel Product Line 350 kWe / 320 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
140 x 66 x 81 in
8025
Level 1
140 x 66 x 105 in
9100
Level 2
140 x 66 x 123 in
9575
Level 3
195 x 66 x 112 in
10,025
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
82 dBA
86 dBA
Level 1
81 dBA
84 dBA
Level 2
80 dBA
83 dBA
Level 3
71 dBA
73 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD350-01 3
Diesel Product Line 350 kWe / 320 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (640 Gallon)
48 Hour (1280 Gallon)
72 Hour (1920 Gallon)
A
B
C
A
B
C
A
B
C
OPU
140.00
66.00
24.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 1
140.00
66.00
24.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 2
140.00
66.00
24.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 3
195.00
66.00
16.00
195.00
66.00
32.00
255.00
66.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD350-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
VD350-01 350 kWe / 330 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
573RSL4033
433CSL6216
433CSL6216
433CSL6216
433PSL6248
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
350
350
350
350
350
AMPS
1458
1216
1054
527
421
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
330
330
330
330
330
AMPS
1375
1146
993
497
397
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Critical
Grade Silencer Mounted
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
Charger 24V 5 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
VD350-01 1
Diesel Product Line 350 kWe / 330 kWe
Application Data Engine Manufacturer:
Volvo
Displacement - Cu. In. (lit):
Model: TAD1352GE
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
780 (12.8) 5.2 (13.1) x 6.2 (15.8)
Max HP Stby (kWm):
18.1:1 1800 537 (395)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
995 (535)
878 (470)
Gas Volume at Stack Temp: CFM (m³/min)
2,391 (67.7)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.0 (10.0)
32.0 (8.0)
Ambient Capacity of Radiator: °F (°C)
122 (50)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (.12)
Water Pump Flow Rate: Gpm (lit/min)
87.0 (329)
87.0 (329)
Heat Rejection to Coolant: BTUM (kW)
10,066 (177)
9,327 (164)
Heat Rejection to CAC: BTUM (kW)
4,948 (87.0)
4,720 (83.0)
Heat Radiated to Ambient: BTUM (kW)
2,988 (52.3)
2,818 (49.3)
2,214 (62.7)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
918 (26.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
16,325 (462)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
918 (26.0) 16,325 (462)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
25.5 (96.5)
23.1 (87.4)
At 75% of Power Rating: gal/hr (lit/hr)
19.3 (73.1)
17.7 (67.0)
At 50% of Power Rating: gal/hr (lit/hr)
13.2 (50.0)
12.3 (46.6)
Total Oil System: gal (lit)
9.0 (36.0)
9.0 (36.0)
Engine Jacket Water Capacity: gal (lit)
5.28 (20.0)
5.28 (20.0)
System Coolant Capacity: gal (lit)
11.7 (44.0)
11.7 (44.0)
Fluids Capacity
Deration Factors Rated Power is available up to 4920 ft (1500 m) at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
VD350-01 2
Diesel Product Line 350 kWe / 330 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
140 x 66 x 82 in
8550
Level 1
140 x 66 x 105 in
9375
Level 2
140 x 66 x 123 in
10,025
Level 3
195 x 66 x 112 in
10,675
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
85 dBA
87 dBA
Level 1
82 dBA
86 dBA
Level 2
80 dBA
84 dBA
Level 3
72 dBA
75 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
VD350-01 3
Diesel Product Line 350 kWe / 330 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (640 Gallon)
48 Hour (1280 Gallon)
72 Hour (1920 Gallon)
A
B
C
A
B
C
A
B
C
OPU
140.00
66.00
24.00
170.00
66.00
36.00
260.00
66.00
36.00
Level 1
140.00
66.00
24.00
170.00
66.00
36.00
260.00
66.00
36.00
Level 2
140.00
66.00
24.00
170.00
66.00
36.00
260.00
66.00
36.00
Level 3
195.00
66.00
18.00
195.00
66.00
32.00
260.00
66.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
VD350-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
VD400-01 400 kWe / 360 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
573RSL4035
433CSL6220
433CSL6220
433CSL6220
433PSL6248
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
400
400
400
400
400
AMPS
1667
1390
1204
602
482
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
360
360
360
360
360
AMPS
1500
1251
1084
542
434
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Critical
Grade Silencer Mounted
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
Charger 24V 5 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
VD400-01 1
Diesel Product Line 400 kWe / 360 kWe
Application Data Engine Manufacturer:
Volvo
Displacement - Cu. In. (lit):
Model: TAD1353GE
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
780 (12.8) 5.2 (13.1) x 6.2 (15.8)
Max HP Stby (kWm):
18.1:1 1800 611 (449)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
923 (495)
905 (485)
Gas Volume at Stack Temp: CFM (m³/min)
2,790 (79.0)
2,613 (74.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.0 (10.0)
40.0 (10.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
87.0 (329)
87.0 (329)
Heat Rejection to Coolant: BTUM (kW)
10,123 (177)
9383 (164)
Heat Rejection to CAC: BTUM (kW)
5,346 (94.0)
5,289 (93.0)
Heat Radiated to Ambient: BTUM (kW)
3,415 (59.8)
3,202 (56.0)
Aspirating: CFM (m³/min)
1,102 (31.2)
1,038 (29.4)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
24,175 (684)
24,175 (684)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
27.9 (105.6)
25.6 (96.9)
At 75% of Power Rating: gal/hr (lit/hr)
21.9 (82.9)
20.1 (76.1)
At 50% of Power Rating: gal/hr (lit/hr)
15.0 (56.8)
14.0 (53.0)
Total Oil System: gal (lit)
9.5 (36.0)
9.5 (36.0)
Engine Jacket Water Capacity: gal (lit)
5.28 (20.0)
5.28 (20.0)
System Coolant Capacity: gal (lit)
11.6 (44.0)
11.6 (44.0)
Fluids Capacity
Deration Factors Rated Power is available up to 4920 ft (1500 m) at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
VD400-01 2
Diesel Product Line 400 kWe / 360 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications - RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 11 Contact Outputs
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
140 x 66 x 82 in
8,550
Level 1
140 x 66 x 105 in
9375
Level 2
140 x 66 x 123 in
10,025
Level 3
195 x 66 x 112 in
10,675
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
85 dBA
88 dBA
Level 1
83 dBA
87 dBA
Level 2
81 dBA
85 dBA
Level 3
71 dBA
73 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
VD400-01 3
Diesel Product Line 400 kWe / 360 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (875 Gallon)
48 Hour (1750 Gallon)
72 Hour (2625 Gallon)
A
B
C
A
B
C
A
B
C
OPU
140.00
66.00
34.00
235.00
66.00
36.00
330.00
66.00
36.00
Level 1
140.00
66.00
34.00
235.00
66.00
36.00
330.00
66.00
36.00
Level 2
140.00
66.00
34.00
235.00
66.00
36.00
330.00
66.00
36.00
Level 3
195.00
66.00
22.00
191.00
66.00
32.00
330.00
66.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
VD400-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD415-01 415 kWe / 375 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
572RSL4025
572RSL4025
433CSL6220
572RSS4270
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
415
415
415
415
AMPS
1442
1249
625
500
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
375
375
375
375
AMPS
1303
1129
564
452
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Listed
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Microprocessor
Listed
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Base
- Structural Steel
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
Governor
105˚C
Prime Temperature Rise
Critical
Grade Silencer Mounted
24V
Battery System & Cables
100%
of Rated Load - One Step
Battery
Charger 24V 5 Amp
SAE
Flywheel Housing
5%
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD415-01 1
Diesel Product Line 415 kWe / 375 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6135HF485
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
824 (13.5) 5.2 (13.2) x 6.5 (16.5)
Max HP Stby (kWm):
16.0:1 1800 617 (460)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
880 (471)
801 (427)
Gas Volume at Stack Temp: CFM (m³/min)
2,860 (80.9)
2,578 (73.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.0 (10.0)
40.0 (10.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
124 (469)
124 (469)
Heat Rejection to Coolant: BTUM (kW)
13,148 (230)
11,953 (209)
Heat Rejection to CAC: BTUM (kW)
6,944 (122)
6,660 (117)
Heat Radiated to Ambient: BTUM (kW)
3,425 (59.9)
3,095 (54.2)
Aspirating: CFM (m³/min)
1,201 (34.0)
1,130 (32.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
23,750 (672)
23,750 (672)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
30.5 (115.6)
26.6 (100.9)
At 75% of Power Rating: gal/hr (lit/hr)
22.4 (84.8)
19.7 (74.7)
At 50% of Power Rating: gal/hr (lit/hr)
15.2 (57.6)
13.7 (51.8)
Total Oil System: gal (lit)
15.9 (60.0)
15.9 (60.0)
Engine Jacket Water Capacity: gal (lit)
4.76 (18.0)
4.76 (18.0)
System Coolant Capacity: gal (lit)
23.0 (87.1)
23.0 (87.1)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122˚F (50˚C) standby and prime. Consult factory for site conditions above these parameters.
JD415-01 2
Diesel Product Line 415 kWe / 375 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
140 x 66 x 85 in
8050
Level 1
140 x 66 x 105 in
9125
Level 2
140 x 66 x 123 in
9600
Level 3
195 x 66 x 112 in
10,050
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
85 dBA
89 dBA
Level 1
82 dBA
86 dBA
Level 2
81 dBA
84 dBA
Level 3
71 dBA
73 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD415-01 3
Diesel Product Line 415 kWe / 375 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (640 Gallon)
48 Hour (1280 Gallon)
72 Hour (1920 Gallon)
A
B
C
A
B
C
A
B
C
OPU
140.00
66.00
24.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 1
140.00
66.00
24.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 2
140.00
66.00
24.00
178.00
66.00
36.00
255.00
66.00
36.00
Level 3
195.00
66.00
16.00
195.00
66.00
32.00
255.00
66.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD415-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
VD450-01 450 kWe / 410 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
572RSL4027
572RSL4027
572RSL4025
572RSS4270
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
450
450
450
450
AMPS
1563
1355
677
542
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standby
Prime
[Only Available For Mobile Applications]
kWe
410
410
410
410
AMPS
1424
1234
617
494
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Critical
Grade Silencer Mounted
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
Charger 24V 5 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 3
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 5000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
VD450-01 1
Diesel Product Line 450 kWe / 410 kWe
Application Data Engine Manufacturer:
Volvo
Displacement - Cu. In. (lit):
Model: TAD1650GE
Bore - in. (cm) x Stroke - in. (cm):
Type:
Compression Ratio:
Aspiration: Cylinder Arrangement:
4-Cycle Turbo Charged, CAC 6 Cylinder Inline
984 (16.1) 5.7 (14.4) x 6.5 (16.5)
Rated RPM: Max HP Stby (kWm):
16.5:1 1800 677 (498)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
946 (508)
874 (468)
Gas Volume at Stack Temp: CFM (m³/min)
3,214 (91.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.2 (10.0)
32.1 (8.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
122 (461)
122 (461)
Heat Rejection to Coolant: BTUM (kW)
12,511 (219)
11,715 (205)
Heat Rejection to CAC: BTUM (kW)
7,109 (125)
6,483 (114)
Heat Radiated to Ambient: BTUM (kW)
4803 (84.0)
4,376 (76.6)
Aspirating: CFM (m³/min)
1,271 (36.0)
1,236 (35.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
22,473 (636)
22,473 (636)
2,966 (84.0)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
32.1 (121.5)
29.0 (109.8)
At 75% of Power Rating: gal/hr (lit/hr)
24.1 (91.2)
21.9 (82.9)
At 50% of Power Rating: gal/hr (lit/hr)
16.7 (63.2)
15.4 (58.3)
Total Oil System: gal (lit)
12.7 (48.0)
11.1 (42.0)
Engine Jacket Water Capacity: gal (lit)
8.7 (33.0)
8.7 (33.0)
System Coolant Capacity: gal (lit)
15.9 (60.0)
15.9 (60.0)
Fluids Capacity
Deration Factors Rated Power is available up to 4920 ft (1500 m) at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
VD450-01 2
Diesel Product Line 450 kWe / 410 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
150 x 68 x 92 in
9650
Level 1
150 x 68 x 114 in
10,475
Level 2
150 x 68 x 125 in
11,125
Level 3
205 x 68 x 114 in
11,775
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
87 dBA
92 dBA
Level 1
83 dBA
88 dBA
Level 2
81 dBA
86 dBA
Level 3
73 dBA
76 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
VD450-01 3
Diesel Product Line 450 kWe / 410 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (875 Gallon)
48 Hour (1750 Gallon)
72 Hour (2625 Gallon)
A
B
C
A
B
C
A
B
C
OPU
150.00
68.00
30.00
230.00
68.00
36.00
325.00
68.00
36.00
Level 1
150.00
68.00
30.00
230.00
68.00
36.00
325.00
68.00
36.00
Level 2
150.00
68.00
30.00
230.00
68.00
36.00
325.00
68.00
36.00
Level 3
205.00
68.00
20.00
230.00
68.00
36.00
325.00
68.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
VD450-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
CD500-01 500 kWe / 460 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
572RSL4029
572RSL4029
572RSL4027
572RSS4270
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
500
500
500
500
AMPS
1737
1505
753
602
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
460
460
460
460
AMPS
1598
1385
692
554
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Additional
Generator
Engine Radiator
Brushless
Single Bearing
UL
Blower
Fan & Fan Drive
Cooled Unit Mounted (40˚C)
Automatic
Voltage Regulator
cUL
2200 Listed
Starter
& Alternator
Listed
±
1.0% Voltage Regulation
Microprocessor
Oil
Pump & Filter
4
Pole, Rotating Field
Base
- Structural Steel
Oil
Drain Extension w/ Valve
130˚C
Standby Temperature Rise
Main
Line Circuit Breaker Mounted & Wired
105˚C
Prime Temperature Rise
Critical
of Rated Load - One Step
Battery
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Based Digital Control
Grade Silencer Mounted Charger 24V 5 Amp Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
CD500-01 1
Diesel Product Line 500 kWe / 460 kWe
Application Data Engine Manufacturer: Model:
Cummins QSX15-G9 NR2
Type: Aspiration: Cylinder Arrangement:
4-Cycle Turbo Charged, CAC 6 Cylinder Inline
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
912 (15.0) 5.39 (13.7) x 6.65 (16.9)
Compression Ratio: Rated RPM: Max HP Stby (kWm):
17.0:1 1800 755 (563)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
909 (488)
875 (468)
Gas Volume at Stack Temp: CFM (m³/min)
3,845 (109)
3,200 (90.6)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
40.8 (10.2)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
105 (397)
105 (397)
Heat Rejection to Coolant: BTUM (kW)
9,230 (162)
7,830 (137)
Heat Rejection to CAC: BTUM (kW)
9,070 (159)
7,300 (128)
Heat Radiated to Ambient: BTUM (kW)
4,553 (79.7)
4,189 (73.3)
Aspirating: CFM (m³/min)
1,510 (42.7)
1,380 (39.1)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
25,000 (708)
25,000 (708)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
35.9 (136)
31.1 (118)
At 75% of Power Rating: gal/hr (lit/hr)
26.2 (99.2)
23.9 (90.5)
At 50% of Power Rating: gal/hr (lit/hr)
18.2 (68.9)
17.2 (65.3)
Total Oil System: gal (lit)
24.0 (90.8)
24.0 (90.8)
Engine Jacket Water Capacity: gal (lit)
6.3 (24.0)
6.3 (24.0)
System Coolant Capacity: gal (lit)
15.3 (57.9)
15.3 (57.9)
Fluids Capacity
Deration Factors Rated power available up to 500 ft (152 m) at ambient temperatures to 104oF standby and prime. Consult factory for site conditions above these parameters.
CD500-01 2
Diesel Product Line 500 kWe / 460 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
150 x 68 x 98 in
8600
LEVEL 1
150 x 68 x 115 in
9500
LEVEL 2
150 x 68 x 126 in
10,100
LEVEL 3
205 x 68 x 114 in
10,700
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
88 dBA
92 dBA
Level 1
84 dBA
88 dBA
Level 2
83 dBA
87 dBA
Level 3
72 dBA
75 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
CD500-01 3
Diesel Product Line 500 kWe / 460 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (875 Gallon)
48 Hour (1750 Gallon)
72 Hour (2625 Gallon)
A
B
C
A
B
C
A
B
C
OPU
150.00
68.00
30.00
230.00
68.00
36.00
336.00
68.00
36.00
Level 1
150.00
68.00
30.00
230.00
68.00
36.00
336.00
68.00
36.00
Level 2
150.00
68.00
30.00
230.00
68.00
36.00
336.00
68.00
36.00
Level 3
205.00
68.00
22.00
230.00
68.00
36.00
336.00
68.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
CD500-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
VD500-01 500 kWe / 460 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
572RSL4029
572RSL4029
572RSL4027
572RSL4270
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
500
500
500
500
AMPS
1737
1505
753
602
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
460
460
460
460
AMPS
1598
1385
692
554
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Critical
Grade Silencer Mounted
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
Charger 24V 5 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 5000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
VD500-01 1
Diesel Product Line 500 kWe / 460 kWe
Application Data Engine Manufacturer:
Volvo
Displacement - Cu. In. (lit):
Model: TAD1641GE
Bore - in. (cm) x Stroke - in. (cm):
Type:
Compression Ratio:
Aspiration: Cylinder Arrangement:
4-Cycle Turbo Charged, CAC 6 Cylinder Inline
984 (16.1) 5.7 (14.4) x 6.5 (16.5)
Rated RPM: Max HP Stby (kWm):
16.5:1 1800 768 (573)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
893 (478)
817 (436)
Gas Volume at Stack Temp: CFM (m³/min)
3,899 (110)
3,553 (101)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.2 (10.0)
40.2 (10.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
122 (462)
122 (462)
Heat Rejection to Coolant: BTUM (kW)
13,137 (230)
12,056 (211)
Heat Rejection to CAC: BTUM (kW)
7,109 (125)
6,483 (114)
Heat Radiated to Ambient: BTUM (kW)
3,700 (64.8)
3,404 (59.6)
Aspirating: CFM (m³/min)
1,617 (45.8)
1,554 (44.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
21,120 (598)
21,120 (598)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
36.8 (139.3)
32.2 (121.9)
At 75% of Power Rating: gal/hr (lit/hr)
26.8 (101.4)
23.7 (89.6)
At 50% of Power Rating: gal/hr (lit/hr)
18.0 (68.1)
16.0 (60.6)
Total Oil System: gal (lit)
12.7 (48.1)
12.7 (48.1)
Engine Jacket Water Capacity: gal (lit)
8.7 (33.0)
8.7 (33.0)
System Coolant Capacity: gal (lit)
16.0 (60.6)
16.0 (60.6)
Fluids Capacity
Deration Factors Rated Power is available up to 4920 ft (1500 m) at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
VD500-01 2
Diesel Product Line 500 kWe / 460 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
150 x 68 x 98 in
9650
Level 1
150 x 68 x 114 in
10,600
Level 2
150 x 68 x 125 in
11,250
Level 3
205 x 68 x 114 in
11,900
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
88 dBA
93 dBA
Level 1
83 dBA
88 dBA
Level 2
82 dBA
86 dBA
Level 3
72 dBA
76 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
VD500-01 3
Diesel Product Line 500 kWe / 460 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (1250 Gallon)
48 Hour (2500 Gallon)
72 Hour (3750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
175.00
68.00
30.00
230.00
68.00
36.00
325.00
68.00
36.00
Level 1
175.00
68.00
30.00
230.00
68.00
36.00
325.00
68.00
36.00
Level 2
175.00
68.00
30.00
230.00
68.00
36.00
325.00
68.00
36.00
Level 3
205.00
68.00
20.00
230.00
68.00
36.00
325.00
68.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
VD500-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
VD550-01 550 kWe / 510 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
572RSL4031
572RSL4031
572RSL4029
572RSS4272
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
550
550
550
550
AMPS
1911
1656
828
662
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
510
510
510
510
AMPS
1772
1535
768
614
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Critical
Grade Silencer Mounted
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
Charger 24V 5 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 5000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
VD550-01 1
Diesel Product Line 550 kWe / 510 kWe
Application Data Engine Manufacturer:
Volvo
Displacement - Cu. In. (lit):
Model: TAD1642GE
Bore - in. (cm) x Stroke - in. (cm):
Type:
Compression Ratio:
Aspiration:
4-Cycle Turbo Charged, Air to Air CAC
Cylinder Arrangement:
6 Cylinder Inline
984 (16.12) 5.7 (14.4) x 6.5 (16.5)
Rated RPM: Max HP Stby (kWm):
16.5:1 1800 822 (613)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
954 (512)
874 (468)
Gas Volume at Stack Temp: CFM (m³/min)
4,153 (118)
3,846 (109)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.2 (10.0)
32.1 (8.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
122 (462)
122 (462)
Heat Rejection to Coolant: BTUM (kW)
14,104 (248)
12,397 (218)
Heat Rejection to CAC: BTUM (kW)
9,042 (158)
7,957 (139)
Heat Radiated to Ambient: BTUM (kW)
4,253 (74.4)
3,919 (68.6)
Aspirating: CFM (m³/min)
1,646 (46.6)
1,603 (45.4)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
21,120 (598)
21,120 (598)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
39.9 (151.0)
35.9 (136.0)
At 75% of Power Rating: gal/hr (lit/hr)
28.8 (109.0)
26.0 (98.0)
At 50% of Power Rating: gal/hr (lit/hr)
19.1 (72.0)
17.5 (66.0)
Total Oil System: gal (lit)
12.7 (48.0)
12.7 (48.0)
Engine Jacket Water Capacity: gal (lit)
8.7 (33.0)
8.7 (33.0)
System Coolant Capacity: gal (lit)
15.9 (60.0)
15.9 (60.0)
Fluids Capacity
Deration Factors Rated Power is available up to 4920 ft (1500 m) at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
VD550-01 2
Diesel Product Line 550 kWe / 510 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
150 x 68 x 98 in
9575
Level 1
150 x 68 x 114 in
10,825
Level 2
150 x 68 x 125 in
11,475
Level 3
205 x 68 x 114 in
12,125
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
88 dBA
93 dBA
Level 1
83 dBA
88 dBA
Level 2
82 dBA
86 dBA
Level 3
72 dBA
76 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
VD550-01 3
Diesel Product Line 550 kWe / 510 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (1250 Gallon)
48 Hour (2500 Gallon)
72 Hour (3750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 1
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 2
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 3
205.00
68.00
30.00
315.00
68.00
36.00
460.00
68.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
VD550-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
VD600-01 600 kWe / 550 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
573RSL4033
573RSL4033
572RSL4031
572RSS4272
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
600
600
600
600
AMPS
2084
1806
903
723
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
550
550
550
550
AMPS
1911
1656
828
662
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Additional
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Pole, Rotating Field
Based Digital Control
Oil
Pump & Filter
4
Critical
Grade Silencer Mounted
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
Charger 24V 5 Amp
105˚C
Prime Temperature Rise
Jacket
of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel Housing
5%
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 5000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colorss - White / Tan / Gray
VD600-01 1
Diesel Product Line 600 kWe / 550 kWe
Application Data Engine Manufacturer:
Volvo
Displacement - Cu. In. (lit):
Model: TWD1643GE
Bore - in. (cm) x Stroke - in. (cm):
Type:
Compression Ratio:
Aspiration:
4-Cycle Turbo Charged, H2O to Air CAC
Cylinder Arrangement:
6 Cylinder Inline
984 (16.12) 5.7 (14.4) x 6.5 (16.5)
Rated RPM: Max HP Stby (kWm):
16.5:1 1800 917 (674)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
862 (461)
792 (422)
Gas Volume at Stack Temp: CFM (m³/min)
4,594 (130)
4,202 (119)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.2 (10.0)
40.2 (10.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
95.4 (361)
95.4 (361)
Heat Rejection to Coolant: BTUM (kW)
15,355 (270)
13,990 (246)
Heat Rejection to CAC: BTUM (kW)
7,677 (135)
6,881 (121)
Heat Radiated to Ambient: BTUM (kW)
3,928 (68.7)
3,600 (63.0)
Aspirating: CFM (m³/min)
1,937 (54.8)
1,874 (53.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
31,802 (900)
31,802 (900)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
40.8 (154.4)
36.7 (138.9)
At 75% of Power Rating: gal/hr (lit/hr)
29.7 (112.4)
26.9 (101.8)
At 50% of Power Rating: gal/hr (lit/hr)
20.0 (75.7)
18.3 (69.3)
Total Oil System: gal (lit)
12.7 (48.0)
12.7 (48.0)
Engine Jacket Water Capacity: gal (lit)
8.7 (33.0)
8.7 (33.0)
System Coolant Capacity: gal (lit)
25.1 (95.0)
25.1 (95.0)
Fluids Capacity
Deration Factors Rated Power is available up to 4920 ft (1500 m) at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
VD600-01 2
Diesel Product Line 600 kWe / 550 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
150 x 68 x 96 in
10,100
Level 1
150 x 68 x 114 in
10,850
Level 2
150 x 68 x 125 in
11,450
Level 3
205 x 68 x 114 in
12,050
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
87 dBA
91 dBA
Level 1
85 dBA
87 dBA
Level 2
83 dBA
85 dBA
Level 3
75 dBA
77 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
VD600-01 3
Diesel Product Line 600 kWe / 550 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (1250 Gallon)
48 Hour (2500 Gallon)
72 Hour (3750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 1
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 2
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 3
205.00
68.00
30.00
315.00
68.00
36.00
460.00
68.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
VD600-01
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
MD800-01 800 kWe / 735 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
574RSL4038
574RSL4038
574RSL4037
574RSS4278
Connection
4 LEAD WYE
4 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
800
800
800
800
AMPS
2779
2408
1204
963
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
735
735
735
735
AMPS
2553
2213
1106
885
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Structural Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Critical
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Exhaust
Governor
105˚C
Prime Temperature Rise
Battery
24V
Battery System & Cables
100%
of Rated Load - One Step
SAE
Flywheel Housing
5%
Jacket
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Grade Silencer Loose Flex Connector
Charger 24V 5 Amp
Water Heater -20˚F 2 Qty: 5000W 240V w/Isolation Valves
Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
MD800-01 1
Diesel Product Line 800 kWe / 735 kWe
Application Data Engine Manufacturer:
Mitsubishi
Displacement - Cu. In. (lit):
Model: S12AZ-Y2PTAW-2
Bore - in. (cm) x Stroke - in. (cm):
Type:
Compression Ratio:
Aspiration:
4-Cycle Turbo Charged, H2O/Air Intercooled
Cylinder Arrangement:
12 Cylinder Vee
2,071 (33.9) 5.91 (15.0) x 6.3 (16.0)
Rated RPM: Max HP Stby (kWm):
15.3:1 1800 1,207 (900)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
883 (473)
860 (460)
Gas Volume at Stack Temp: CFM (m³/min)
8,192 (232)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
23.6 (5.9)
23.6 (5.9)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
291 (1,102)
291 (1,102)
Heat Rejection to Coolant: BTUM (kW)
20,418 (357)
17,531 (307)
Heat Rejection to Intercooler: BTUM (kW)
16,043 (281)
13,774 (241)
Heat Radiated to Ambient: BTUM (kW)
7,969 (139)
7,321 (128)
Aspirating: CFM (m³/min)
3,107 (87.9)
2,648 (74.9)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
44,950 (1,272)
7,062 (200)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
44,950 (1,272)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
67.4 (255)
58.7 (222)
At 75% of Power Rating: gal/hr (lit/hr)
46.1 (175)
42.0 (159)
At 50% of Power Rating: gal/hr (lit/hr)
31.3 (119)
28.6 (108)
Total Oil System: gal (lit)
31.7 (120)
31.7 (120)
Engine Jacket Water Capacity w/Intercooler: gal (lit)
26.4 (100)
26.4 (100)
System Coolant Capacity: gal (lit)
80.0 (303)
80.0 (303)
Fluids Capacity
Deration Factors Altitude: Derate 0.5% per 328 ft (100 m) above 3280 ft (1000 m) standby and prime. | Temperature: Derate 1.0% per 18oF (10oC) above 104oF (40oC) standby and prime. Consult factory for site conditions above these parameters.
MD800-01 2
Diesel Product Line 800 kWe / 735 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
180 x 75 x 95 in
16,750
Level 1
200 x 90 x 108 in
18,850
Level 2
N/A
N/A
Level 3
344 x 90 x 108 in
21,000
Height measured from bottom of base to top of enclosure.
No Load
Full Load
OPU
87 dBA
90 dBA
Level 1
86 dBA
88 dBA
Level 2
N/A
N/A
Level 3
74 dBA
78 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
MD800-01 3
Diesel Product Line 800 kWe / 735 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base.
Double Wall UL Listed 142 Fuel Tanks 12 Hour (900 Gallon)
24 Hour (1800 Gallon)
36 Hour (3600 Gallon)
A
B
C
A
B
C
A
B
C
OPU
CF
CF
CF
CF
CF
CF
CF
CF
CF
Level 1
200.00
90.00
20.00
200.00
90.00
36.00
360.00
90.00
36.00
Level 2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Level 3
344.00
90.00
10.00
344.00
90.00
20.00
360.00
90.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
MD800-01 4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
MD1000-01 1000 kWe / 920 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
741RSL4045
741RSL4045
575RSL4044
741RSS4282
Connection
12 LEAD WYE
12 LEAD DELTA
4 LEAD WYE
4 LEAD WYE
kWe
1000
1000
1000
1000
AMPS
3474
3011
1505
1204
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
920
920
920
920
AMPS
3196
2770
1385
1108
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Structural Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Critical
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Exhaust
Governor
105˚C
Prime Temperature Rise
Battery
24V
Battery System & Cables
100%
of Rated Load - One Step
SAE
Flywheel Housing
5%
Jacket
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Grade Silencer Loose Flex Connector
Charger 24V 5 Amp
Water Heater -20˚F 2 Qty: 5000W 240V w/Isolation Valves
Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
MD1000-01 1
Diesel Product Line 1000 kWe / 920 kWe
Application Data Engine Manufacturer:
Mitsubishi
Displacement - Cu. In. (lit):
Model: S12H-Y2PTAW-1
Bore - in. (cm) x Stroke - in. (cm):
Type:
Compression Ratio:
Aspiration:
4-Cycle Turbo Charged, H2O/Air Intercooled
Cylinder Arrangement:
12 Cylinder Vee
2,265 (37.1) 5.91 (15.0) x 6.89 (17.5)
Rated RPM: Max HP Stby (kWm):
14.5:1 1800 1,528 (1,140)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
910 (488)
870 (465)
Gas Volume at Stack Temp: CFM (m³/min)
9,534 (270)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
23.6 (5.9)
23.6 (5.9)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
383 (1,450)
383 (1,450)
Heat Rejection to Coolant: BTUM (kW)
23,715 (415)
21,678 (379)
Heat Rejection to Intercooler: BTUM (kW)
18,633 (326)
17,033 (298)
Heat Radiated to Ambient: BTUM (kW)
7,115 (125)
6,546 (115)
Aspirating: CFM (m³/min)
3,602 (102)
3,284 (92.9)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
47,973 (1,358)
8,722 (247)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
47,973 (1,358)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
75.0 (284)
70.2 (266)
At 75% of Power Rating: gal/hr (lit/hr)
59.7 (226)
54.6 (207)
At 50% of Power Rating: gal/hr (lit/hr)
39.8 (151)
36.0 (136)
Total Oil System: gal (lit)
52.8 (200)
52.8 (200)
Engine Jacket Water Capacity w/Intercooler: gal (lit)
26.4 (100)
26.4 (100)
System Coolant Capacity: gal (lit)
84.0 (318)
84.0 (318)
Fluids Capacity
Deration Factors Altitude: Derate 0.5% per 328 ft (100 m) above 3280 ft (1000 m) standby and prime. | Temperature: Derate 1.0% per 18oF (10oC) above 104oF (40oC) standby and prime. Consult factory for site conditions above these parameters.
MD1000-01 2
Diesel Product Line 1000 kWe / 920 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
180 x 82 x 103 in
20,550
Level 1
200 x 90 x 108 in
22,650
Level 2
N/A
N/A
Level 3
344 x 90 x 108 in
24,800
Height measured from bottom of base to top of enclosure.
No Load
Full Load
OPU
87 dBA
90 dBA
Level 1
86 dBA
88 dBA
Level 2
N/A
N/A
Level 3
75 dBA
79 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
MD1000-01 3
Diesel Product Line 1000 kWe / 920 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base.
Double Wall UL Listed 142 Fuel Tanks 12 Hour (900 Gallon)
24 Hour (1250 Gallon)
48 Hour (3600)
A
B
C
A
B
C
A
B
C
OPU
CF
CF
CF
CF
CF
CF
CF
CF
CF
Level 1
200.00
90.00
20.00
200.00
90.00
36.00
360.00
90.00
36.00
Level 2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Level 3
344.00
90.00
10.00
344.00
90.00
20.00
360.00
90.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
MD1000-01 4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
MD1250-01 1250 kWe / 1150 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
CF
CF
742RSL4048
743RSS4288
Connection
4 LEAD WYE
4 LEAD DELTA
4 LEAD WYE
4 LEAD WYE
kWe
1250
1250
1250
1250
AMPS
4342
3763
1881
1505
Temp Rise
CF
CF
130˚C / 27˚C
130˚C / 27˚C
kWe
1150
1150
1150
1150
AMPS
3995
3462
1731
1385
Temp Rise
CF
CF
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Structural Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Critical
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Exhaust
Governor
105˚C
Prime Temperature Rise
Battery
24V
Battery System & Cables
100%
of Rated Load - One Step
SAE
Flywheel Housing
5%
Jacket
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Grade Silencer Loose Flex Connector
Charger 24V 5 Amp
Water Heater -20˚F 2 Qty: 9000W 240V w/Isolation Valves
Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
MD1250-01 1
Diesel Product Line 1250 kWe / 1150 kWe
Application Data Engine Manufacturer:
Mitsubishi
Displacement - Cu. In. (lit):
Model: S12R-Y2PTAW-1
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Turbo Charged, H2O/Air Intercooled
Cylinder Arrangement:
12 Cylinder Vee
2,992 (49.0) 6.69 (17.0) x 7.09 (18.0)
Max HP Stby (kWm):
14.5:1 1800 1,881 (1,403)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
927 (497)
890 (477)
Gas Volume at Stack Temp: CFM (m³/min)
12,570 (356)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
23.6 (5.9)
23.6 (5.9)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
489 (1,851)
489 (1,851)
Heat Rejection to Coolant: BTUM (kW)
29,045 (508)
26,111 (457)
Heat Rejection to Intercooler: BTUM (kW)
29,045 (508)
26,111 (457)
Heat Radiated to Ambient: BTUM (kW)
8,182 (143)
7,528 (132)
Aspirating: CFM (m³/min)
4,767 (135)
4,273 (121)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
69,386 (1,964)
11,299 (320)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
69,386 (1,964)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
103 (392)
91.0 (344)
At 75% of Power Rating: gal/hr (lit/hr)
75.1 (284)
68.4 (259)
At 50% of Power Rating: gal/hr (lit/hr)
51.0 (193)
46.4 (176)
Total Oil System: gal (lit)
39.6 (150)
39.6 (150)
Engine Jacket Water Capacity w/Intercooler: gal (lit)
34.3 (130)
34.3 (130)
System Coolant Capacity: gal (lit)
86.0 (326)
86.0 (326)
Fluids Capacity
Deration Factors Altitude: Derate 0.5% per 328 ft (100 m) above 3280 ft (1000 m) standby and prime. | Temperature: Derate 1.0% per 18oF (10oC) above 104oF (40oC) standby and prime. Consult factory for site conditions above these parameters.
MD1250-01 2
Diesel Product Line 1250 kWe / 1150 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
220 x 96 x 112 in
23,575
Level 1
240 x 106 x 129 in
29,900
Level 2
N/A
N/A
Level 3
420 x 106 x 129 in
34750
Height measured from bottom of base to top of enclosure.
No Load
Full Load
OPU
89 dBA
92 dBA
Level 1
87 dBA
90 dBA
Level 2
N/A
N/A
Level 3
79 dBA
81 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
MD1250-01 3
Diesel Product Line 1250 kWe / 1150 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base.
Double Wall UL Listed 142 Fuel Tanks 12 Hour (1250 Gallons)
24 Hour (2500 Gallons)
48 Hour (5000 Gallons)
A
B
C
A
B
C
A
B
C
OPU
CF
CF
CF
CF
CF
CF
CF
CF
CF
Level 1
240.00
106.00
18.00
240.00
106.00
34.00
410.00
106.00
36.00
Level 2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Level 3
CF
CF
CF
CF
CF
CF
CF
CF
CF
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
MD1250-01 4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
MD1600-01 1600 kWe / 1450 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
CF
CF
743RSL4052
743RSS4290
Connection
4 LEAD WYE
4 LEAD DELTA
4 LEAD WYE
4 LEAD WYE
kWe
1600
1600
1600
1600
AMPS
5558
4817
2408
1927
Temp Rise
CF
CF
130˚C / 27˚C
130˚C / 27˚C
kWe
1450
1450
1450
1450
AMPS
5037
4365
2183
1746
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Structural Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Critical
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Exhaust
Governor
105˚C
Prime Temperature Rise
Battery
24V
Battery System & Cables
100%
of Rated Load - One Step
SAE
Flywheel Housing
5%
Jacket
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Grade Silencer Loose Flex Connector
Charger 24V 5 Amp
Water Heater -20˚F 2 Qty: 9000W 240V w/Isolation Valves
Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
MD1250-01 1
Diesel Product Line 1600 kWe / 1450 kWe
Application Data Engine Manufacturer:
Mitsubishi
Displacement - Cu. In. (lit):
Model: S16R-Y2PTAW-1
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Turbo Charged, H2O/Air Intercooled
Cylinder Arrangement:
16 Cylinder Vee
3,989 (65.4) 6.69 (17.0) x 7.09 (18.0)
Max HP Stby (kWm):
14.5:1 1800 2,346 (1,750)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
940 (504)
890 (477)
Gas Volume at Stack Temp: CFM (m³/min)
15,642 (443)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
23.6 (5.9)
23.6 (5.9)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
489 (1,851)
489 (1,851)
Heat Rejection to Coolant: BTUM (kW)
36,167 (633)
32,563 (570)
Heat Rejection to Intercooler: BTUM (kW)
36,167 (633)
32,563 (570)
Heat Radiated to Ambient: BTUM (kW)
8,652 (151)
7,841 (137)
Aspirating: CFM (m³/min)
5,932 (168)
5,5332 (151)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
99,909 (2,827)
14,089 (399)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
99,909 (2,827)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
129.2 (487)
115.4 (436)
At 75% of Power Rating: gal/hr (lit/hr)
94.1 (356)
86.8 (325)
At 50% of Power Rating: gal/hr (lit/hr)
64.4 (241)
58.7 (220)
Total Oil System: gal (lit)
52.8 (200)
52.8 (200)
Engine Jacket Water Capacity w/Intercooler: gal (lit)
44.9 (170)
44.9 (170)
System Coolant Capacity: gal (lit)
97.0 (367)
97.0 (367)
Fluids Capacity
Deration Factors Altitude: Derate 0.5% per 328 ft (100 m) above 3280 ft (1000 m) standby and prime. | Temperature: Derate 1.0% per 18oF (10oC) above 104oF (40oC) standby and prime. Consult factory for site conditions above these parameters.
MD1600-01 2
Diesel Product Line 1600 kWe / 1450 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
250 x 94 x 119 in
30,150
Level 1
265 x 110 x 135 in
35,850
Level 2
N/A
N/A
Level 3
CF
CF
Height measured from bottom of base to top of enclosure.
No Load
Full Load
OPU
90 dBA
92 dBA
Level 1
88 dBA
91 dBA
Level 2
N/A
N/A
Level 3
CF
CF
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
MD1600-01 3
Diesel Product Line 1600 kWe / 1450 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base.
Double Wall UL Listed 142 Fuel Tanks 12 Hour (1925 Gallons)
24 Hour (3850 Gallons)
48 Hour (7700 Gallons)
A
B
C
A
B
C
A
B
C
OPU
CF
CF
CF
CF
CF
CF
CF
CF
CF
Level 1
265.00
110.00
22.00
300.00
110.00
36.00
565.00
110.00
36.00
Level 2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Level 3
CF
CF
CF
CF
CF
CF
CF
CF
CF
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
MD1600-01 4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
MD2000-01 2000 kWe / 1850 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
CF
CF
744RSL4054
743RSS4292
Connection
4 LEAD WYE
4 LEAD DELTA
4 LEAD WYE
4 LEAD WYE
kWe
2000
2000
2000
2000
AMPS
6948
6021
3011
2408
Temp Rise
CF
CF
130˚C / 27˚C
130˚C / 27˚C
kWe
1850
1850
1850
1850
AMPS
6426
5569
2785
2228
Temp Rise
CF
CF
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Structural Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Critical
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Exhaust
Governor
105˚C
Prime Temperature Rise
Battery
24V
Battery System & Cables
100%
of Rated Load - One Step
SAE
Flywheel Housing
5%
Jacket
Air
- Electronic Isochronous
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Grade Silencer Loose Flex Connector
Charger 24V 5 Amp
Water Heater -20˚F 2 Qty: 9000W 240V w/Isolation Valves
Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
MD2000-01 1
Diesel Product Line 2000 kWe / 1850 kWe
Application Data Engine Manufacturer:
Mitsubishi
Displacement - Cu. In. (lit):
Model: S16R-Y2PTAW2-1
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Turbo Charged, H2O/Air Intercooled
Cylinder Arrangement:
16 Cylinder Vee
3,989 (65.4) 6.69 (17.0) x 7.09 (18.0) 14.5:1 1800
Max HP Stby (kWm):
2,923 (2,181)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
979 (526)
882 (472)
Gas Volume at Stack Temp: CFM (m³/min)
19,209 (544)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
23.6 (5.9)
23.6 (5.9)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
489 (1,851)
489 (1,851)
Heat Rejection to Coolant: BTUM (kW)
44,374 (777)
39,937 (699)
Heat Rejection to Intercooler: BTUM (kW)
44,374 (777)
39,937 (699)
Heat Radiated to Ambient: BTUM (kW)
11,384 (199)
10,530 (184)
Aspirating: CFM (m³/min)
7,274 (206)
6,532 (185)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
111,214 (3,147)
17,302 (490)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
111,214 (3,147)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
160.1 (606)
141.5 (535)
At 75% of Power Rating: gal/hr (lit/hr)
116.7 (442)
106.6 (403)
At 50% of Power Rating: gal/hr (lit/hr)
79.0 (299)
71.7 (272)
Total Oil System: gal (lit)
52.8 (200)
52.8 (200)
Engine Jacket Water Capacity w/Intercooler: gal (lit)
44.9 (170)
44.9 (170)
System Coolant Capacity: gal (lit)
104 (394)
104 (394)
Fluids Capacity
Deration Factors Altitude: Derate 0.5% per 328 ft (100 m) above 3280 ft (1000 m) standby and prime. | Temperature: Derate 1.0% per 18oF (10oC) above 104oF (40oC) standby and prime. Consult factory for site conditions above these parameters.
MD2000-01 2
Diesel Product Line 2000 kWe / 1850 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
255 x 110 x 130 in
32,200
Level 1
265 x 110 x 145 in
39,000
Level 2
N/A
N/A
Level 3
CF
CF
Height measured from bottom of base to top of enclosure.
No Load
Full Load
OPU
91 dBA
95 dBA
Level 1
90 dBA
94 dBA
Level 2
N/A
N/A
Level 3
CF
CF
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
MD2000-01 3
Diesel Product Line 2000 kWe / 1850 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base.
Double Wall UL Listed 142 Fuel Tanks 12 Hour (1925 Gallons)
24 Hour (3850 Gallons)
48 Hour (7700 Gallons)
A
B
C
A
B
C
A
B
C
OPU
CF
CF
CF
CF
CF
CF
CF
CF
CF
Level 1
265.00
110.00
22.00
300.00
110.00
36.00
565.00
110.00
36.00
Level 2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Level 3
CF
CF
CF
CF
CF
CF
CF
CF
CF
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
MD2000-01 4
ENGINEERING GUIDE Specification Sheets | Diesel Product Line 60 Hz 1800 RPM IT4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD60-04IT4 60 kWe / 60 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
362CSL1604
361CSL1602
361CSL1602
361CSL1602
361PSL1634
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
60
60
60
60
60
AMPS
250
208
180
90
72
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
60
60
60
60
60
AMPS
250
208
180
90
72
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Formed Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 12V 6 Amp Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD60-04IT4 1
Diesel Product Line 60 kWe / 60 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045HFG92
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 4 Cylinder Inline
Max HP Stby (kWm):
275 (4.5) 4.2 (10.6) x 5.0 (12.7) 16.1:1 1800 107 (80)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
835 (446)
835 (446)
Gas Volume at Stack Temp: CFM (m³/min)
399 (11.3)
399 (11.3)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
68.0 (17.0)
68.0 (17.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
65.0 (245)
65.0 (245)
Heat Rejection to Coolant: BTUM (kW)
2,960 (51.8)
Heat Rejection to CAC: BTUM (kW)
455 (7.96)
Heat Radiated to Ambient: BTUM (kW)
1,025 (18.0)
Cooling System
2,960 (51.8) 455 (7.96) 1,025 (18.0)
Air Requirements Aspirating: CFM (m³/min)
180 (5.09)
180 (5.09)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
7,330 (207)
7,330 (207)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
5.33 (20.2)
5.33 (20.2)
At 75% of Power Rating: gal/hr (lit/hr)
4.09 (15.5)
4.09 (15.5)
At 50% of Power Rating: gal/hr (lit/hr)
2.83 (10.7)
2.83 (10.7)
Total Oil System: gal (lit)
3.8 (14.7)
3.8 (14.7)
Engine Jacket Water Capacity: gal (lit)
2.25 (8.5)
2.25 (8.5)
System Coolant Capacity: gal (lit)
6.1 (23.1)
6.1 (23.1)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD60-04IT4 2
Diesel Product Line 60 kWe / 60 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
84 x 44 x 59 in
2432
Level 1
84 x 44 x 72 in
2953
Level 2
84 x 44 x 82 in
3212
Level 3
116 x 44 x 78 in
3326
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
73 dBA
77 dBA
Level 1
70 dBA
72 dBA
Level 2
69 dBA
71 dBA
Level 3
62 dBA
65 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD60-04IT4 3
Diesel Product Line 60 kWe / 60 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (120 Gallon)
48 Hour (240 Gallon)
72 Hour (360 Gallon)
A
B
C
A
B
C
A
B
C
OPU
84.00
44.00
14.00
84.00
44.00
28.00
90.00
44.00
36.00
Level 1
84.00
44.00
14.00
84.00
44.00
28.00
90.00
44.00
36.00
Level 2
84.00
44.00
14.00
84.00
44.00
28.00
90.00
44.00
36.00
Level 3
116.00
44.00
10.00
116.00
44.00
18.00
116.00
44.00
26.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD60-04IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD80-04IT4 80 kWe / 80 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
363CSL1607
362CSL1606
362CSL1606
362CSL1604
362PSL1635
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
80
80
80
80
80
AMPS
333
278
240
120
96
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
80
80
80
80
80
AMPS
333
278
240
120
96
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Formed Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 12V 6 Amp Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD80-03IT4 1
Diesel Product Line 80 kWe / 80 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045HFG92
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 4 Cylinder Inline
Max HP Stby (kWm):
275 (4.5) 4.2 (10.6) x 5.0 (12.7) 16.1:1 1800 133 (99)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
855 (457)
855 (457)
Gas Volume at Stack Temp: CFM (m³/min)
494 (14.0)
494 (14.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
68.0 (17.0)
68.0 (17.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
65 (245)
65.0 (245)
Heat Rejection to Coolant: BTUM (kW)
3,586 (62.8)
Heat Rejection to CAC: BTUM (kW)
740 (13.0)
740 (13.0)
Heat Radiated to Ambient: BTUM (kW)
911 (15.9)
911 (15.9)
Aspirating: CFM (m³/min)
222 (6.3)
222 (6.3)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
7,254 (205)
Cooling System
3,586 (62.8)
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
7,254 (205)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
6.5 (24.6)
6.5 (24.6)
At 75% of Power Rating: gal/hr (lit/hr)
4.9 (18.5)
4.9 (18.5)
At 50% of Power Rating: gal/hr (lit/hr)
3.4 (12.9)
3.4 (12.9)
Total Oil System: gal (lit)
3.9 (14.7)
3.9 (14.7)
Engine Jacket Water Capacity: gal (lit)
2.2 (8.5)
2.2 (8.5)
System Coolant Capacity: gal (lit)
6.1 (23.1)
6.1 (23.1)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD80-03IT4 2
Diesel Product Line 80 kWe / 80 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
84 x 44 x 59 in
2575
Level 1
84 x 44 x 72 in
3025
Level 2
84 x 44 x 82 in
3350
Level 3
116 x 44 x 78 in
3475
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
74 dBA
78 dBA
Level 1
70 dBA
73 dBA
Level 2
68 dBA
71 dBA
Level 3
63 dBA
66 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD80-03IT4 3
Diesel Product Line 80 kWe / 80 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (175 Gallon)
48 Hour (350 Gallon)
72 Hour (525 Gallon)
A
B
C
A
B
C
A
B
C
OPU
84.00
44.00
20.00
84.00
44.00
36.00
160.00
44.00
36.00
Level 1
84.00
44.00
20.00
84.00
44.00
36.00
160.00
44.00
36.00
Level 2
84.00
44.00
20.00
84.00
44.00
36.00
160.00
44.00
36.00
Level 3
116.00
44.00
14.00
116.00
44.00
26.00
160.00
44.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD80-03IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD100-02IT4 100 kWe / 90 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
363CSL3133
362CSL1606
362CSL1606
363CSL1606
362PSL1636
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
100
100
100
100
100
AMPS
417
347
300
150
120
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
90
90
90
90
90
AMPS
375
313
270
135
108
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Formed Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 12V 6 Amp Water Heater -20˚F 1500W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD100-02IT4 1
Diesel Product Line 100 kWe / 90 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 4045HFG93
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 4 Cylinder Inline
Max HP Stby (kWm):
275 (4.5) 4.2 (10.6) x 5.0 (12.7) 16.5:1 1800 166 (124)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
871 (466)
871 (466)
Gas Volume at Stack Temp: CFM (m³/min)
593 (16.8)
593 (16.8)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
68.0 (17.0)
68.0 (17.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
65.0 (245)
65.0 (245)
Heat Rejection to Coolant: BTUM (kW)
4,269 (75.0)
4,269 (75.0)
Heat Rejection to CAC: BTUM (kW)
1,025 (17.9)
1,019 (17.9)
Heat Radiated to Ambient: BTUM (kW)
1,138 (19.9)
1,138 (19.9)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
268 (7.6)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
7,562 (132)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
268 (7.6) 7,562 (132)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
8.1 (30.7)
7.4 (28.0)
At 75% of Power Rating: gal/hr (lit/hr)
6.2 (23.5)
6.0 (22.7)
At 50% of Power Rating: gal/hr (lit/hr)
4.2 (15.9)
3.8 (14.4)
Total Oil System: gal (lit)
4.0 (15.0)
4.0 (15.0)
Engine Jacket Water Capacity: gal (lit)
2.3 (8.5)
2.3 (8.5)
System Coolant Capacity: gal (lit)
5.5 (20.8)
5.5 (20.8)
Fluids Capacity
Deration Factors Rated Power is available up to 5500 ft (1676 m) standby and 7500ft (2286 m) prime at ambient temperatures to 122°F (50°C). Consult factory for site conditions above these parameters.
JD100-02IT4 2
Diesel Product Line 100 kWe / 90 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
100 x 44 x 61 in
2925
Level 1
100 x 44 x 74 in
3400
Level 2
100 x 44 x 92 in
3600
Level 3
132 x 44 x 84 in
3875
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
76 dBA
79 dBA
Level 1
73 dBA
76 dBA
Level 2
71 dBA
74 dBA
Level 3
67 dBA
70 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD100-02IT4 3
Diesel Product Line 100 kWe / 90 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (250 Gallon)
48 Hour (500 Gallon)
72 Hour (750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 1
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 2
100.00
44.00
22.00
115.00
44.00
36.00
165.00
44.00
36.00
Level 3
132.00
44.00
18.00
132.00
44.00
30.00
165.00
44.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD100-02IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD150-02IT4 150 kWe / 135 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
431CSL6206
431CSL6202
431CSL6202
431CSL6202
431PSL6240
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
150
150
150
150
150
AMPS
625
521
452
226
181
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
135
135
135
135
135
AMPS
563
469
406
203
163
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Formed Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 12V 6 Amp Water Heater -20˚F 2000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD150-02IT4 1
Diesel Product Line 150 kWe / 135 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6068HFG94
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
Max HP Stby (kWm):
415 (6.8) 4.2 (10.6) x 5.0 (12.7) 17.2:1 1800 241 (180)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
765 (407)
765 (407)
Gas Volume at Stack Temp: CFM (m³/min)
812 (23.0)
812 (23.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
68 (17.0)
68 (17.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
124 (468)
124 (468)
Heat Rejection to Coolant: BTUM (kW)
6,887 (121)
6,887 (121)
Heat Rejection to CAC: BTUM (kW)
1,981 (34.8)
1,981 (34.8)
Heat Radiated to Ambient: BTUM (kW)
2,348 (41.1)
2,348 (41.1)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
399 (11.3)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
12,520 (354)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
399 (11.3) 12,520 (354)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
11.8 (44.3)
10.6 (40.3)
At 75% of Power Rating: gal/hr (lit/hr)
8.8 (33.3)
8.0 (30.4)
At 50% of Power Rating: gal/hr (lit/hr)
6.1 (23.1)
5.6 (21.3)
Total Oil System: gal (lit)
8.6 (32.5)
8.6 (32.5)
Engine Jacket Water Capacity: gal (lit)
3.1 (11.9)
3.1 (11.9)
System Coolant Capacity: gal (lit)
10.2 (38.6)
10.2 (38.6)
Fluids Capacity
Deration Factors Rated Power is available up to 10,000 ft (3048 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD150-02IT4 2
Diesel Product Line 150 kWe / 135 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
110 x 48 x 71 in
3775
Level 1
110 x 48 x 81 in
4525
Level 2
110 x 48 x 100 in
4825
Level 3
150 x 48 x 92 in
5100
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
79 dBA
83 dBA
Level 1
78 dBA
82 dBA
Level 2
77 dBA
81 dBA
Level 3
68 dBA
71 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD150-02IT4 3
Diesel Product Line 150 kWe / 135 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (375 Gallon)
48 Hour (750 Gallon)
72 Hour (1125 Gallon)
A
B
C
A
B
C
A
B
C
OPU
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 1
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 2
110.00
48.00
26.00
150.00
48.00
36.00
230.00
48.00
36.00
Level 3
150.00
48.00
18.00
150.00
48.00
36.00
230.00
48.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD150-02IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD200-02IT4 200 kWe / 180 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
432CSL6210
431CSL6206
431CSL6206
431CSL6206
431PSL6243
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
200
200
200
200
200
AMPS
833
695
602
301
241
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
180
180
180
180
180
AMPS
750
625
542
271
217
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Formed Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 12V 6 Amp Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD200-02IT4 1
Diesel Product Line 200 kWe / 180 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
549 (9.0)
Model: 6090HFG94
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
16:1
Aspiration:
Rated RPM:
1800
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
Max HP Stby (kWm):
4.66 (11.8) x 5.35 (13.6)
318 (237)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
762 (406)
762 (406)
Gas Volume at Stack Temp: CFM (m³/min)
1,172 (33.2)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40 (10.1)
40 (10.1)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
127 (480)
127 (480)
Heat Rejection to Coolant: BTUM (kW)
8,350 (147)
8,350 (147)
Heat Rejection to CAC: BTUM (kW)
2,732 (48.0)
2,732 (48.0)
Heat Radiated to Ambient: BTUM (kW)
3,130 (55.0)
3,130 (55.0)
1,172 (33.2)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
565 (16.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
20,602 (583)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
565 (16.0) 20,602 (583)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
15.5 (58.7)
13.9 (52.8)
At 75% of Power Rating: gal/hr (lit/hr)
11.6 (43.9)
10.8 (40.9)
At 50% of Power Rating: gal/hr (lit/hr)
8.2 (31.0)
7.5 (28.5)
Total Oil System: gal (lit)
8.2 (31.0)
8.2 (31.0)
Engine Jacket Water Capacity: gal (lit)
4.5 (17.0)
4.5 (17.0)
System Coolant Capacity: gal (lit)
13.2 (50.0)
13.2 (50.0)
Fluids Capacity
Deration Factors Rated Power is available up to 5500 ft (1676 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD200-02IT4 2
Diesel Product Line 200 kWe / 180 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
130 x 62 x 79 in
6050
Level 1
130 x 62 x 100 in
7050
Level 2
130 x 62 x 114 in
7475
Level 3
190 x 62 x 106 in
7925
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
78 dBA
82 dBA
Level 1
76 dBA
80 dBA
Level 2
75 dBA
78 dBA
Level 3
67 dBA
70 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD200-02IT4 3
Diesel Product Line 200 kWe / 180 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (475 Gallon)
48 Hour (950 Gallon)
72 Hour (1425 Gallon)
A
B
C
A
B
C
A
B
C
OPU
130.00
62.00
22.00
150.00
62.00
36.00
210.00
62.00
36.00
Level 1
130.00
62.00
22.00
150.00
62.00
36.00
210.00
62.00
36.00
Level 2
130.00
62.00
22.00
150.00
62.00
36.00
210.00
62.00
36.00
Level 3
190.00
62.00
14.00
190.00
62.00
28.00
210.00
62.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD200-02IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD250-03IT4 250 kWe / 230 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4025
432CSL6210
432CSL6210
432CSL6210
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
250
250
250
250
250
AMPS
1041
868
753
376
301
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
230
230
230
230
230
AMPS
958
799
692
346
277
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Formed Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 12V 6 Amp Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD250-03IT4 1
Diesel Product Line 250 kWe / 230 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
549 (9.0)
Model: 6090HFG95
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
16:1
Aspiration:
Rated RPM:
1800
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
Max HP Stby (kWm):
4.66 (11.8) x 5.35 (13.6)
398 (297)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
716 (380)
716 (380)
Gas Volume at Stack Temp: CFM (m³/min)
1483 (42.0)
1483 (42.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
41.0 (10.3)
41.0 (10.3)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
107 (405)
107 (405)
Heat Rejection to Coolant: BTUM (kW)
10,194 (179)
10,194 (179)
Heat Rejection to CAC: BTUM (kW)
4,952 (87.0)
4,952 (87.0)
Heat Radiated to Ambient: BTUM (kW)
2,312 (40.5)
2,127 (37.2)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
742 (21.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
22,302 (631)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
742 (21.0) 22,302 (631)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
19.1 (72.4)
13.9 (52.8)
At 75% of Power Rating: gal/hr (lit/hr)
13.9 (52.7)
10.8 (40.9)
At 50% of Power Rating: gal/hr (lit/hr)
9.7 (36.7)
7.5 (28.5)
Total Oil System: gal (lit)
9.0 (34.0)
9.0 (34.0)
Engine Jacket Water Capacity: gal (lit)
4.5 (17.0)
4.5 (17.0)
System Coolant Capacity: gal (lit)
13.2 (50.0)
13.2 (50.0)
Fluids Capacity
Deration Factors Rated Power is available up to 5500 ft (1676 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD250-03IT4 2
Diesel Product Line 250 kWe / 230 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
130 x 62 x 81 in
6500
Level 1
130 x 62 x 100 in
7500
Level 2
130 x 62 x 114 in
7950
Level 3
190 x 62 x 106 in
8400
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
78 dBA
82 dBA
Level 1
76 dBA
80 dBA
Level 2
75 dBA
78 dBA
Level 3
67 dBA
70 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD250-03IT4 3
Diesel Product Line 250 kWe / 230 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (475 Gallon)
48 Hour (950 Gallon)
72 Hour (1425 Gallon)
A
B
C
A
B
C
A
B
C
OPU
130.00
62.00
22.00
150.00
62.00
36.00
210.00
62.00
36.00
Level 1
130.00
62.00
22.00
150.00
62.00
36.00
210.00
62.00
36.00
Level 2
130.00
62.00
22.00
150.00
62.00
36.00
210.00
62.00
36.00
Level 3
190.00
62.00
14.00
190.00
62.00
28.00
210.00
62.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD250-03IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD275-03IT4 275 kWe / 260 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4027
432CSL6210
432CSL6210
432CSL6210
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
275
275
275
275
275
AMPS
1146
955
828
414
331
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
260
260
260
260
260
AMPS
1083
903
782
391
313
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Formed Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
12V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 12V 6 Amp Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD275-03IT4 1
Diesel Product Line 275 kWe / 260 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
549 (9.0)
Model: 6090HFG95
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
16:1
Aspiration:
Rated RPM:
1800
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
Max HP Stby (kWm):
4.66 (11.8) x 5.35 (13.6)
440 (328)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
846 (452)
846 (452)
Gas Volume at Stack Temp: CFM (m³/min)
1730 (49.0)
1730 (49.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
41.0 (10.3)
41.0 (10.3)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
107 (405)
107 (405)
Heat Rejection to Coolant: BTUM (kW)
11,020 (194)
Heat Rejection to CAC: BTUM (kW)
5,635 (99)
Heat Radiated to Ambient: BTUM (kW)
2,544 (44.5)
Cooling System
11,020 (194) 5,635 (99) 2,544 (44.5)
Air Requirements Aspirating: CFM (m³/min)
812 (23.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
21,883 (619)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
812 (23.0) 21,883 (619)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
22.0 (83.3)
18.7 (70.8.8)
At 75% of Power Rating: gal/hr (lit/hr)
15.4 (58.3)
14.1 (53.4)
At 50% of Power Rating: gal/hr (lit/hr)
10.7 (40.5)
9.6 (36.3)
Total Oil System: gal (lit)
8.2 (31.0)
9.0 (34.0)
Engine Jacket Water Capacity: gal (lit)
4.5 (17.0)
4.5 (17.0)
System Coolant Capacity: gal (lit)
14.3 (54.1)
14.3 (54.1)
Fluids Capacity
Deration Factors Rated Power is available up to 5500 ft (1676 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD275-03IT4 2
Diesel Product Line 275 kWe / 260 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
130 x 62 x 81 in
6500
Level 1
130 x 62 x 100 in
7500
Level 2
130 x 62 x 114 in
7950
Level 3
190 x 62 x 106 in
8400
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
80 dBA
84 dBA
Level 1
79 dBA
83 dBA
Level 2
77 dBA
80 dBA
Level 3
68 dBA
71 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD275-03IT4 3
Diesel Product Line 275 kWe / 260 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (550 Gallon)
48 Hour (1100 Gallon)
72 Hour (1650 Gallon)
A
B
C
A
B
C
A
B
C
OPU
130.00
62.00
24.00
165.00
62.00
36.00
234.00
62.00
36.00
Level 1
130.00
62.00
24.00
165.00
62.00
36.00
234.00
62.00
36.00
Level 2
130.00
62.00
24.00
165.00
62.00
36.00
234.00
62.00
36.00
Level 3
190.00
62.00
16.00
190.00
62.00
30.00
234.00
62.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD275-03IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD300-03IT4 300 kWe / 265 kWe
Standby / Prime
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4029
433CSL6216
433CSL6216
432CSL6212
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
300
300
300
300
300
AMPS
1250
1042
904
452
361
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
265
265
265
265
265
AMPS
1104
921
798
399
319
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Structural Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 24V 5 Amp Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD300-03IT4 1
Diesel Product Line 300 kWe / 265 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6135HFG95
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
Max HP Stby (kWm):
824 (13.5) 5.2 (13.2) x 6.5 (16.5) 15.3:1 1800 477 (356)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
705 (374)
705 (374)
Gas Volume at Stack Temp: CFM (m³/min)
1670 (47.3)
1670 (47.3)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
68.0 (17.0)
68.0 (17.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
204 (774)
204 (774)
Heat Rejection to Coolant: BTUM (kW)
13,877 (243.8)
Heat Rejection to CAC: BTUM (kW)
4,377 (76.9)
4,377 (76.9)
Heat Radiated to Ambient: BTUM (kW)
2,775 (48.6)
2,451 (42.9)
Cooling System
13,877 (243.8)
Air Requirements Aspirating: CFM (m³/min)
858 (24.3)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
36,563 (1,034)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
858 (24.3) 36,563 (1,034)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
23.1 (87.4)
21.0 (79.3)
At 75% of Power Rating: gal/hr (lit/hr)
17.7 (66.9)
16.1 (60.9)
At 50% of Power Rating: gal/hr (lit/hr)
12.5 (47.3)
11.42 (43.2)
Total Oil System: gal (lit)
15.9 (60.0)
15.9 (60.0)
Engine Jacket Water Capacity: gal (lit)
6.6 (25.0)
6.6 (25.0)
System Coolant Capacity: gal (lit)
18.7 (70.8)
18.7 (70.8)
Fluids Capacity
Deration Factors Rated Power is available up to 10,114 ft (3082 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD300-03IT4 2
Diesel Product Line 300 kWe / 265 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
140 x 66 x 91 in
8275
Level 1
140 x 66 x 111 in
9250
Level 2
140 x 66 x 125 in
9725
Level 3
195 x 66 x 114 in
10,200
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
80 dBA
86 dBA
Level 1
79 dBA
83 dBA
Level 2
78 dBA
81 dBA
Level 3
68 dBA
72 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD300-03IT4 3
Diesel Product Line 300 kWe / 265 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (640 Gallon)
48 Hour (1280 Gallon)
72 Hour (2250 Gallon)
A
B
C
A
B
C
A
B
C
OPU
140.00
66.00
24.00
180.00
66.00
36.00
252.00
66.00
36.00
Level 1
140.00
66.00
24.00
180.00
66.00
36.00
252.00
66.00
36.00
Level 2
140.00
66.00
24.00
180.00
66.00
36.00
252.00
66.00
36.00
Level 3
195.00
66.00
16.00
195.00
66.00
32.00
252.00
66.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD300-03IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD365-02IT4 365 kWe / 325 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
433CSL6216
433CSL6216
433CSL6216
432PSL6248
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
365
365
365
365
AMPS
1267
1098
549
440
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
325
325
325
325
AMPS
1129
978
489
391
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Structural Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 24V 5 Amp Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD365-02IT4 1
Diesel Product Line 365 kWe / 325 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6135HFG95
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
Max HP Stby (kWm):
824 (13.5) 5.2 (13.2) x 6.5 (16.5) 15.3:1 1800 551 (411)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
700 (371)
700 (371)
Gas Volume at Stack Temp: CFM (m³/min)
1,925 (54.5)
1,925 (54.5)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
68.0 (17.0)
68.0 (17.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
204 (774)
204 (774)
Heat Rejection to Coolant: BTUM (kW)
15,499 (272)
15,499 (272)
Heat Rejection to CAC: BTUM (kW)
5,777 (101.5)
5,777 (101.5)
Heat Radiated to Ambient: BTUM (kW)
3,116 (54.5)
3,116 (54.5)
Cooling System
Air Requirements Aspirating: CFM (m³/min)
996 (28.2)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
34,970 (990)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
996 (28.2) 34,970 (990)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
26.6 (100.7)
23.9 (90.4)
At 75% of Power Rating: gal/hr (lit/hr)
20.1 (76.1)
18.2 (68.9)
At 50% of Power Rating: gal/hr (lit/hr)
14.0 (53.2)
12.9 (48.9)
Total Oil System: gal (lit)
15.9 (60.0)
15.9 (60.0)
Engine Jacket Water Capacity: gal (lit)
6.6 (25.0)
6.6 (25.0)
System Coolant Capacity: gal (lit)
25.4 (96.0)
25.4 (96.0)
Fluids Capacity
Deration Factors Rated Power is available up to 8800 ft (2682 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD365-02IT4 2
Diesel Product Line 365 kWe / 325 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
140 x 66 x 91 in
8825
Level 1
140 x 66 x 111 in
9825
Level 2
140 x 66 x 125 in
10,300
Level 3
195 x 66 x 114 in
10,750
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
82 dBA
88 dBA
Level 1
81 dBA
85 dBA
Level 2
80 dBA
83 dBA
Level 3
70 dBA
74 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD365-02IT4 3
Diesel Product Line 365 kWe / 325 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (750 Gallon)
48 Hour (1500 Gallon)
72 Hour (2250 Gallon)
A
B
C
A
B
C
A
B
C
OPU
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 1
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 2
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 3
195.00
66.00
20.00
200.00
66.00
36.00
294.00
66.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD365-02IT4
Rev1.0
4
Diesel Product Line
208-600 Volt 60 Hz / 1800 RPM
JD415-02IT4 415 kWe / 375 kWe
Standby / Prime
Ratings 208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
572RSL4025
572RSL4025
433CSL6220
572RSS4270
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
415
415
415
415
AMPS
1442
1250
625
500
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
375
375
375
375
AMPS
1303
1129
564
452
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment Engine
Additional
Generator
Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Voltage Regulator
Based Digital Control
Blower
Fan & Fan Drive
Automatic
Base
- Structural Steel
Starter
& Alternator
±
1.0% Voltage Regulation
Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
Battery
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
105˚C
Prime Temperature Rise of Rated Load - One Step
Governor
- Electronic Isochronous
24V
Battery System & Cables
100%
SAE
Flywheel & Housing
5%
Air
Cleaner (Dry Single Stage)
Exhaust
Particulate Filter / Silencer Mtd
Flexible
Fuel Connectors
EPA
Certified - Tier IT4
Maximum Harmonic Content
NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Charger 24V 5 Amp Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts (Pad Type)
Radiator
Duct Flange (OPU Only)
Single
Source Supplier
2YR
/ 2000HR Standby Warranty
1YR
/ 1500HR Prime Warranty
Standard
Colors - White / Tan / Gray
JD415-02IT4 1
Diesel Product Line 415 kWe / 375 kWe
Application Data Engine Manufacturer:
John Deere
Displacement - Cu. In. (lit):
Model: 6135HFG95
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
Max HP Stby (kWm):
824 (13.5) 5.2 (13.2) x 6.5 (16.5) 15.3:1 1800 634 (473)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
700 (371)
700 (371)
Gas Volume at Stack Temp: CFM (m³/min)
2,133 (60.4)
2,133 (60.4)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
68.0 (17.0)
68.0 (17.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
204 (774)
204 (774)
Heat Rejection to Coolant: BTUM (kW)
17,440 (306)
17,440 (306)
Heat Rejection to CAC: BTUM (kW)
7,195 (126)
7,195 (126)
Heat Radiated to Ambient: BTUM (kW)
3,543 (62.0)
3,202 (56.0)
Aspirating: CFM (m³/min)
1,098 (31.1)
1,098 (31.1)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
34,703 (983)
34,703 (983)
Cooling System
Air Requirements.0
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption At 100% of Power Rating: gal/hr (lit/hr)
30.7 (116.2)
27.4 (103.5)
At 75% of Power Rating: gal/hr (lit/hr)
22.8 (86.3)
20.6 (78.2)
At 50% of Power Rating: gal/hr (lit/hr)
15.9 (60.1)
14.5 (54.9)
Total Oil System: gal (lit)
15.9 (60.0)
15.9 (60.0)
Engine Jacket Water Capacity: gal (lit)
6.6 (25.0)
6.6 (25.0)
System Coolant Capacity: gal (lit)
23.7 (89.7)
23.7 (89.7)
Fluids Capacity
Deration Factors Rated Power is available up to 8800 ft (2682 m) at ambient temperatures to 122°F (50°C) standby and prime. Consult factory for site conditions above these parameters.
JD415-02IT4 2
Diesel Product Line 415 kWe / 375 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
140 x 66 x 91 in
8825
Level 1
140 x 66 x 111 in
9825
Level 2
140 x 66 x 125 in
10,300
Level 3
195 x 66 x 114 in
10,750
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
83 dBA
89 dBA
Level 1
82 dBA
86 dBA
Level 2
81 dBA
84 dBA
Level 3
71 dBA
74 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD415-02IT4 3
Diesel Product Line 415 kWe / 375 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks 24 Hour (750 Gallon)
48 Hour (1500 Gallon)
72 Hour (2250 Gallon)
A
B
C
A
B
C
A
B
C
OPU
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 1
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 2
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 3
195.00
66.00
20.00
200.00
66.00
36.00
294.00
66.00
36.00
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Distributed By:
Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
JD415-02IT4
Rev1.0
4
ENGINEERING GUIDE Specification Sheets | Gaseous Product Line 60 Hz 1800 RPM
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
GM25-02 25 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
283PSL1707
283PSL1706
283PSL1706
283PSL1706
283PSL5250
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
25 (25)
25 (25)
25 (25)
25 (25)
25 (25)
AMPS Nat (LP)
104 (104)
87 (87)
75 (75)
38 (38)
30 (30)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Certified
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Certified
Starter
& Alternator
±
1% Voltage Regulation
Microprocessor
Pole, Rotating Field
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Based Digital Control
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
100%
of Rated Load - One Step
Critical
Grade Silencer Mounted
Battery
Charger 12V 6 Amp
Governor
- Electronic Isochronous
12V
Battery System & Cables
5%
SAE
Flywheel & Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1000W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
GM25-02
Colors - White / Tan / Gray
1
Gaseous Product Line 25 kWe
Application Data Engine Manufacturer: Model:
General Motors GM 3.0L EPA
Type:
4-Cycle
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm): Compression Ratio:
Aspiration: Natural
Rated RPM:
Cylinder Arrangement:
Max HP Stby (kWm):
4 Cylinder Inline
181 (3.0) 4.0 (10.2) x 3.6 (9.1) 9.3 : 1 1800 50.8 (37.9)
Exhaust System Gas Temp. (Stack): °F (°C)
1,220 (660)
Gas Volume at Stack Temp: CFM (m³/min)
220 (6.23)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
16.8 (63.6)
Heat Rejection to Coolant: BTUM (kW)
1,436 (25.1)
Heat Rejection to CAC: BTUM (kW)
N/A
Heat Radiated to Ambient: BTUM (kW)
326 (5.70)
Air Requirements Aspirating: CFM (m³/min)
44.3 (2.67)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
4,752 (135)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
Consult Factory For Remote Cooled Applications
Natural Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
431 (12.2)
184 (5.21)
At 75% of Power Rating: ft3/hr (m3/hr)
339 (9.59)
140 (3.96)
At 50% of Power Rating: ft3/hr (m3/hr)
262 (7.41)
104 (2.94)
.75”
.75”
Fuel Inlet Size: NPT
Fluids Capacity Total Oil System: gal (lit)
1.3 (4.90)
Engine Jacket Water Capacity: gal (lit)
1.0 (3.80)
System Coolant Capacity: gal (lit)
3.9 (14.80)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 3% Per 1000ft Over 328ft
GM25-02
2
Gaseous Product Line 25 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
66 x 34 x 44 in
1050
Level 1
66 x 34 x 54 in
1325
Level 2
66 x 34 x 72 in
1425
Level 3
90 x 34 x 64 in
1575
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
76 dBA
78 dBA
Level 1
74 dBA
76 dBA
Level 2
70 dBA
73 dBA
Level 3
65 dBA
67 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
GM25-02
3
Gaseous Product Line 25 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
GM25-02
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
GM40-02 40 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
361CSL1601
284PSL1742
284PSL1742
284PSL1742
284PSL5253
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
40 (40)
40 (40)
40 (40)
40 (40)
40 (40)
AMPS Nat (LP)
167 (167)
139 (139)
120 (120)
60 (60)
48 (48)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Certified
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Certified
Starter
& Alternator
±
1% Voltage Regulation
Microprocessor
Pole, Rotating Field
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Based Digital Control
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
100%
of Rated Load - One Step
Critical
Grade Silencer Mounted
Battery
Charger 12V 6 Amp
Governor
- Electronic Isochronous
12V
Battery System & Cables
5%
SAE
Flywheel & Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1000W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
GM40-02
Colors - White / Tan / Gray
1
Gaseous Product Line 40 kWe
Application Data Engine Manufacturer: Model:
General Motors GM 4.3L EPA
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration: Natural
Rated RPM:
Cylinder Arrangement:
Max HP Stby (kWm):
6 Cylinder Vee
262 (4.30) 4.0 (10.2) x 3.6 (9.1) 9.4 : 1 1800 67 (50)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
330 (9.3)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
36.6 (138.5)
Heat Rejection to Coolant: BTUM (kW)
2,220 (38.9)
Heat Rejection to CAC: BTUM (kW)
N/A
Heat Radiated to Ambient: BTUM (kW)
512 (8.96)
Air Requirements Aspirating: CFM (m³/min)
136.5 (3.86)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
5,157 (146)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
Consult Factory For Remote Cooled Applications
Natural Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
553 (15.7)
23.7 (6.71)
At 75% of Power Rating: ft3/hr (m3/hr)
446 (12.6)
198 (5.62)
At 50% of Power Rating: ft3/hr (m3/hr)
342 (9.69)
152 (4.30)
1.0”
1.0”
Fuel Inlet Size: NPT
Fluids Capacity Total Oil System: gal (lit)
1.3 (4.90)
Engine Jacket Water Capacity: gal (lit)
1.9 (7.30)
System Coolant Capacity: gal (lit)
5.7 (21.6)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 3% Per 1000ft Over 328ft
GM40-02
2
Gaseous Product Line 40 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
80 x 38 x 46 in
1300
Level 1
80 x 38 x 60 in
1650
Level 2
80 x 38 x 76 in
1800
Level 3
110 x 38 x 68 in
2000
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
77 dBA
78 dBA
Level 1
76 dBA
77 dBA
Level 2
71 dBA
74 dBA
Level 3
69 dBA
71 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
GM40-02
3
Gaseous Product Line 40 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
GM40-02
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
GM50-02 50 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
361CSL1602
361CSL1601
361CSL1601
361CSL1601
361PSL1633
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
50 (50)
50 (50)
50 (50)
50 (50)
50 (50)
AMPS Nat (LP)
208 (208)
174 (174)
150 (150)
75 (75)
60 (60)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Certified
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Certified
Starter
& Alternator
±
1% Voltage Regulation
Microprocessor
Pole, Rotating Field
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Based Digital Control
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
100%
of Rated Load - One Step
Critical
Grade Silencer Mounted
Battery
Charger 12V 6 Amp
Governor
- Electronic Isochronous
12V
Battery System & Cables
5%
SAE
Flywheel & Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1000W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
GM50-02
Colors - White / Tan / Gray
1
Gaseous Product Line 50 kWe
Application Data Engine Manufacturer: Model:
General Motors GM 5.0L EPA
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration: Natural
Rated RPM:
Cylinder Arrangement:
Max HP Stby (kWm):
8 Cylinder Vee
305 (5.0) 3.75 (9.5) x 3.48 (8.8) 9.4 : 1 1800 83.4 (62.2)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
380 (10.8)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
36.6 (138.5)
Heat Rejection to Coolant: BTUM (kW)
3,400 (59.5)
Heat Rejection to CAC: BTUM (kW)
N/A
Heat Radiated to Ambient: BTUM (kW)
605 (10.6)
Air Requirements Aspirating: CFM (m³/min)
159 (4.5)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min) Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
7,115 (201) Consult Factory For Remote Cooled Applications
Natural Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
734 (20.8)
308 (8.72)
At 75% of Power Rating: ft3/hr (m3/hr)
614 (17.4)
250 (7.08)
At 50% of Power Rating: ft3/hr (m3/hr)
482 (13.6)
195 (5.51)
1.0”
1.0”
Fuel Inlet Size: NPT
Fluids Capacity Total Oil System: gal (lit)
1.4 (5.3)
Engine Jacket Water Capacity: gal (lit)
2.0 (7.6)
System Coolant Capacity: gal (lit)
6.0 (22.7)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 3% Per 1000ft Over 328ft
GM50-02
2
Gaseous Product Line 50 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
80 x 38 x 52 in
1650
Level 1
80 x 38 x 60 in
2000
Level 2
80 x 38 x 76 in
2150
Level 3
110 x 38 x 68 in
2350
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
79 dBA
81 dBA
Level 1
77 dBA
79 dBA
Level 2
75 dBA
78 dBA
Level 3
71 dBA
74 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
GM50-02
3
Gaseous Product Line 50 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
GM50-02
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
GM60-02 60 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
362CSL1604
361CSL1602
361CSL1602
361CSL1601
361PSL1633
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
60 (60)
60 (60)
60 (60)
60 (60)
60 (60)
AMPS Nat (LP)
250 (250)
208 (208)
181 (181)
90 (90)
72 (72)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Certified
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Certified
Starter
& Alternator
±
1% Voltage Regulation
Microprocessor
Pole, Rotating Field
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Based Digital Control
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
100%
of Rated Load - One Step
Critical
Grade Silencer Mounted
Battery
Charger 12V 6 Amp
Governor
- Electronic Isochronous
12V
Battery System & Cables
5%
SAE
Flywheel & Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1000W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
GM60-02
Colors - White / Tan / Gray
1
Gaseous Product Line 60 kWe
Application Data Engine Manufacturer: Model:
General Motors GM 5.7L EPA
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration: Natural
Rated RPM:
Cylinder Arrangement:
Max HP Stby (kWm):
8 Cylinder Vee
350 (5.70) 4.0 (10.2) x 3.5 (8.8) 9.4 : 1 1800 105 (78.3)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
589 (17)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
36.6 (138.5)
Heat Rejection to Coolant: BTUM (kW)
3,650 (64.2)
Heat Rejection to CAC: BTUM (kW)
N/A
Heat Radiated to Ambient: BTUM (kW)
854 (14.9)
Air Requirements Aspirating: CFM (m³/min)
182 (5.20)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min) Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
7,400 (209) Consult Factory For Remote Cooled Applications
Natural Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
859 (24.3)
363 (10.3)
At 75% of Power Rating: ft3/hr (m3/hr)
725 (20.5)
305 (8.6)
At 50% of Power Rating: ft3/hr (m3/hr)
578 (16.4)
244 (6.9)
1.0”
1.0”
Fuel Inlet Size: NPT
Fluids Capacity Total Oil System: gal (lit)
1.4 (5.3)
Engine Jacket Water Capacity: gal (lit)
2.0 (7.6)
System Coolant Capacity: gal (lit)
6.0 (22.7)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 3% Per 1000ft Over 328ft
GM60-02
2
Gaseous Product Line 60 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
80 x 38 x 52 in
1650
Level 1
80 x 38 x 60 in
2000
Level 2
80 x 38 x 76 in
2150
Level 3
110 x 38 x 68 in
2350
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
79 dBA
81 dBA
Level 1
77 dBA
79 dBA
Level 2
76 dBA
78 dBA
Level 3
72 dBA
75 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
GM60-02
3
Gaseous Product Line 60 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
GM60-02
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
GM100-03 90 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
363CSL1607
362CSL1606
362CSL1606
362CSL1604
362PSL1635
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
90 (80)
90 (80)
90 (80)
90 (80)
90 (80)
AMPS Nat (LP)
375 (333)
313 (278)
271 (241)
135 (120)
108 (96)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Certified
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Certified
Starter
& Alternator
±
1% Voltage Regulation
Microprocessor
Pole, Rotating Field
Base
- Formed Steel Line Circuit Breaker Mounted & Wired
Based Digital Control
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
100%
of Rated Load - One Step
Critical
Grade Silencer Mounted
Battery
Charger 12V 6 Amp
Governor
- Electronic Isochronous
12V
Battery System & Cables
5%
SAE
Flywheel & Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 1000W 120V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
GM100-03
Colors - White / Tan / Gray
1
Gaseous Product Line 90 kWe
Application Data Engine Manufacturer: Model:
General Motors GM 5.7LTCAC
Displacement - Cu. In. (lit): Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 8 Cylinder Vee
350 (5.70) 4.0 (10.2) x 3.5 (8.8) 9.4 : 1 1800
Max HP Stby (kWm):
155 (116)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
846 (23.9)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
40.0 (147.6)
Heat Rejection to Coolant: BTUM (kW)
6,300 (110)
Heat Rejection to CAC: BTUM (kW)
711 (12.4)
Heat Radiated to Ambient: BTUM (kW)
1,536 (26.9)
Air Requirements Aspirating: CFM (m³/min)
263 (7.44)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min) Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
16,500 (467) Consult Factory For Remote Cooled Applications
Natural Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
1,360 (38.5)
509 (14.4)
At 75% of Power Rating: ft3/hr (m3/hr)
1,110 (31.4)
411 (11.6)
At 50% of Power Rating: ft3/hr (m3/hr)
770 (21.8)
290 (8.22)
1.25”
1.25”
Fuel Inlet Size: NPT
Fluids Capacity Total Oil System: gal (lit)
1.5 (5.70)
Engine Jacket Water Capacity: gal (lit)
2.7 (10.3)
System Coolant Capacity: gal (lit)
10.8 (41.0)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 3% Per 1000ft Over 328ft
GM100-03
2
Gaseous Product Line 90 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
96 x 54 x 65 in
2847
Level 1
96 x 54 x 76 in
3364
Level 2
96 x 54 x 104 in
3856
Level 3
136 x 54 x 96 in
4146
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
84 dBA
87 dBA
Level 1
82 dBA
85 dBA
Level 2
77 dBA
79 dBA
Level 3
72 dBA
75 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
GM100-03
3
Gaseous Product Line 90 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
GM100-03
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
NG150-01 150 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
431CSL6206
431CSL6202
431CSL6202
431CSL6202
431PSL6240
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
150 (95)
150 (95)
150 (95)
150 (95)
150 (95)
AMPS Nat (LP)
625 (396)
521 (330)
452 (286)
226 (143)
181 (114)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Certified
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Certified
Starter
& Alternator
±
1% Voltage Regulation
Microprocessor
Pole, Rotating Field
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Based Digital Control
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
100%
of Rated Load - One Step
Critical
Grade Silencer Mounted
Battery
Charger 24V 5 Amp
Governor
- Electronic Isochronous
24V
Battery System & Cables
5%
SAE
Flywheel & Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 2500W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
NG150-01
Colors - White / Tan / Gray
1
Gaseous Product Line 150 kWe
Application Data Engine Manufacturer:
NGE
Displacement - Cu. In. (lit):
Model: D081TIC
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged 6 Cylinder Inline
492 (8.10) 4.37 (11.1) x 5.47 (13.9) 10.5 : 1 1800
Max HP Stby (kWm):
239 (178)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
1,129 (31.9)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
63.0 (238)
Heat Rejection to Coolant: BTUM (kW)
9,357 (163.7)
Heat Rejection to CAC: BTUM (kW)
760 (13.3)
Heat Radiated to Ambient: BTUM (kW)
2,348 (41.1)
Air Requirements Aspirating: CFM (m³/min)
355 (10.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
12,500 (354)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
Consult Factory For Remote Cooled Applications
Natural Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
1,539 (43.6)
517 (14.7)
At 75% of Power Rating: ft3/hr (m3/hr)
1,191 (33.7)
390 (11.1)
At 50% of Power Rating: ft3/hr (m3/hr)
845 (23.9)
283 (8.02)
1.5” (1)
1.5” (1)
Fuel Inlet Size: NPT (Qty)
Fluids Capacity Total Oil System: gal (lit) Engine Jacket Water Capacity: gal (lit) System Coolant Capacity: gal (lit)
6.34 (24.0) 6.0 (22.7) 21.3 (80.0)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1.5% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 2.5% Per 1000ft Over 1200ft
NG150-01
2
Gaseous Product Line 150 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
120 x 54 x 57 in
5221
Level 1
120 x 54 x 86 in
5986
Level 2
120 x 54 x 107 in
6300
Level 3
160 x 54 x 89 in
6529
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
80 dBA
82 dBA
Level 1
77 dBA
79 dBA
Level 2
77 dBA
79 dBA
Level 3
68 dBA
70 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
NG150-01
3
Gaseous Product Line 150 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
NG150-01
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
NG200-01 190 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
432CSL6210
431CSL6206
431CSL6206
431CSL6206
431PSL6243
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
190 (130)
190 (130)
190 (130)
190 (130)
190 (130)
AMPS Nat (LP)
792 (542)
660 (452)
572 (391)
286 (196)
229 (157)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
UL
2200 Certified
Voltage Regulator
cUL
Blower
Fan & Fan Drive
Automatic
Certified
Starter
& Alternator
±
1% Voltage Regulation
Microprocessor
Pole, Rotating Field
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Based Digital Control
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Main
100%
of Rated Load - One Step
Critical
Grade Silencer Mounted
Battery
Charger 24V 5 Amp
Governor
- Electronic Isochronous
24V
Battery System & Cables
5%
SAE
Flywheel Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Jacket
Water Heater -20˚F 3000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
NG200-01
Colors - White / Tan / Gray
1
Gaseous Product Line 190 kWe
Application Data Engine Manufacturer:
NGE
Displacement - Cu. In. (lit):
Model: D111TIC
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 6 Cylinder Inline
673 (11.1) 4.84 (12.3) x 6.1 (15.5) 10.5 : 1 1800
Max HP Stby (kWm):
302 (225)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
1,425 (40.3)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
81.9 (310)
Heat Rejection to Coolant: BTUM (kW)
11,071 (194)
Heat Rejection to CAC: BTUM (kW)
1,460 (25.6)
Heat Radiated to Ambient: BTUM (kW)
2,163 (37.9)
Air Requirements Aspirating: CFM (m³/min)
448 (12.7)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
18,000 (509)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
Consult Factory For Remote Cooled Applications
Natural Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
2,115 (59.9)
704 (19.9)
At 75% of Power Rating: ft3/hr (m3/hr)
1,648 (46.7)
600 (17.0)
At 50% of Power Rating: ft3/hr (m3/hr)
1,157 (32.8)
404 (11.5)
2.0” (1)
2.0” (1)
Fuel Inlet Size: NPT (Qty)
Fluids Capacity Total Oil System: gal (lit)
6.6 (25.0)
Engine Jacket Water Capacity: gal (lit)
6.6 (25.0)
System Coolant Capacity: gal (lit)
27.7 (105)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1.5% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 2.5% Per 1000ft Over 1200ft
NG200-01
2
Gaseous Product Line 190 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
125 x 66 x 80 in
6294
Level 1
140 x 66 x 105 in
7234
Level 2
140 x 66 x 123 in
7700
Level 3
195 x 66 x 112 in
8140
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
81 dBA
84 dBA
Level 1
79 dBA
82 dBA
Level 2
78 dBA
81 dBA
Level 3
70 dBA
71 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
NG200-01
3
Gaseous Product Line 190 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 2 & 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
NG200-01
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
NG265-01 265 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4027
432CSL6210
432CSL6210
432CSL6210
431PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
265 (170)
265 (170)
265 (170)
265 (170)
265 (170)
AMPS Nat (LP)
1104 (708)
921 (591)
798 (512)
399 (256)
319 (205)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Based Digital Control
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1% Voltage Regulation
Main
Pole, Rotating Field
Critical
Grade Silencer Mounted Charger 24V 5 Amp
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
100%
of Rated Load - One Step
Jacket
Governor
- Electronic Isochronous
24V
Battery System & Cables
5%
SAE
Flywheel Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 4000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
NG265-01
Colors - White / Tan / Gray
1
Gaseous Product Line 265 kWe
Application Data Engine Manufacturer:
NGE
Displacement - Cu. In. (lit):
Model: D146TIC
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Turbo Charged, CAC
Cylinder Arrangement:
8 Cyl Vee
892 (14.6) 5.04 (12.8) x 5.59 (14.2) 10.5 : 1 1800
Max HP Stby (kWm):
402 (300)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
1,895 (53.6)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
180 (681)
Heat Rejection to Coolant: BTUM (kW)
16,189 (285)
Heat Rejection to CAC: BTUM (kW)
4,682 (81.9)
Heat Radiated to Ambient: BTUM (kW)
3,017 (52.8)
Air Requirements Aspirating: CFM (m³/min)
603 (17.1)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
30,000 (849)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
Consult Factory For Remote Cooled Applications
Natrual Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
2,782 (78.7)
926 (26.2)
At 75% of Power Rating: ft3/hr (m3/hr)
2,168 (61.4)
789 (22.4)
At 50% of Power Rating: ft3/hr (m3/hr)
1,522 (43.1)
532 (15.1)
1.5” (2.0)
1.5” (2.0)
Fuel Inlet Size: NPT (Qty)
Fluids Capacity Total Oil System: gal (lit)
8.19 (31.0)
Engine Jacket Water Capacity: gal (lit)
11.4 (43.2)
System Coolant Capacity: gal (lit)
33.5 (127)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1.5% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 2.5% Per 1000ft Over 1200ft
NG265-01
2
Gaseous Product Line 265 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
140 x 66 x 73 in
8539
Level 1
140 x 78 x 106 in
10,260
Level 2
N/A
N/A
Level 3
260 x 78 x 106 in
11,088
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
81 dBA
84 dBA
Level 1
79 dBA
81 dBA
Level 2
N/A
N/A
Level 3
71 dBA
73 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
NG265-01
3
Gaseous Product Line 265 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
NG265-01
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
NG350-01 350 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
573RSL4033
433CSL6216
433CSL6216
433CSL6216
433PSL6248
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
350 (225)
350 (225)
350 (225)
350 (225)
350 (225)
AMPS Nat (LP)
1458 (938)
1216 (782)
1054 (677)
527 (339)
421 (271)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Based Digital Control
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1% Voltage Regulation
Main
Pole, Rotating Field
Critical
Grade Silencer Mounted Charger 24V 5 Amp
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
100%
of Rated Load - One Step
Jacket
Governor
- Electronic Isochronous
24V
Battery System & Cables
5%
SAE
Flywheel Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 5000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
NG350-01
Colors - White / Tan / Gray
1
Gaseous Product Line 350 kWe
Application Data Engine Manufacturer:
NGE
Displacement - Cu. In. (lit):
Model: D183TIC
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 10 Cylinder Vee
1115 (18.3) 5.04 (12.8) x 5.59 (14.2) 10.5 : 1 1800
Max HP Stby (kWm):
536 (400)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
2,366 (67.0)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
174 (659)
Heat Rejection to Coolant: BTUM (kW)
20,784 (364)
Heat Rejection to CAC: BTUM (kW)
4,120 (72.1)
Heat Radiated to Ambient: BTUM (kW)
3,486 (61.0)
Air Requirements Aspirating: CFM (m³/min)
788 (22.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
36,000 (1,019)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
Consult Factory For Remote Cooled Applications
Natrual Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
3,499 (99.0)
1,146 (32.4)
At 75% of Power Rating: ft3/hr (m3/hr)
2,727 (77.2)
977 (27.7)
At 50% of Power Rating: ft3/hr (m3/hr)
1,914 (54.2)
659 (18.7)
2.0” (2.0)
2.0” (2.0)
Fuel Inlet Size: NPT (Qty)
Fluids Capacity Total Oil System: gal (lit)
9.25 (35.0)
Engine Jacket Water Capacity: gal (lit)
13.2 (50.0)
System Coolant Capacity: gal (lit)
56.0 (212)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1.5% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 2.5% Per 1000ft Over 1200ft
NG350-01
2
Gaseous Product Line 350 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
156 x 68 x 90 in
9430
Level 1
156 x 86 x 116 in
11,727
Level 2
N/A
N/A
Level 3
288 x 86 x 116 in
13,073
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
83 dBA
86 dBA
Level 1
81 dBA
84 dBA
Level 2
N/A
N/A
Level 3
72 dBA
74 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
NG350-01
3
Gaseous Product Line 350 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
NG350-01
Rev1.0
4
Gaseous Product Line
208-600 Volt 60 Hz / 1800 RPM
NG400-01 400 kWe
Standby
Ratings 240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
573RSL4035
433CSL6220
433CSL6220
433CSL6220
433PSL6248
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
400 (250)
400 (250)
400 (250)
400 (250)
400 (250)
AMPS Nat (LP)
1667 (1042)
1390 (868)
1204 (753)
602 (376)
482 (301)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment Additional
Generator
Engine Radiator
Cooled Unit Mounted (50˚C)
Brushless
Single Bearing
Microprocessor
Based Digital Control
Voltage Regulator
Base
- Structural Steel Line Circuit Breaker Mounted & Wired
Blower
Fan & Fan Drive
Automatic
Starter
& Alternator
±
1% Voltage Regulation
Main
Pole, Rotating Field
Critical
Grade Silencer Mounted Charger 24V 5 Amp
Oil
Pump & Filter
4
Oil
Drain Extension w/Valve
130˚C
Standby Temperature Rise
Battery
100%
of Rated Load - One Step
Jacket
Governor
- Electronic Isochronous
24V
Battery System & Cables
5%
SAE
Flywheel Housing
NEMA
Air
Cleaner (Dry Single Stage)
Flexible EPA
Fuel Connector
Certified
Maximum Harmonic Content MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 5000W 240V
w/Isolation Valves Vibration
Isolation Mounts
Radiator
Duct Flange (OPU Only)
Single 2YR
Source Supplier
/ 2000HR Standby Warranty
Standard
NG400-01
Colors - White / Tan / Gray
1
Gaseous Product Line 400 kWe
Application Data Engine Manufacturer:
NGE
Displacement - Cu. In. (lit):
Model: D219TIC
Bore - in. (cm) x Stroke - in. (cm):
Type: 4-Cycle
Compression Ratio:
Aspiration:
Rated RPM:
Cylinder Arrangement:
Turbo Charged, CAC 12 Cylinder Vee
1,338 (21.9) 5.04 (12.8) x 5.59 (14.2) 10.5 : 1 1800
Max HP Stby (kWm):
612 (457)
Exhaust System Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
2,995 (84.8)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System Ambient Capacity of Radiator: °F (°C)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
174 (659)
Heat Rejection to Coolant: BTUM (kW)
25,760 (451)
Heat Rejection to CAC: BTUM (kW)
6,080 (106)
Heat Radiated to Ambient: BTUM (kW)
3,415 (59.8)
Air Requirements Aspirating: CFM (m³/min)
968 (27.0)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
40,000 (1,132)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
Consult Factory For Remote Cooled Applications
Natrual Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
4,230 (120)
1,408 (39.8)
At 75% of Power Rating: ft3/hr (m3/hr)
3,297 (93.3)
1,200 (34.0)
At 50% of Power Rating: ft3/hr (m3/hr)
2,314 (65.5)
809 (22.9)
2.0” (2.0)
2.0” (2.0)
Fuel Inlet Size: NPT (Qty)
Fluids Capacity Total Oil System: gal (lit)
10.6 (40.0)
Engine Jacket Water Capacity: gal (lit)
13.8 (52.3)
System Coolant Capacity: gal (lit)
60.2 (228)
All calculations based on natural gas fuel. Deration Factors: Temperature: Derate 1.5% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 2.5% Per 1000ft Over 1200ft
NG400-01
2
Gaseous Product Line 400 kWe
DGC-2020 Control Panel Standard Features Digital
Metering
Engine
Parameters
Generator Engine CAN
Protection Functions
Protection
Bus ECU Communications
Windows-Based Multilingual Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
16
Programmable Contact Inputs
Up
to 15 Contact Outputs (7 standard)
UL
Recognized, CSA Certified, CE Approved
Event IP
Recording
54 Front Panel Rating with Integrated Gasket
NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data LxWxH
Weight lbs
OPU
156 x 76 x 90 in
9863
Level 1
156 x 86 x 116 in
12,160
Level 2
N/A
N/A
Level 3
288 x 86 x 116 in
13,506
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
83 dBA
86 dBA
Level 1
81 dBA
84 dBA
Level 2
N/A
N/A
Level 3
72 dBA
74 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice. Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
NG400-01
3
Gaseous Product Line 400 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available). **Level 3 enclosures are 150 MPH Wind Rated as standard. ***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches. **All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions. ***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice. Blue Star Power Systems, Inc.
Distributed By:
52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 www.bluestarps.com
NG400-01
Rev1.0
4
ENGINEERING GUIDE Automatic Transfer Switches
ASCO Power Transfer Switch Comparison Features
ATS Product Series 185
300
4000
7000
Intended Application
Residential Light Commercial
Commercial Light Industrial
Industrial
Mission Critical Critical Power
Ampere sizes available
100 - 400
30 - 3,000
30 - 4,000
30 - 4,000
Phases Available
Single
Single or Three
Single or Three
Single or Three
Pole Counts Available Low Voltage
2 220 - 240V
2, 3 or 4 115 - 600V
2, 3 or 4 115 - 600V
2, 3 or 4 115 - 600V
Medium Voltage
N/A
N/A
N/A
5kV, 15kV
Yes Yes Yes N/A N/A N/A N/A N/A N/A N/A
Yes Yes Yes N/A N/A N/A N/A N/A N/A N/A
Yes Yes N/A Yes Yes N/A N/A N/A N/A N/A
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
10 -100 kA
10-100 kA
Comparison Features
Product Type Open Transition Transfer Switch Service Entrance Rated Transfer Switch Power Transfer Load Center Closed-Transition Transfer Switch Delayed-Transition Transfer Switch Soft Load Transfer Bypass-Isolation Transfer Switch Closed-Transition Bypass-Isolation TS Delayed-Transition Bypass-Isolation TS Soft Load Bypass-Isolation TS
Withstand and Close-On Ratings WCR When Used With Any Circuit Breakers
N/A
WCR When Used With Specific Circuit Breakers
10kA -35kA 100 -200kA N/A
22 -100kA 100 -200kA N/A
22 -100kA 100 -200kA 36-65kA
22-100kA 100-200kA 36-65kA
STD
STD
Yes
Yes
N/A N/A
Yes N/A
Yes N/A
Yes Yes
WCR when used with current limiting fuses Short Time Withstand Rating
N/A
Neutral Configuration Solid Switched Overlapping
ATS Product Series
Comparison
185
300
4000
7000
Voltage and Frequency Settings Phase Selection Pick up Normal Source Voltage Drop out Normal Source Voltage Pick up Emergency Source Voltage Drop out Emergency Source Voltage Frequency Pick Up Emergency Source Frequency Drop out Emergency Source Frequency Normal Overvoltage Trip Emergency Overvoltage Trip Normal Overfrequency Trip Emergency Overfrequency Trip Pick up Normal Source Frequency Drop out Normal Source Frequency Normal & Emergency Voltage Unbalance
Time Delay Settings Override Normal Source Momentary Outage Transfer to Emergency Re-transfer to Normal Utility Power Loss Mode Engine Cool Down Override Emergency Source Momentary Outage Generator Exerciser
Single Phase
Single or Three Phase
Single or Three Phase
Single or Three Phase
198 Volts 154-187 Volts 198 Volts 165 Volts 50 or 60Hz 48 or 57Hz
90% or 95% 70% to 90% 90% Fixed 75% Fixed 50 or 60 Hz 95% Fixed
85 to 100% 70 to 98% 85 to 100% 70 to 98% 50 or 60 Hz 90 to 100%
85 to 100% 70 to 98% 85 to 100% 70 to 98% 50 or 60 Hz 90 to 100%
43 or 51Hz N/A N/A N/A N/A
85% Fixed N/A N/A N/A N/A
85 to 98% 102 to 115% 102 to 115% 102 to 110% 102 to 110%
85 to 98% 102 to 115% 102 to 115% 102 to 110% 102 to 110%
N/A N/A N/A
90 to 100% 85 to 98% Yes
90 to 100% 85 to 98% Yes
1 or 3 Seconds 0 to 5 Minutes 1 Sec. to 30 Mins. 5 Minutes 4 Seconds 7 Day
0 to 6 Seconds 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes Programmable
0 to 6 Seconds 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes 0 to 60 Minutes Programmable
N/A N/A N/A 1 or 3 Seconds 10 Seconds 5 Minutes 2 or 5 Minutes 4 Seconds 7 Day
Indication and Controls Load Connected to Normal
Yes
Yes
Yes
Yes
Load Connected to Emergency
Transfer Test Switch
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Terminals For Remote Transfer Control
STD
STD
STD
STD
Yes N/A N/A N/A
Yes Yes Yes STD
Yes Yes Yes Optional
Yes Yes Yes Optional
Power Manager
N/A N/A
N/A N/A
Yes Optional
Yes Optional
Transfer Controls Lock Out
N/A
N/A
Yes
Optional
Yes Yes N/A N/A N/A
Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes
N/A Yes N/A Yes
Yes Yes N/A Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Normal Source Available Emergency Source Available
Bypass Time Delay Switch Transfer Inhibit In-Phase Monitor Load Disconnect Contacts with Time Delay Event Log
Enclosures Type 1 Type 3R Type 4 Type 4X Type 12
Connectivity RS-485 Serial Ethernet Modbus Monitoring and Control via ASCO Products
Optional Accessories Optional
Field Kits Only
Limited
.
Limited
Extensive
.
800-800-ASCO www.ascopower.com 50 Hanover Rd, Florham Park, New Jersey 07932 U.S.A. Publication 3149 R6
© May, 2010
Printed in the U.S.A.
Power Switching & Controls for Business-Critical Continuity
24-hour protection no matter when trouble strikes
ASCO S eries 300 Power Transfer Switches for Power Outage Protection Where would you be without a constant flow of electrical power? We often take for granted that power will always be around when we need it. In reality, power failures are very common. And when the power goes out, your business suffers. Power failures are unpredictable. They can occur at any time and for any number of reasons—a bolt of lightning, a power surge, a blackout, an accident or even equipment failure. They come without warning and often at the most inconvenient times. It’s for this reason that many businesses and other entities have invested in emergency power backup systems. Typically, the system consists of an engine
2
generator and an automatic transfer switch (ATS) which transfers the load from the utility to the generator. An ATS with built-in control logic monitors your normal power supply and senses any interruptions. When the utility power fails, the ATS automatically starts the engine and transfers the load after the generator has reached proper voltage and frequency. This happens in a matter of seconds after the power failure occurs. When the utility power has been restored, the ATS will automatically switch the load back, and after a time delay, it will shut down the engine. With an Automatic Transfer Switch, you are protected 24 hours a day, seven days a week.
Typical Applications Telecom
Agriculture
In the telecommunications industry, providing a high level of service and dependability is crucial. Lost power means an interruption in service for your customers and lost business for your company. For instance, with cell sites scattered across a wide geographical region and in many remote areas, the chances of an interruption in power are increased, making Automatic Transfer Switches a valuable resource at each location. To maintain dependable service, each cell site must be monitored 24 hours a day. This can be very difficult without some type of remote monitoring and testing capability. The Series 300 Transfer Switch, combined with ASCO’s monitoring and control management system, is a costeffective, packaged solution which can help meet both of these challenging objectives without a major investment at each cell site. With ASCO’s connectivity solutions you can remotely monitor and control numerous sites from around the corner or around the world.
Maintaining electrical power is vital to an agriculture operation. If the flow of power is interrupted, your operation could be at risk unless the backup generator is quickly activated. A prolonged power outage can affect numerous aspects of the operation, from housing and feeding livestock to processing and producing the end product. With an ASCO Series 300 Transfer Switch, power will automatically be transferred over to your backup generator, eliminating the need to manually switch from utility to generator. When power is restored, the ASCO Series 300 Transfer Switch will, after an adjustable time delay to allow for utility stabilization, auto-matically switch the load back to the utility service.
Commercial / Retail, Light Industrial The retail industry is very competitive. An electrical power failure can have a dramatic impact on a retailer’s bottom line. If power is interrupted during peak shopping times, the effect could be extremely damaging to present and future business. A power interruption will not only suspend shopping, it can also create safety problems, result in lost transaction data, lost account information and damage to data collection equipment. In addition, retailers who rely on controlled climates to protect valuable inventory could suffer even greater losses, especially if the power failure occurs at a time when no one is available to rectify the situation. To avoid any of these power outage problems, simply install a backup generator with an ASCO Series 300 Transfer Switch and power outage concerns will be a thing of the past.
Municipal The ASCO Series 300 Transfer Switch can be a critical component of a municipal government’s emergency power backup system. Residents of townships, cities and counties rely on police, fire, ambulance/first aid and other critical public sector services. An interruption in power would affect the ability of emergency services to effectively respond to the needs of the community. When time is a critical factor, such as when responding to a fire alarm or an emergency call, an ASCO Series 300 Transfer Switch can be a lifesaver, switching power to the backup generator. While not all municipal services are a matter of life and death, they are always expected to be there.
3
Series 300 Power Transfer Switches
Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually every major technological advance in the Transfer Switch industry. The ASCO Series 300 was designed for one purpose–to automatically transfer critical loads in the event of a power outage. Each and every standard component was designed by ASCO engineers for this purpose. The rugged construction and proven performance of the ASCO Series 300 assure the user of many years of complete reliability. The Series 300 is even designed to handle the extraordinary demands placed on the switch when starting or restarting stalled motors and switching high inrush loads. ASCO’s Series 300 modular, compact design makes it easy to install, inspect and maintain. All parts are accessible from the front so switch contacts can be easily inspected.
Features The Series 300 is listed to UL 1008 standard for Transfer Switch Equipment and CSA standard C22.2 for automatic transfer switches. Meets NFPA 110 for Emergency and Standby Power Systems and the National Electrical Code (NEC) Articles 700, 701 and 702. 30 through 3000 amps in a compact design. Available to 600 VAC, single or three phase. True double-throw operation: The single solenoid design is inherently inter-locked and prevents contacts from stopping between sources or from being in contact with both sources at the same time.
UL Listed Withstand & Close-On Ratings Available Symmetrical Amperes RMS Switch Ratings Amps
30 70 - 200 230 260, 400 600 600 600 800,1000,1200 1600, 2000 2600, 3000
Notes:
4
When Used With Current Limiting Fuses
Maximum Voltage
When Used With Specific Circuit Breakers
100,000 200,000 100,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000
480v/60Hz 480v/60Hz 480v/60Hz 480v/60Hz 600v/60Hz 480v/60Hz 240v/60Hz 600v/60Hz 600v/60Hz 600v/60Hz
10,000 22,000 22,000 42,000 42,000 50,000 65,000 65,000 85,000 100,000
1. Current – limiting fuse should be Class J type through 400 amps: use Class L type above 400 - amp fuse rating 2. Refer to publication 1128 for specific manufacturer’s breakers
Fig. 1: ASCO Power Transfer Switch rated 200 amperes shown in Type 3R enclosure
There’s no danger of the Series 300 ATS transferring loads to a dead source because the unique ASCO single-solenoid operator derives power to operate from the source to which the load is being transferred. Easy-to-read flush-mounted control and display panel provides LED indicators for switch position and source availability. It also includes test and time-delay bypass switches as standard features. Standard engine exerciser for weekly automatic testing of engine generator set with or without load. Adjustable time-delay feature prevents switch from being activated due to momentary utility power outages and generator dips. Supplied with solid neutral termination. Optional switched neutral pole available. Accessory kits available. Available for immediate delivery. Now available for service entrance applications. Contact Asco for assistance.
Series 300 Power Transfer Switches Designed to Fit Anywhere The ASCO Series 300 product line represents the most compact design of automatic power transfer switches in the industry. With space in electrical closets being at a premium, the use of wall or floor-mounted ASCO Power Transfer Switches assures designers optimum utilization of space. All transfer switches through 2000 amps are designed to be completely front accessible. This permits the enclosures to be installed flush to the wall and still allows installation of all power cabling and connections from the front of the switch. Cable entrance plates are also standard on the 1600 and 2000 amp units to install optional side-mounted pull boxes for additional cable bending space.
Fig. 3: ASCO Power Transfer Switch rated 400 amperes
Fig. 4: ASCO Power Transfer Switch rated 600 Amperes
Fig. 6: ASCO Power Transfer Switch rated 2000 amperes shown in Type 3R enclosure
Fig. 2: ASCO Power Transfer Switch rated 200 amperes
Fig. 5: ASCO Power Transfer Switch rated 1000 amperes
Fig. 7: ASCO Power Transfer Switch rated 3000 amperes
5
Series 300 Microprocessor Controller
The ASCO Microprocessor Controller is used with all sizes of Power Transfer Switches. It represents the most reliable microprocessor controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and connectivity functions required for most emergency and standby power applications.
Voltage & Frequency Sensing Adjustable three-phase, close-differential voltage sensing on normal source. Normal source pickup voltage is adjustable to 95% of nominal; drop-out is adjustable from 70% to 90% of nominal. Frequency sensing on emergency source. Pickup at 95% and dropout at 85% of nominal.
Time Delays
Fig. 8: ASCO Series 300 Microprocessor Controller
Adjustable time delay to override momentary normal source outages to delay all transfer switch and enginestarting signals. Transfer to emergency time delay––Adjustable from 0 to 5 minutes for controlled timing of load transfer to emergency. Re-transfer to normal time delay––Adjustable to 30 minutes. Five-minute unloaded running time delay for emergency engine generator cool down. Four-second time delay to ignore momentary voltage and frequency transients during initial genset loading.
Standard Selectable Features
Fig. 9: Door-Mounted Control & Display Panel
Inphase monitor to transfer motor loads, without any intentional off time, to prevent inrush currents from exceeding normal starting levels. Engine exerciser to automatically test backup generator each week—Includes control switch for testing with or without load. Selective load disconnect, double-throw contact to operate at an adjustable 0 to 20 second adjustable time delay prior to transfer and reset 0 to 20 seconds after transfer. 60 Hz or 50 Hz selectable switch. Three-phase/single-phase selectable switch.
Remote Control Features Control and Display Panel Easy-to-read flush-mounted control and display panel provides LED indicators for switch position and source availability. It also includes test and time-delay bypass switches.
6
Terminal provisions for connecting: Remote test switch. Remote contact for test or for peak shaving applications. Circuit will be automatically bypassed if emergency source fails. Remote time-delay bypass switch.
Series 300 Microprocessor Controller
Battery to Maintain Engine Exerciser Clock Settings
Re-transfer to Normal Adjustable Time Delay
Simple and Accurate Adjustment of Voltage, Frequency and Time-Delay Settings Without Need for Meters and Variable Power Supplies
Transfer to Emergency Adjustable Time Delay
Dip Switches for Enabling Built-In Control Functions Serial Communication Port
Customer Control Interfaces
Fig. 10: Microprocessor Controller
Performance Features 600 volt spacing per UL and CSA standards. Interfacing relays are industrial grade, plug-in type with dust covers. Meets or exceeds the requirements for Electromagnetic Compatibility (EMC).
ANSI C37.90A/IEEE472 Voltage Surge Test NEMA ICS-109.21 Impulse Withstand Test Digital circuitry isolated from line voltages IEC 801-2 Electrostatic discharge (ESD) immunity ENV50140 and IEC 803-1: Radiated electromagnetic field immunity
IEC 801-4 Electrical fast transient (EFT) immunity ENV50142 Surge transient immunity ENV50141: Conducted radio-frequency field immunity EN55011: Group 1, Class A conducted and radiated emissions Optically isolated RS-485 Serial Port EN61000- 4-11 voltage dips and interruptions immunity
7
Series 300 ATS Optional Accessories Accessory 11BG A programmable engine exerciser that provides for weekly or bi-weekly operation, includes one form C contact for source availability of normal and one contact for availability of emergency (contact rating 2 amps @ 30 Vdc, 0.5 amp @ 125 Vac resistive). The programmable engine exerciser incorporates a 7 day or 14 day time base with a digital readout display. Includes “with or without” load control selection for exerciser period.
Accessory 14AA /14BA Auxiliary contacts to indicate position of main contacts. Two (2) for normal and two (2) for emergency position (one set is standard).
Accessory 44A Strip Heater with thermostat for extremely cold areas to prevent condensation and freezing of this condensation. External 120 volt power source required.
Fig. 11: Programmable Engine Exerciser with Source Availability Contacts (Accessory 11BG)
Accessory 44G Strip Heater with thermostat, wired to load terminals: 208-240, 360-380, 460-480, 550-600 volts. Contains wiring harnesses for all transfer switch sizes.
Accessory 72A /72E *See “Connectivity Products”, Page 18
Accessory 123 A protective window that includes a poly-carbonate frame and weather gasket to provide secure access to the membrane interface for the type 1 enclosures. This lockable cover is an alternative to providing 3R secure enclosures.
Fig. 12: Strip Heater Kit (Accessory 44G)
Field Conversion Kits for Series 300 Transfer Switches Kit No.
Description
K629830 Engine Exerciser and source availability contacts (Acc. 11BG) K613127-001 Strip Heater Kit (125 watt) 120 volt (Acc. 44A) K613127-002 Strip Heater Kit (125 watt) 208-480 volt (Acc. 44G) K609027 K473872-001 K755257-001 K754603-001 K778330-001
Cable Pull Box (1600-2000 amp) 6 FT Extension Harness1 Serial Module with or without power manager (Acc. 72A) Connectivity Module with or without power manager (Acc. 72E) Window Kit (Acc. 123)
1. For 30-200 Amp switches only, not available for 300SE, or 300L
Fig. 13: Window Kit (Accessory 123)
8
Series 386 Non-Automatic Power Transfer Switches User-Initiated Control ASCO 386 non-automatic transfer switches are generally used in applications where operating personnel are available and the load is not an emergency type requiring automatic transfer of power. The power-switching mechanism and controller is the same hardware used on the highly reliable ASCO Series 300 transfer switches. ASCO 386s are furnished as standard with a momentary-type selector switch to initiate transfer and re-transfer. They can also be arranged for remote control via ASCO’s connectivity products.
Electrical Features: Listed under UL 1008, CSA certified: - UL listed through 480 VAC. - CSA certified through 600 VAC. Door-mounted selector switch for local, manually initiated electrical control. Sizes from 30 through 3000 amps. Available to 600 VAC, 50 or 60 Hz. Rated for all classes of load transfer. 100% tungsten load ratings through 400 amps. Designed for emergency and standby applications. Same withstand and close-on rating as Series 300.
Standard Selectable Control Features: I nphase monitor to transfer motor loads between live sources, without any intentional off time, to prevent inrush currents from exceeding normal starting levels. Selective load disconnect, double-throw contact to operate at an adjustable 0 to 20 second time delay prior to transfer and reset 0 to 20 seconds after transfer. High/Low nominal voltage setting. Allows user to adjust for source low reduced voltage conditions in remote areas. 60 Hz or 50 Hz selectable switch. Single/Three-phase selectable switch.
Control Features: Fig. 14: ASCO 386 400 Amp Type 1 Enclosure w/Optional Accessories 9C, 9D Source Availability Lights
Switch position indicating signal lights. One auxiliary contact closed when transfer switch is connected to normal and one closed on emergency, standard feature 14A/14B.
Optional Accessories:
6Q Key-operated, momentary source selector switch furnished instead of the standard selector switch.
9C, 9D Source availability lights to provide operator with a local indication of power source availability.
Accessory 14AA/14BA auxiliary contacts to indicate
Fig. 15: Control and Display Panel
position of main contacts. Two (2) for normal position and two (2) for emergency position (one set is standard). 72A Serial module (5110) is used to allow local or remote communications with ASCO POWERQUEST® connectivity products. Special Enclosures (Specify by appropriate code in catalog number): Type 3R: Rain-tight Type 4: Weatherproof Type 12: Oil Tight 72E Connectivity Module 5150 is used to bring several different serial devices that communicate at different baud rates and with different protocols to a common Ethernet media.
9
Series 300 & 386 Transfer Switch Ordering Information To order an ASCO Series 300 Power Transfer Switch, complete the following catalog number:
300 + B
+
Product Neutral Code
Voltage Code
Continuous rating
3 poles, 30, 70, 104, 150, 2004, 3Ø 2304, 260, 400, 600, 800, 1000, 1200, 1600, 2000 26005, 30005
1
Switched Neutral
N
+
Amperes
2 poles, 1Ø
Solid Neutral
B
600
Poles
Blank
300
3 +
A3 B3 C D E F H J K L M N Q R
1
+
X
+
C
+
Enclosure
Options
Controller
+
Blank Open Type
Insert “X”
115 120 208 220 230 240 380 400 415 440 460 480 575 600
If optional accessories are required
1
C
Type 1 (Standard)
F
Type 3R
G
Type 4
H
Type 4X Type 12
M
Type 3R Secure
N
Type 4 Secure
P
Type 4X Secure Double Door SS
R
Type 3RX Secure Double Door SS
+ 480 V 60 Hz
Optional Accessories 11BG
Programmable Engine Exerciser
14AA/14BA
2
L
11CD
Auxiliary Contacts (2 sets)
Specific Volt & Freq This information is necessary to allow correct control settings prior to shipment
44A, 44G
2
Strip Heater w/ Thermostat
72A
Serial Module
72E
6
Connectivity Module
123 Window Kit
6,7
To order an ASCO Series 386 Transfer Switch, complete the following catalog number:
386 + Product 386
B + Neutral Code A
3 Phase Poles
Solid Neutral
2 poles, 1Ø
B1
3 poles, 3Ø
Switched Neutral
600
+
N
+
Voltage Code
Amperes Continuous rating 30, 70, 100, 150, 2004, 2304, 260, 400, 600, 800, 1000, 1200, 1600, 2000, 2600, 30005
A3 B3 C D E F H J K L M N Q R
115 120 208 220 230 240 380 400 415 440 460 480 575 600
+
1
+
Controller
1
X
C
+
+
Options
Enclosure
Insert “X”
Blank Open Type Type 1 C (Standard)
If optional accessories are required
9C/9D + 480 V 60 Hz Optional Accessories
Specific Volt & Freq
6Q
This information is necessary to allow correct control settings prior to shipment
Key-Operated Control
F
Type 3R
G
Type 4
H
Type 4X
L
Type 12
2
Source Availability Lights
M
Type 3R Secure
Auxiliary Contacts
N
Type 4 Secure
P
Type 4X Secure Double Door SS
R
Type 3RX Secure Double Door SS
2
9C/9D
14AA/14BA 72A
6
Serial Module All Accessories
6,7
Notes:
1. Specify neutral code “C” for 260 and 400 amperes only. 2. Available 30-1000, and 1600 amps. Use Type 3R for 1200, 2000, 2600 and 3000 amp applications. 3. 115-120 volt available 30-400 amps only. For other voltages contact ASCO. 4. 200 and 230 amp rated switches for use with copper cable only. 5. Secure 3R type provided as standard for 2600-3000 amp when outdoor enclosure is required. 6. Type 304 Stainless Steel is standard. Suitable for indoor or outdoor use where there may be caustic or alkali chemicals in use. To provide an improved reduction in corrosion of salt and some chemicals, optional type 316 Stainless Steel is recommended. This is a preferred choice for marine environments. 7. Available on switches rated 1200, 2000, 2600, and 3000 Amps.
Extended Warranties for Series 300 Transfer Switches
10
Catalog No.
Description
2EXW300
Two-Year Extended Warranty (Parts & Labor)
3EXW300
Three-Year Extended Warranty (Parts & Labor)
4EXW300
Four-Year Extended Warranty (Parts & Labor)
5EXW300
Five-Year Extended Warranty (Parts & Labor)
72E
Connectivity Module
Series 300 & 386 Transfer Switch Dimensions and Shipping Weights UL Type 1 Enclosure4 Switch Rating Amps
Phase Poles
Neutral Code
Width
2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 3 3 3 3
A B A B A B3 or C A B3 or C A B A B A B A B A B A B A B A B
17 1/2 (445) 17 1/2 (445) 17 1/2 (445) 17 1/2 (445) 18 (457) 18 (457) 18 (457) 18 (457) 24 (610) 24 (610) 24 (610) 24 (610) 34 (864) 34 (864) 34 (864) 34 (864) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965)
30, 70, 100*, 104 150, 200 *Series 386 only
2303, 260, 400
600
800, 1000
1200 1600, 20001 2600, 30002
Dimensions, In. (mm) Height Depth 31 (787) 31 (787) 31 (787) 31 (787) 48 (1219) 48 (1219) 48 (1219) 48 (1219) 63 (1600) 63 (1600) 63 (1600) 63 (1600) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 87 (2210) 87 (2210) 87 (2210) 87 (2210) 87 (2210) 87 (2210) 91 (2311) 91 (2311)
11 5/8 (295) 11 5/8 (295) 11 5/8 (295) 11 5/8 (295) 13 (330) 13 (330) 13 (330) 13 (330) 17 (432) 17 (432) 17 (432) 17 (432) 20 (508) 20 (508) 20 (508) 20 (508) 24 (610) 24 (610) 24 (610) 24 (610) 24 (610) 24 (610) 60 (1524) 60 (1524)
Approx. Shipping Notes: 1. Unit is designed for top cable Weight Lb. (kg) entry of emergency & load and 69 (32) 73 (33) 73 (33) 75 (34) 100 (45) 110 (50) 100 (45) 120 (55) 263 (119) 270 (122) 270 (122) 277 (126) 450 (204) 475 (217) 475 (217) 500 (228) 685 (312) 705 (321) 705 (321) 725 (328) 925 (419) 975 (441) 1700 (771) 2135 (969)
bottom entry of normal. A cable pull box is also available for all top or bottom cable access when required (optional accessory kit #K609027). Not required for type 3R, 4X & 12 enclosures where available. 2. Enclosures for 2600, 3000 amps are free-standing with removable top, sides & back. 3. Neutral Code “B” for 230 amperes only. 4. Dimensional data is approximate and subject to change. Certified dimensions available upon request.
UL Type 3R, 4 or 12 Enclosure1,4,5,6 Switch Rating Amps
Phase Poles
Neutral Code
2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 3 3 3 3
A B A B A B3 or C A B3 or C A B A B A B A B A B A B A B A B
30, 70, 100*, 104 150, 200 *Series 386 only
2303, 260, 400
600
800, 1000
12006 1600, 20002 2600, 3000
Dimensions, In. (mm) Width Height Depth 17 1/2 (445) 17 1/2 (445) 17 1/2 (445) 17 1/2 (445) 18 (458) 18 (458) 18 (458) 18 (458) 24 (610) 24 (610) 24 (610) 24 (610) 34 (864) 34 (864) 34 (864) 34 (864) 41 (1043) 41 (1043) 41 (1043) 41 (1043) 41 (1043) 41 (1043) 41 (1043) 41 (1043)
35 (886) 35 (886) 35 (886) 35 (886) 50 1/2 (1284) 50 1/2 (1284) 50 1/2 (1284) 50 1/2 (1284) 63 (1602) 63 (1602) 63 (1602) 63 (1602) 75 (1907) 75 (1907) 75 (1907) 75 (1907) 94 1/2 (2403) 94 1/2 (2403) 94 1/2 (2403) 94 1/2 (2403) 95 1/2 (2428) 95 1/2 (2428) 95 1/3 (2424) 95 1/3 (2424)
11 5/8 (295) 11 5/8 (295) 11 5/8 (295) 11 5/8 (295) 14 1/3 (364) 14 1/3 (364) 14 1/3 (364) 14 1/3 (364) 18.50 (470) 18.50 (470) 18.50 (470) 18.50 (470) 20 (508) 20 (508) 20 (508) 20 (508) 33 1/2 (852) 33 1/2 (852) 33 1/2 (852) 33 1/2 (852) 62 (1577) 62 (1577) 74 (1882) 74 (1882)
Approx. Shipping Notes: 1. 30-1000 amps non-secure enWeight Lb. (kg) closure. 1200-3000 amps secure 84 (38) 87 (40) 87 (40) 90 (41) 132 (60) 140 (63) 140 (63) 148 (67) 664 (300) 672 (303) 672 (303) 680 (307) 664 (300) 672 (303) 672 (303) 680 (307) 1131 (513) 1160 (526) 1160 (526) 1189 (539) 1810 (817) 1860 (843) 2005 (905) 2070 (938)
enclosure 2. When climate conditions at installation site present condensation risk, special precautions should be taken, such as the inclusion of space heaters, to prevent interior condensation and freezing of this condensation. 3. Neutral code “B” for 230 amperes only. 4. Dimensions for switch sizes 30 1000 amperes suitable for Type 3R, 4, or 12 non secure enclosure, 1200 -3000 amperes only suitable for type 3R. 5. For 1200 ampere type 4, or 12 use 1600 amperes secure enclosure dimensions. 6. Dimensional data is approximate and subject to change. Certified dimensions available upon request.
Series 300 & 386 External Power Connections Sizes UL-Listed Solderless Screw-Type Terminals Switch Rating (Amps)
30 - 230
Ranges of AL-CU Wire Sizes (Unless Specified Copper Only)
2
260, 400 600 800, 1000, 1200 1600, 2000 2600, 3000
One #14 to 4/0 AWG Two 1/0 AWG to 250 MCM or One #4 AWG to 600 MCM Two 2/0 AWG to 600 MCM Four 1/0 to 600 MCM Six 1/0 to 600 MCM Twelve 3/0 to 600 MCM
Notes: 1. All Series 300 switches are furnished with a solid neutral plate (unless switched neutral configuration is specified) and terminal lugs. Specify “A” in catalog number to order a neutral plate on the series 386 switches. 2. 200 and 230 amp rated switches for use with copper cable only. Refer to paragraph 310.15 of the NEC for additional information. 3. Use wire rated 75oC minimum for all power connections.
11
Series 300SE Power Transfer Switch The ASCO Service Entrance Power Transfer Switch combines automatic power switching with the necessary disconnecting, grounding, and bonding required for use as service entrance equipment. The power transfer switch meets all National Electrical Code requirements for service entrance use. Transfer switches generally are installed at facilities that have a single utility feed and a single emergency power source.
600 - 3000 Amp Construction
ASCO Series 300SE products use two types of construction. Products 400 amperes or less, utilize a single enclosure including a service (utility source) disconnect circuit breaker, as well as the power transfer switch, grounding and bonding provisions. Products 600 amperes and above, utilize a multi-section switchboard construction including a service equipment section containing the service (utility source) disconnect circuit breaker, grounding, and bonding provisions. A second section contains the power transfer switch.
Fig. 16: ASCO Series 300 SE Rated 800 amperes Type 1 enclosure with Service Entrance Equipment
Product Features:
70 - 400 Amp Construction
Suitable for use as service entrance equipment. Listed to UL 891 (standard for switchboards) for 600 - 3000 amps, sizes and UL 1008 (standard for panel-boards) for 70 - 400 amps. Automatic Transfer Switch is listed to UL 1008 for total system loads Sizes available from 70 - 3000 amps, 600 VAC, 50 or 60 Hz, single or three phase Silver plated copper ground and neutral bus solderless screw type terminals Ground fault trip protection provided on sizes 1000 amps and above Available with solid or switched neutral
Fig. 17: ASCO Series 300 SE rated 200 amperes in Type 1 enclosure with single source breakers
Series 300SE Transfer Switch Ordering Information To order an ASCO Series 300SE Power Transfer Switch, complete the following catalog number:
3AUS + Product 3AUS
B
+
3
Neutral Code
Phase Poles
B1
2 poles, 1Ø
Switched Neutral
3 poles, 3Ø
+
400 Amperes Continuous Rating
70, 100, 150, 2006, 2256, 250, 400, 600, 800, 1000, 1200, 1600, 2000 2500, 3000
N
+
+
Voltage Code A3 B3 C D E F H J K L M N Q R
115 120 208 220 230 240 380 400 415 440 460 480 575 600
1
+
Controller 1
X
C
+
Options Insert “X” If optional accessories are required
+
Enclosure Blank
Open Type
C
Type 1 (Standard)
F G H
Type 3R Type 4X
L
Type 12
M
Type 3R Secure
N
Type 4 Secure
P
Type 4X Secure Double Door SS
R
Type 3RX Secure Double Door SS
Type 4
2
2
11CD
+
Specific Volt & Freq
11BG Programmable Engine Exerciser
This information is necessary to allow correct control settings prior to shipment
14AA/14BA Auxiliary Contacts (2 sets) 44G Strip Heater w/Thermostat 72A Serial Module
6
72E Connectivity Module 73A Surge Suppressor
7,8
Notes:
12
1. Specify neutral code “C” for 250 and 400 amperes only. 2. Available 70-1000 ampacity. Use Type 3R for 1200-3000 amp applications. 3. 115-120 volt available 150-400 amps only. 4. A solid neutral is standard on 3AUS. 5. For switch sizes 70 - 225 amperes only.
240 V/60
Optional Accessories
6. 200, 225 amp rated switch suitable for use with copper cable only. 7. Type 316 Stainless Steel is standard. It provides an improved reduction in corrosion of salt and some chemicals. It is the preferred choice for marine environments. 8. Available only on switches rated 1200, 2000, 2600, and 3000 Amps.
Series 300SE Transfer Switch Dimensions and Shipping Weights UL Type 1 Enclosure4 Switch Rating Amps
Dimensions, In. (mm) Height
Phase Poles
Neutral Code
Width
2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 3 3 3 3
STD B STD B STD C STD C STD B STD B STD B STD B STD B STD B
36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965)
Phase Poles
Neutral Code
Width
2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 3 3 3 3
STD B STD B STD C STD C STD B STD B STD B STD B STD B STD B
36(914) 36(914) 36(914) 36(914) 36(914) 36(914) 36(914) 36(914) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041)
70, 100 ,150, 200, 225 250, 400
6001, 8001
10001, 12001 16001, 20001 25001, 30001
48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311)
Depth
Approx. Shipping Weight Lb. (kg)
13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 28 (711) 28 (711) 28 (711) 28 (711) 48 (1218) 48 (1218) 48 (1218) 48 (1218) 48 (1218) 48 (1218) 72 (1829) 72 (1829)
400 (185) 408 (188) 408 (188) 416 (192) 400 (185) 408 (188) 408 (188) 416 (192) 800 (370) 820 (378) 820 (378) 846 (390) 1085 (501) 1105 (510) 1105 (510) 1134 (523) 2590 (1198) 2640 (1218) 4590 (2118) 4655 (2148)
Depth
Approx. Shipping Weight Lb. (kg)
16 (406) 16 (406) 16 (406) 16 (406) 16 (406) 16 (406) 16 (406) 16 (406) 34(864) 34(864) 34(864) 34(864) 62(1575) 62(1575) 62(1575) 62(1575) 62(1575) 62(1575) 85(2159) 85(2159)
180 (83) 188 (87) 188 (87) 196 (90) 440 (203) 448 (207) 448 (207) 485 (225) 990 (458) 1010 (467) 1010 (467) 1036 (479) 1305 (604) 1325 (613) 1325 (613) 1354 (626) 2890 (1337) 2940 (1360) 5350 (2474) 5415 (2504)
UL Type 3R Enclosure4 Switch Rating Amps 70, 100 ,150, 200, 225 must specify
250, 400
6001, 8001
10001, 12001 16001, 20001 25001, 30001
Notes: 1. Unit is designed for top and bottom cable entry for all services
and load. 2. Enclosures for 600 – 3000 amps are freestanding. 3. When temperatures below 32° F can be experienced, special precautions should be taken, such as the inclusion of strip heaters, to prevent condensation and freezing of this condensation. This is
Extended Warranties for Series 300SE Transfer Switches Catalog No. 2EXW300SE 3EXW300SE 4EXW300SE 5EXW300SE
Dimensions, In. (mm) Height 48(1219) 48(1219) 48(1219) 48(1219) 48(1219) 48(1219) 48(1219) 48(1219) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 96(2438) 96(2438)
particularly important when environmental enclosures (Type 3R, 4 & 12) are ordered for installation outdoors. See Optional Accessories page for space heater options (acc. 44G). 4. Dimensional data is approximate and subject to change. Certified dimensions available upon request.
Series 300SE External Power Connections
Sizes UL-Listed Solderless Screw-Type Terminals
Description
Switch Rating
Two-Year Extended Warranty (Parts & Labor) Three-Year Extended Warranty (Parts & Labor) Four-Year Extended Warranty (Parts & Labor) Five-Year Extended Warranty (Parts & Labor)
Series 300SE AIC Rating Switch Rating
AIC Rating
Voltage
70, 100, 150, 200, 225 250, 400 600 800, 1000,1200, 1600, 2000 2500, 3000
25,000 35,000 50,000 65,000 100,000
480 480 480 480 480
70, 100, 150, 200*, 225* 250, 400 600 800, 1000, 1200 1600, 2000 2500 3000
Ranges of AL-CU Wire Sizes (Unless Specified Copper Only)
One #14 to 4/0 AWG Two 1/0 AWG to 250 MCM or One #4 AWG to 600 MCM Two 1/0 AWG to 600 MCM Four 1/0 to 600 MCM Six 1/0 to 600 MCM Twelve 3/0 to 600 MCM Twelve 3/0 to 600 MCM
Note: All Series 300SE switches are furnished with a solid neutral plate (unless switched neutral configuration is specified) and terminal lugs. * 200 and 225 amp rated switch for use with copper cable only.
13
Series 300L Power Transfer Load Center • Conventional double throw transfer switch configuration • Automatic Transfer Switch is listed to UL1008, the standard for Transfer Switch Equipment, and meets NFPA 110 for Emergency and Standby Power Systems and the National Electrical Code (NEC) Articles 700, 701, and 702. Also certified to CSA 22.2 No. 178 • Rated up to 240VAC, 200, or 400 amps • Available in Type 1 indoor, or Type 3R secure aluminum outdoor enclosure • Reliable and field proven single solenoid operating mechanism • Programmable microprocessor controller with flush mounted control and display panel • LED indicators for switch position and source availability • Engine exerciser for weekly automatic testing of engine generator set with or without load • Two auxiliary contacts, one contact closed when switch is in normal position and one contact closed when switch is in emergency position • Suitable as service entrance equipment, includes main circuit breaker overcurrent protection on the normal source, and circuit breaker disconnect device on emergency • Includes a UL 67 Listed 42 position Square - D panelboard load center • Local/remote communications capability for interfacing with ASCO POWERQUEST® communication products 14
ASCO 300L Automatic Power Transfer Load Center shown with optional quick connect Cam - Loc assembly and bottom Telco cabinet section (in type 3R secure aluminum enclosure)
Short Circuit Ratings 200A Mains: 22kA at 240vac (Main circuit breaker (Normal & Emergency) Square D circuit breakers rated 2/3 pole, 200A) Note: If a generator input receptacle is supplied for a portable generator then the ratings are as follows: Normal Source – 22kA at 240 vac (Utility Main Disconnect circuit breaker) Emergency Source #2 (Permanent Generator Input circuit breaker) – 10kA at 240vac Emergency Source -#1 (Portable Generator Input circuit breaker) – 5kA at 240vac 400A Mains: 42kA at 240vac. (Main circuit breaker (Normal & Emergency) Square D circuit breakers rated 2/3 pole, 400A) Panelboard: Square D 225/400A series rated 42 circuit panelboard single/three phase with 100% rated neutral, accepts bolt – on or plug – in branch devices.
300L Power Transfer Switch Ordering Information 300 + L4 + Product 300
2
200
+
Load Center
Poles
4 = 42 Space
2 poles, 1Ø
F
+
Amperes
3 poles, 3Ø
C
208
F
240
5
X
+
Controller
Voltage Code
Continuous Rating
200 400
+
1
C
+
Options
Insert “X” if optional accessories are required
+
Enclosure
C M
73TL1 Optional Accessories
Type 1 (Standard)
11BG - Programmable Engine Exerciser
Type 3R Secure (Outdoor)
14AA/14BA - Auxiliary Contacts (2 Sets)1 37P - Generator Receptacle 2
+ 240V 60Hz Specific Voltage & Freq This Information is necessary to allow correct settings prior to shipment
44A - Strip Heater w/Thermostat 72A -Serial Module 72E - Connectivity Module 73 - Surge Suppression (TVSS) 85L - Power Manager 117IB - Interlock Breaker for Portable Generator 128TB - Telco Cabinet 130MG - Cam Loc2
1. Available on 300L, Power Transfer Load Center only. (two sets are standard) for 7000L Series. 2. Available for Type 3R enclosure only, rated 200 Amps. Not available for 400 Amp.
Sizes UL-Listed Solderless Screw-Type Terminals Switch Rating (Amps)
Max # of Conductors Ranges of AL-CU Wire Sizes per Terminal (Unless Specified Copper Only)
# 4 AWG to 250 MCM # 1 AWG to 600 MCM # 1 AWG to 250 MCM
One One Two
200 400
Dimensions for UL Type 1 and 3R Secured Enclosure Dimensions, In. (mm) Height
Phase Poles
Width
200
2,3
30(762)
78(1981)
6(152)
250(115)
400
2,3
38(965)
80(2032)
7-1/4(184)
300(138)
2,3
36(914)
53(1346)
11(279)
305(141)
2,3
38(965)
84(2134)
11-1/4(286)
325(149)
Switch Rating Amps
Depth
Approx. Shipping Weight Lb. (kg)
Enclosed UL Type1
Enclosed UL Type3R Aluminum Secure 2001 400
Note: 1. Add 20 inches to the height of the type 3R enclosure if accessory 128TB, Telco cabinet is required.
Extended Warranties for Series 300L Power Transfer Center Switches
Field Conversion Kits for Series 300L Transfer Switches
Catalog No.
Description
Kit No.
2EXW300L 3EXW300L 4EXW300L 5EXW300L
Two-Year Extended Warranty (Parts & Labor) Total 2 years Three-Year Extended Warranty (Parts & Labor) Total 3 years Four-Year Extended Warranty (Parts & Labor) Total 4 years Five-Year Extended Warranty (Parts & Labor) Total 5 years
K733433-001 Single Phase Surge Suppression 240v/120v (Acc. 73V*1) K733433-003 Three Phase Surge Suppression 209v/120v (Acc. 73V*3)
Note: 1.
Description
Consult ASCO for Type 3R secure enclosures
15
Series 300 Power Monitoring & Control ASCO Connectivity Solutions ASCO POWERQUEST® communications products allow for the monitoring and control of power transfer switches in your Emergency or Standby Power Distribution System. Local and remote networks are supported with either single or multiple points of access and web-enabled communications allow access to your power system from anywhere around the world.
Features
Monitors and controls Power Transfer Switches and Engine Generators Monitors normal and emergency voltages and frequency Indicates transfer switch position and source availability Provides transfer and re-transfer of loads for system testing View normal and emergency voltage and frequency settings View transfer switch time-delay settings Provides transfer switch rating and identification Automatic notification of alarms by E-mail View current, power and power factor with ASCO Power Managers connected to the system
POWERQUEST ® Typical Network Architecture
ASCO 5110 (72A) Serial Modules RS-485
ASCO 5150 (72E) Connectivity Modules
ASCO 5200 Power Manager
To Additional Automatic Transfer Switches
Generator 1
ASCO ATS 1
Ethernet switch
POWERQUEST® 32.15 Software
ASCO ATS 2
ASCO 5110 (72A) Serial Modules RS-485
ASCO 5150 (72E) Connectivity Modules
ASCO 5200 Power Manager
To Additional Automatic Transfer Switches
Generator 2
ASCO ATS 1
16
ASCO ATS 2
Series 300 Power Monitoring & Control Local Computer
Remote Access Computer Ethernet RS 485
Ethernet Switch
Internet
Pager
Firewall
E-mail Server
ASCO 5500 Thin Web Server
Ethernet
Monitoring and Control
ATS Annunciator
Modbus/RTU Building Management Computer
RS 485
ASCO 4000 Series Power Control System
Ethernet Switch
ASCO 5110 (72A) Serial Modules
ASCO 5150 (72E) Connectivity Modules To Additional Automatic Transfer Switches
ASCO ATS 1
ASCO ATS 2
To Additional Automatic Transfer Switches
ASCO ATS 1
ASCO ATS 2
The 5500 Thin Web Server is a client-server application requiring no software to be installed on the client computer. When combined with ASCO Communication Interface Modules (5110, 5150), it provides the most comprehensive Intranet and Internet communication system for the monitoring and control of power transfer switches and engine generators located in your emergency or standby power distribution system. The communication system allows multiple client access, from local or remote locations, and provides for the monitoring of up to 64 power transfer switches and eight (8) engine generators. In addition, automatic paging is provided for all alarm signals.
17
Series 300 Connectivity Products POWERQUEST ® Solutions Comparison ASCO Connectivity Solution Guide Feature
5500 POWERQUEST® Thin Web Server 32.15
5150 Connectivity Module
5350 Remote Annunciator
Quantity of Monitored / Controlled Power Transfer Switches per LAN
32
64
1
8
Number of Monitored / Controlled Gensets
4
8
1
8
Control & Monitoring Capability
Yes
Yes
No
Yes
Embedded Web Pages
No
Yes
Yes
Ethernet Network Compatible
Yes
Yes
Yes
Yes Yes
Monitor Multiple Protocols & Baud Rates (ASCO I, ASCO II, Modbus)
No
No
Yes
Yes
Intranet
Internet
Intranet
Intranet
Monitor Multiple Sites Multiple Client Access
No
Up to 8
Up to 8
Up to 8
Client Software Required
Yes
Internet Explorer
Internet Explorer
Internet Explorer*
Monitors Dissimilar ASCO Controllers on Common LAN
No
No
Yes
Yes
Communicates with ASCO Remote Annuciators
No
No
Yes
Yes
E-mail / Paging Alarms
No
Yes
No
No
Historical Trending Option Alarms
No
Yes
No
Yes**
* Internet Explorer only required for initial communications set up ** Historical trending not available on Remote Annunciator.
5110 Serial Module
Cat. No: 5110 Acc. No: 72A
Fig. 19: Serial Module
The Serial Module (5110) is used to allow local or remote connectivity with ASCO POWERQUEST® connectivity products. The module is used to connect Series 300 transfer switches to a serial network via an RS-485 interface. The module has two port connectors used for ATS & Stand-alone Power Manager connectivity. The serial connection is accomplished from a 5-pin terminal header/socket block. The serial network can support up to 32 devices.
5150 Connectivity Module Cat. No: 5150 Acc. No: 72E
Fig. 20: Connectivity Module
The Connectivity Module (5150) is used to bring several different serial devices that communicate at different baud rates and with different protocols to a common Ethernet medium. The module is used to connect Series 300 transfer switches to a standard 10BaseT Ethernet TCP/IP network using standard RJ-45 connectors. The module contains built in JAVATM applets (program applications for an internet browser) for each monitored device that can load automatically to a standard Web Browser. The module is designed to communicate with up to 8 clients such as Web Browsers, and POWERQUEST® systems simultaneously over the ethernet connection.
5310 ATS Remote Annunciator Cat. No: 5310
Based on the same core technology as the ASCO 5350 ATS Remote Annunciator (next page), the 5310 provides remote annunciation of transfer switch status and transfer/ retransfer control for a single transfer switch. Built-in Ethernet technology provide fast and reliable communications.
18
Fig. 21: Single Channel Automatic Transfer Switch Annunciator
Series 300 Power Connectivity Products 5350 ATS Remote Annunciator Cat. No: 5350
Fig. 22: Eight Channel Automatic Transfer Switch Annunciator
The ASCO 5350 ATS Remote Annunciator is a stand alone device capable of providing individual status annunciation for up to eight transfer switches. Separate LEDs indicate switch status and position. Push buttons initiate transfer switch operation and testing. Transfer switch annunciators can also be set up in multiple locations to monitor the same devices, allowing for redundant annunciation of business-critical transfer switches.
POWERQUEST ® 32.15
Fig. 23: ASCO POWERQUEST® 32.15
POWERQUEST® 32.15 is a PC based monitoring and control system for ASCO devices. The local RS-485 network connects with up to 32 Power Transfer Switches and four Engine Generators. An analog phone connection and ASCO Telephone Interface Module allow for direct dial up, monitoring and control of remote locations. When combined with the ASCO 5110 Serial Module (Acc. 72A), the ASCO 5120 Telephone Interface Module, and the ASCO 5200 Series Power Manager, it provides the most economical communications system for monitoring and controlling Power Transfer Switches and Engine Generators.
5500 Series Thin Web Server Cat. No: A5510
The ASCO Thin Web Server allows you to monitor and control transfer switches and engine generators anytime over the Internet or an Intranet from anywhere in the world. It also transmits an E-mail message that an alarm has occurred with one or more of the transfer switches. Plus, this is possible from your home computer or anywhere that has Internet service, using the ASCO Thin Web Server with its embedded HTML web pages. Fig. 24: Thin Web Server
5200 Series Power Manager Cat. No: 5220D
The ASCO 5200 Series Power Manager is a microprocessor metering device specifically designed for transfer switch applications to provide real-time measurements of single and three-phase power systems. It uses digital signal processing technology to measure voltage and phase currents, which it uses to calculate real, reactive, and apparent power and bi-directional energy. All measurements can be displayed locally or at a remote PC via POWERQUEST®. It can also collect data for both normal and emergency positions using auxiliary contact inputs from the transfer switch. Eight digital input and four digital outputs available for customer use. The ASCO 5200 Series Power Manager is available with or without a stand alone NEMA 1 enclosure. Fig. 25: ASCO 5200D Series Power Manager
19
A SCO Power Technologies 50 Hanover Road F l o r ha m Park, NJ 07932 USA 8 0 0 8 0 0 A SCO w w w. ascopower.com w w w. ascoapu.com
Emerson Network Power. The global leader in enabling Business-Critical ContinuityTM.
EmersonNetworkPower.com Outside Plant
AC Power Connectivity
Embedded Computing Embedded Power
DC Power
Infrastructure Management & Monitoring
Power Switching & Controls Precision Cooling
Racks & Integrated Cabinets Services Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co. Publication 1195 R14
© Oc tober, 2009
Printed in the U.S.A.
START-UP COMMISSIONING, SERVICE & SCHEDULED MAINTENANCE
A SCO Power Technologies 50 Hanover Road F l o r ha m Pa r k , N J 0 7 9 3 2 USA ASCO Services Inc. , provides a wide range of technical services to users of automatic transfer switches in emergency and standby power systems. These services include comprehensive scheduled maintenance programs, modifications, upgrades and emergency repairs. Systems serviced range in complexity from a single automatic transfer switch to multiple transfer switches and engine generators. ASCO Services is a wholly owned subsidiary and the exclusive OEM service arm of ASCO Power Technologies, the world’s largest manufacturer of power transfer switching and control equipment. Serving the needs of ASCO’s customers is a major focus; however, ASCO Services is also routinely called upon to perform regular maintenance and emergency repairs on equipment manufactured by others.
ASCO Services offers comprehensive maintenance agreements that detail the preventive care needed to keep emergency power systems ready to respond. A service agreement is an effective way to budget in advance and avoid unexpected expenditures. A 35 point checklist is utilized to assure critical systems and components are kept in top operating condition. These preventive programs can be customized for national accounts. This customization permits central corporate control of costs and scheduling. Periodic reports provide detailed information as to activity, maintenance performed and corrective action.
8 0 0 8 0 0 A SCO www.ascopower.com www.ascoapu.com
ASCO Services deploys more than 75 service personnel strategically located throughout the nation to provide 24-hour response in emergency situations. Each region is manned by experienced personnel who receive ongoing support and training in the newest equipment concepts, design and controls. Because equipment can be utilized for a long number of years, field representatives also receive education on older designs. This knowledge can be invaluable in addressing total system concerns, evaluating problems and providing solutions on site. Service vans are equipped with parts and advanced testing equipment that facilitate these on-the-spot repairs. ASCO Services 1-800-800-ASCO.
Emerson Network Power. The global leader in enabling Business-Critical ContinuityTM.
EmersonNetworkPower.com Outside Plant
AC Power Connectivity
Embedded Computing Embedded Power
DC Power
Infrastructure Management & Monitoring
Power Switching & Controls Precision Cooling
Racks & Integrated Cabinets Services Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co. Publication 3144 R3
19
© July, 2010
Printed in the U.S.A.
4000 SERIES DESIGNED TO FIT ANYWHERE*
4000 SERIES DESIGNED TO FIT ANYWHERE* Critical Loads Demand ASCO
2-Position Transfer Switching 4ATS, 4NTS Switch Rating Amps
Poles
Width Height Depth inches (mm) inches (mm) inches (mm)
Enclosed UL Type 1 2
ASCO 4000 SERIES Power Transfer Switches Protecting: Healthcare Facilities Web Hosting, Internet Data Centers Commercial Buildings / Industrial Buildings
30, 70, 100, 125, 150, 200, 230 260, 400 600 800, 1000 1200 1600, 2000 1 1600, 2000 (front connected)3 2600, 3000 1 4000 1
2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral C 2, 3 or 3 with neutral A/B
18 (457) 24 (610) 24 (610) 34 (864) 38 (965) 38 (965) 38 (965) 38 (965)
48 (1219) 56 (1422) 63 (1600) 72 (1829) 87 (2210) 91 (2311) 87 (2210) 91 (2311)
13 (330) 14 (356) 17 (432) 20 (508) 23 (584) 48 (1219 23 (584) 60 (1524)
2, 3 or 3 with neutral A/B
60 (1524)
91 (2311)
72 (1829)
10-1/4 (260) 25 (635) 30 (762) 31 (787) 28 (711) 28 (711) 70 (1778)
5-1/2 (140) 8 (203) 9-7/8 (251) 12-7/8 (327) 26-1/4 (667) 30-3/4 (781) 53 (1272)
Notes: 1. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back. 2. Consult ASCO for dimensions on enclosures other than UL type 1. 3. Optional arrangement.
Open Configuration 30, 70, 100, 125,150, 200, 230 260, 400 600 800, 1000, 1200 1600, 2000 2600, 3000 4000
Distributed Power / Load Management
As we become more dependent on the quality and reliability of electrical power, interruption or complete loss of power can create serious and even crippling financial losses, or impose dangers to life and safety. ASCO Power Technologies (ASCO) provides the solutions to handle the transfer of critical loads to emergency sources reliably and with state of the art products. Using ASCO products can mean the difference between a minor inconvenience and a major catastrophe. You’ll find ASCO Power Transfer Switches wherever there is a critical load to be protected.
2
When flexibility in power switching is a must, ASCO offers a variety of product solutions to meet virtually every application requirement, including distributed generation applications. That’s why the 4000 SERIES is available in open, delayed, closed and closed soft load configurations. Additionally, switched or overlapping neutral options provide for reliable operation of ground fault protection systems and reduction of voltage transients from unbalanced load switching.
Poles
Width inches (mm)
2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral C 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/C
24 (610) 24(610) 34 (864) 38 (965) 38 (965) 38 (965) 38 (965) 60 (1524)
56 (1422) 63 (1600) 72 (1829) 87 (2210) 91 (2311) 87 (2210) 91 (2311) 91 (2311)
150, 260, 400
2, 3 or 3 with neutral B
18-1/2 (470)
25 (635)
8 (203)
600 800, 1000, 1200 1600, 2000 2600, 3000 4000
2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B
19 (483) 27 (686) 33-1/4 (845) 33-1/4 (845) 60 (1524)
30 (762) 31 (787) 28 (711) 28 (711) 70 (1778)
9-7/8 (251) 12-7/8 (327) 26-1/4 (667) 30-3/4 (781) 53 (1272)
Switch Rating Amps
Height Depth inches (mm) inches (mm)
Enclosed UL Type 1 2 150, 260, 400 600 800, 1000 1200 1600, 2000 1 1600, 2000 (front connected) 3000 1 4000 1
14 (356) 17(432) 20 (508) 23 (584) 48 (1219) 23 (584) 60 (1524) 72 (1829)
Open Configuration 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B
10-1/4 (260) 18-1/2 (470) 19 (483) 27 (686) 33-1/4 (845) 33-1/4 (845) 60 (1524)
Notes: 1. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back. 2. Consult ASCO for dimensions on enclosures other than UL type 1.
Telecom Central Offices Process Manufacturing / Wafer Fabrication Plants /
Closed Transition and Delayed Transition Transfer Switching 4ACTS, 4NCTS, 4ADTS, 4NDTS
Shipping Weights1 2-Position Transfer Switching 4ATS, 4NTS Switch Rating Amps
Poles
Enclosed lb (kg)
Open lb (kg)
30, 70, 100, 125 30, 70, 100, 125 30, 70, 100, 125 150, 200, 230 150, 200, 230 150, 200, 230 260, 400 260, 400 260, 400 600 600 600 800, 1000 800, 1000 800, 1000 1200 1200 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 2600, 3000 4000 4000 4000
2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B
67 (31) 70 (32) 73 (33) 69 (32) 72 (33) 75 (34) 216 (98) 223 (101) 230 (105) 316 (143) 324 (147) 332 (151) 400 (182) 420 (192) 446 (203) 685 (312) 705 (321) 731 (333) 1110 (503) 1160 (525) 1210 (548) 1365 (620) 1430 (649) 1495 (679) 1969 (893) 2149 (975) 2328 (1056)
15 (7) 18 (8) 21 (10) 17 (8) 20 (9) 23 (11) 82 (37) 89 (40) 102 (46) 88 (40) 96 (44) 104 (47) 150 (68) 170 (78) 196 (90) 150 (68) 170 (78) 196 (90) 370 (167) 420 (190) 470 (213) 405 (184) 470 (213) 535 (243) 1258 (571) 1451 (658) 1623 (736)
Notes: 1. Open weights include transfer switch and control panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions.
Shipping Weights Closed Transition and Delayed Transition Transfer Switching 4ACTS, 4NCTS, 4ADTS, 4NDTS
* All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
Switch Rating Amps
Poles
Enclosed lb (kg)
Open* lb (kg)
150, 260, 400 150, 260, 400 150, 260, 400 600 600 600 800, 1000 800, 1000 800, 1000 1200 1200 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 2600, 3000 4000 4000 4000
2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B
235 (107) 242 (110) 250 (113) 335 (152) 343 (156) 352 (159) 420 (192) 450 (205) 480 (219) 710 (324) 740 (337) 770 (351) 1300 (590) 1350 (612) 1400 (635) 1555 (706) 1620 (735) 1685 (765) 1969 (893) 2149 (975) 2328 (1056)
101 (46) 108 (49) 115 (52) 107 (48) 115 (52) 124(56) 175 (80) 205 (94) 235 (108) 175 (80) 205 (94) 235 (108) 505 (229) 555 (252) 605 (274) 540 (245) 660 (300) 725 (329) 1258 (571) 1451 (658) 1623 (736)
Notes: 1. Open weights include transfer switch and control panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions.
20
* All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
21
The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World.
4000 SERIES Power Transfer Switches Product Features • Conventional two-position transfer configuration, plus closed and delayed transition modes of operation. All configurations available with either automatic or non-automatic control. • UL listed to 1008 Transfer Switch Equipment & CSA certified to CSA 22.2 No.178-1978 Automatic Transfer Switches. • Qualified to IEC 60947-6-1, CE marked (optional). (Limited to certain accessories.) • Rated up to 600 VAC, 30 through 4000 amperes. • Reliable and field proven solenoid operating mechanism. • High withstand and close-on ratings including short time withstand current rating for optimum flexibility in circuit breaker coordination (800-4000 amperes). • Solid, switched neutral configurations available. • Front replaceable main and arcing contacts (800-4000 amperes). Fig. 1: Three Pole 4000 SERIES Automatic Transfer Switch rated 800 amperes
4000 SERIES ASCO Power Transfer Switches are the standard of the industry. High speed transfer of loads between alternate sources of power, regardless of ampacity size, is achieved by a reliable, field proven solenoid operating mechanism. When combined with a programmable microprocessor controller with keypad and LCD display, they offer the most advanced method of transferring all types of loads, such as motors, electronic drives, UPS’s and microprocessor based systems. 4000 SERIES Power Transfer Switches are available open or enclosed, in ampacity sizes from 30 through 4000 amperes with a limited selection of optional accessories.
• Programmable microprocessor controller with keypad and LCD display. • Industrial grade user interface with integrated controls and indicating lights. • Convenient one line diagram with switch position and source acceptability LED indicators. • Standard ground conductor connections. • Four auxiliary contacts, two contacts closed when switch is in normal position and two contacts closed when switch is in emergency position.* • Local/remote communications capability for interfacing with ASCO POWERQUEST ® communication products. *Only two contacts standard on 150-400A 4ACTS and 4NCTS
3
4000 SERIES POWER SWITCHING SOLUTIONS
Fig. 2: Four pole, Closed-Transition Transfer Switch rated 1000 amperes in Type 1 enclosure.
Fig. 3: Four pole, Delayed-Transition Transfer Switch rated 400 amperes in Type 1 enclosure.
Closed-Transition Transfer Switching
Delayed-Transition Transfer Switching
ASCO Automatic Closed-Transition Transfer Switches feature main contacts that overlap, permitting the transfer of electrical loads without power interruption. The switch transfers in a make-before-break mode if both sources are within acceptable parameters. Control logic continuously monitors source conditions and automatically determines whether the load transfer should be open (conventional non-overlap mode) or Closed-Transition. Available 150 through 4000 amperes.
ASCO Delayed-Transition Transfer Switches are designed to provide transfer of loads between power sources with a timed load disconnect position for an adjustable time period. Applications include older style variable frequency drives, rectifier banks, and load management applications.
Closed-Transition Transfer within 5 electrical degrees is achieved passively, without control of engine generator set. Therefore, no additional control wire runs are required between the ATS and engine generator set governor. Plus, protective relaying may not be required under normal operation since the contact overlap time is less than 100 milliseconds (consult your local utility on protective relay requirements). Failure to synchronize indication, extended parallel time protection, and transfer switch lock out are standard features.
4
• Available 150 through 4000 amperes. • Utilizes reliable, field proven solenoid operating mechanisms. • Mechanical interlocks to prevent direct connection of both sources. • Indicator light (LED Type) for load disconnect position. • Adjustable time delay for load disconnect position.
4000 SERIES POWER SWITCHING SOLUTIONS Non-Automatic Transfer Switching ASCO Non-Automatic Transfer Switches are electrically operated units which are operated with manual control switches mounted locally or at remote locations. • Sizes from 30 through 4000 amperes. • Microprocessor based controller provides for addition of optional accessories. • Controller prevents inadvertent operation under low voltage conditions. • Low control circuit operating currents allow for long line runs between remotely mounted manual control switches and the transfer switch. • Source acceptability lights inform operator if sources are available to accept load. • Standard inphase monitor can be activated for transferring motor loads.
Fig. 4: Three pole Non-Automatic, electrically operated 200 ampere switch shown in Type 1 enclosure.
Withstand and Close-On Ratings for all 4000 SERIES Products
5
4000 SERIES MICROPROCESSOR CONTROLLER
The 4000 SERIES microprocessor controller is used with all sizes of Power Transfer Switches from 30 through 4000 amperes. It represents the most advanced digital controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and diagnostic functions required for most emergency and standby power applications. Because of severe voltage transients frequently encountered with industrial distribution systems, the microprocessor logic board is separated and isolated from the power board as shown below. This improves electrical noise immunity performance and helps assure compliance with the rigorous transient suppression standards highlighted below.
Fig. 5: 4000 SERIES Microprocessor Controller.
Fig. 6: Microprocessor Power and Logic PC Boards.
4000 SERIES Microprocessor Controller Emission Standard - Group 1, Class A Generic Immunity Standard, from which: Electrostatic Discharge (ESD) Immunity Radiated Electromagnetic Field Immunity Electrical Fast Transient (EFT) Immunity Surge Transient Immunity Conducted Radio-Frequency Field Immunity Voltage Dips, Interruptions and Variations Immunity
6
EN 55011:1991 EN 50082-2:1995 EN 61000-4-2:1995 ENV 50140:1993 EN 61000-4-4:1995 EN 61000-4-5:1995 EN 61000-4-6:1996 EN 61000-4-11:1994
4000 SERIES MICROPROCESSOR CONTROLLER Features • Digital microprocessor. • Touch pad programming of features and settings without the need for meters, or variable power supplies.
• Password protection to prevent unauthorized tampering of settings.
• Sixteen (16) selectable operating voltages available in a single controller.
• Remote monitoring and control with ASCO POWERQUEST ® communications. products. Specify optional accessory 72A or 72E.
• On-board diagnostics provide control panel and ATS status information to analyze system performance.
• Load shed option for bus optimization applications. Specify optional accessory 30B.
• Displays and counts down active timing functions.
• Lamp Test - Provides a convenient way to verify functionality of all LED’s on the user interface.
• Selectable multi-language display (English, German, Portuguese, Spanish, or French. For others contact ASCO).
Voltage and Frequency Sensing
Time Delays
• 3-Phase under and over voltage settings on normal and emergency sources.
• Engine start time delay - delays engine starting signal to override momentary normal source outages - adjustable 0 to 6 seconds.
• Under and over frequency settings on normal and emergency. • True RMS Voltage Sensing with +/- 1% accuracy; Frequency Sensing Accuracy is +/- 0.2%.
• Transfer to emergency time delay - adjustable 0 to 60 minutes.
• Selectable settings: single or three phase voltage sensing on normal and emergency; 50 or 60Hz.
• Emergency source stabilization time delay to ignore momentary transients during initial generator set loading - adjustable 0 to 6 seconds.
• Phase sequence sensing for phase sensitive loads.
• Retransfer to normal time delay with two settings:
• Voltage unbalance detection between phases.
• Power failure mode - 0 to 60 minutes. • Test mode - 0 to 10 hours.
Status and Control Features • Output contact (N/O or N/C) for engine-start signals.
• Unloaded running time delay for engine cooldown adjustable 0 to 60 minutes.
• Selection between “commit/no-commit” on transfer to emergency after engine start and normal restores before transfer.
• Fully programmable engine exerciser with seven independent routines to exercise the engine generator, with or without loads, on a daily, weekly, bi-weekly or monthly basis.
• Terminals for remote test or customer contact for peak shaving applications
• Contains all alarm signals, logic and time delays for use with closed transition switches.
• Advanced inphase algorithm which automatically measures the frequency difference between the two sources and initiates transfer at appropriate phase angles to minimize disturbances when transferring motor loads. • Output signals for remote indication of normal and emergency source acceptability. • Statistical ATS/System monitoring data screens which provide: • Total number of ATS transfers.
• Insynch time delay - 0 to 3 seconds. • Failure to synchronize - 1 to 5 minutes. • Extended parallel time - 0.1 to 1.0 seconds. • Transfer switch locked out. • Delayed transition load disconnect time delay adjustable 0 to 5 minutes. (Delayed Transition Switches only.)
• Number of ATS transfers caused by power source failure. • Total number of days ATS has been in operation. • Total number of hours that the normal and emergency sources have been available.
7
4000 SERIES POWER CONTROL CENTER SCREENS Status Source Status
System Status
Normal Source Vab=480V....................ABC Vbc=480V.........Vunbal=1%Vc a=480V................60.0Hz
Normal OK Load on Normal Displays system status in clear, concise language. Message shown indicates normal source is acceptable and the load is connected to the normal source.
Displays voltage for each phase, frequency, phase rotation and voltage unbalance for both normal and emergency sources.
Time Delay Status
Inphase Transfer Mode
Normal OK
Emerg OK
TD.Engine.Cooldown: 4min15s
Waiting for In-Sync -45o 0.02Hz
Active time delay status displays time remaining until next control event.
Displays the relative phase angle between sources and frequency differential to indicate the controller is awaiting an inphase condition.
Settings Voltage and Frequency Settings
Time Delay Settings
Normal Voltage Dropout.............85%.408V Pickup...............90%.432V O.V. Trip.........110%.528V
TD N>E Xfer Signal Bypass if N Fail: No Pre Xfer: 0 min 20S Post Xfer: 0 min 20S
Provides voltage and frequency setting values for normal and emergency sources. Voltage pick-up, dropout and trip settings are set in percentage of nominal voltage and are also displayed in rms voltage values.
Engine Exerciser
Provides direct reading display for setting time delays.
Feature Settings Shed Load
P1..................Engine.Exerciser Enable:.....Yes....WLoad:....Yes Start:19h30. ALL MON Run.Time:...............2h15min
Direction: Inphase: No
Seven independent programs, load/no load selection, flexible run times and daily, weekly, bi-weekly and monthly exercise routines.
From E TD/0.25
Standard features can be activated with the keypad. As an example, when enabled, the “shed load” option causes the transfer switch to transfer the load off of the specified source. If desired, the load shed transfer can be made inphase.
Data Logging ATS Statistics ATS Statistics ATS Total Xfers: 46 SRC Fail Tot Xfers: 20 Days Energized: 36.5
8
Instant availability of statistical information on total number of ATS transfers, number of transfers caused by power failures and total days controller has been energized, plus more.
4000 SERIES USER INTERFACE User Interface Features • Convenient One Line Diagram - Provides a clear view of the position of the transfer switch, as well as the acceptability of the Normal and Emergency sources. • Source Acceptability LEDs - Provide true indication of the acceptability of each source, as determined by the voltage, frequency, voltage unbalance, and phase sequence settings of the control panel. • Transfer Switch Position LEDs - Provide an indication of which source the transfer switch is connected to. • Transfer Test - Allows the user to test the operation of the transfer switch under a simulated failure of the normal source. Holding for 15 seconds allows time for the engine generator to come online and the transfer switch to transfer the load. • Retransfer to Normal - Allows the user to bypass the programmed Retransfer to Normal time delay upon the return of the normal source when the switch has transfered to emergency either during normal operation or a transfer test.
Fig. 7: 4000 SERIES Open Transition User Interface • Lamp Test - Provides a convenient way to verify the functionality of all LEDs on the User Interface. • User Controls Locked - Visually displays the status of the keypad lock feature of the control panel. When illuminated, the buttons of the User Interface are disabled and the user must enter a password into the control panel to unlock the switch. When LED is blinking, the controls are temporarily unlocked for five minutes from the last button pressed.
Additional Closed Transition User Interface Features • Extended Parallel Time - Provides visual indication when the pre-set extended parallel time has been exceeded. The controls automatically open the emergency or normal main contacts. Separate contact also available to shunt trip to an external breaker. • Failure To Synchronize - Visually displays a failure to synchronize alarm if the time delay settings is exceeded, during closed transition transfer operation. • Transfer Switch Locked Out - Prevents transfer in either direction if the extended parallel time is exceeded. • Alarm Reset - Resets extended parallel and failure to synchronize alarms.
Fig. 8: 4000 SERIES Closed Transition User Interface
• Closed Transition Bypass - Pushbutton allows transfer between sources in an open transition mode.
9
4000 SERIES OPTIONAL ACCESSORIES Time Delays
Customer Control Circuits
2C
30A
Load-shedding circuit initiated by opening of a customer-supplied contact.
30B
Load-shedding circuit initiated by removal of customer-supplied control voltage. (Specify voltage).
44G
Strip Heater with thermostat recommended for outdoor applications on temperatures below 32O F (0OC) to prevent condensation and freezing.
1G
Provides an extended time delay on engine starting. The standard feature one time delay is adjustable from zero to six seconds. Accessory 2C allows this time delay to be adjustable from zero to sixty minutes in one second intervals factory set at five minutes. Similar to accessory 2C except using an external 24 volt DC power input. Available only as a feature of accessory 18Z.
Add-on Boards
Indicators & Controls
18Z
Includes one Form C contact (Rated 2A @ 30VDC
14A/14B Additional auxiliary contact sets to indicate switch position. Two sets are typically standard. Maximum number of two additional sets. (Varies by configuration)
or .5A @ 125VAC) for each of the following:
6C
• Selective Load Disconnect. - Pre and post transfer signal time delay for selective load disconnect with a programmable bypass on source failures adjustable 0 to 5 minutes.
• Normal Source Acceptability. • Emergency Source Acceptability.
Reset Switch for manual retransfer to normal with automatic override upon emergency source failure.
Neutral Conductor Options • Solid neutral, with fully-rated terminals. (AL-CU) UL Listed.
• Fourth contact can be set to mimic the acceptability contacts or annunciate any combination of the acceptability contacts and/or any switch alarm conditions available:
• Conventional neutral switching pole. Note: Specify neutral option in catalog number, see page 18 for instructions.
Communications Options 72A
72E
Extended Parallel Time (Closed transition),
Serial communication module for remote communications to ASCO POWERQUEST ® products. Also allows 4000 SERIES Transfer Switches to communicate via Modbus/RTU. Ethernet connectivity module for remote communications to ASCO POWERQUEST ® products. Contains embedded web pages for the remote monitoring of ASCO products as well as some 3rd party devices. Also provides Serial-to-Ethernet link with ability to communicate using Modbus/TCP.
Failure to Synchronize (Closed transition), Transfer Switch Locked Out (Closed transition), Load Disconnected (Delayed transition). • Accessory 18Z includes an extension of the engine start time delay (feature) to 60 seconds if an external 24VDC supply is connected to a 4000 series controller. This external power source will also allow the LCD display to be active when both normal and emergency sources are unavailable. 18Z2
Includes two 18Z accessory boards. (Maximum of two 18Z accessory boards allowed.)
Fig. 9: 4000 SERIES Accessory 18Z mounting on User Interface 1st Relay Board Accessory 18Z 2nd Relay Board Accesory 18Z2
Studs Standoffs
10
4000 SERIES OPTIONAL ACCESSORIES ASCO 5200 SERIES Power Manager
POWER SYSTEM TOTAL 404 KW +1.00 PF 0 KVAR 60.00 Hz 404 KVA ATSºn NORM
The ASCO 5200 SERIES Power Manager is a microprocessor based metering device that provides real-time measurements of single and three phase power systems. The Power Manager uses digital signal processing technology to measure voltage and current per phase; real, reactive and apparent power, and bi-directional energy. All measurements can be viewed locally with a backlit liquid crystal display and/or displayed remotely with ASCO POWERQUEST ® products. Direct voltage input for systems up to 600 Volts AC can be monitored without the use of external potential transformers (PTs). Measures three phase currents and a fourth current input is available for measuring current in the neutral conductor. The Power Manager includes one discrete input for transfer switch position, eight general purpose discrete inputs, and four relay outputs for monitoring and controlling external devices.
Power Metering • Voltage: Line - Line: VAB, VBC, VCA, VAVERAGE Line - Neutral: VAN, VBN, VCN, VAVERAGE
Fig. 10: ASCO 5200 SERIES Power Manager.
Configurable Designations • Local - A four line, 20 character LCD backlit display. • Remote - With optional Acc. 72A or 72E and Power Manager monitoring systems. • Provides user programmable setpoints based on twelve metering and I/O parameters. Each setpoint allows the user to select the parameter, the trip & reset levels, the trip & reset time delays and the alarm type or relay output to trigger. This can be used for protective relaying and peak shaving applications.
• Frequency: 45.0 to 66.0 Hertz
Integrated ATS Features
• Current: IA, IB, IC, IAVERAGE
When configured on load of ATS:
• Unbalance %: Voltage, Amps
• Displays ATS position.
• Real Power: KWA, KWB, KWC, KWNET
• Displays power data as a function of ATS position (normal/emergency).
• Reactive Power: KVARA, KVARB, KVARC, KVARNET • Apparent Power: KVAA, KVAB, KVAC, KVANET • Real Energy: KWHIMPORT, KWHEXPORT, KWHNET • Reactive Energy: KVARHIMPORT, KVARHEXPORT, KVARHNET • Power Factor: PFA, PFB, PFC, PFNET
Data Access • Eight digital inputs, four relay outputs. • Input/Output 15-character, user definable screen display for identification of input/output signals.
• Accumulates energy data separately for normal and emergency sources.
Optional Configurations and Connection Arrangements Connected To: Load Normal Emergency
With Display Acc. 85L Acc. 85N Acc. 85M
Without Display Acc. 75L Acc. 75N Acc. 75M
Add suffix “A” to above designations if neutral conductor monitoring is required. Note: Accessory 75 and 85 includes component mounting, CTs, shorting blocks and all necessary interwiring.
Note: The ASCO Power Manager is also available as a separate unit for monitoring electrical parameters anywhere in the power distribution system.
11
4000 SERIES POWER MONITORING & CONTROL ASCO POWERQUEST Solutions ASCO POWERQUEST ® communications products allow for the monitoring and control of power transfer switches in your Emergency or Standby Power Distribution System. Local Area networks and Remote networks are supported with either single or multiple points of access, and web-enabled communications allow access to your power system from anywhere around the world.
Features • Monitors and controls Power Transfer Switches and Engine Generators • Monitors normal and emergency voltages and frequency • Indicates transfer switch position and source availability • Provides transfer and re-transfer of loads for system testing • View normal and emergency voltage and frequency settings • View transfer switch time-delay settings • Provides transfer switch rating and identification • Automatic paging notifies personnel, by e-mail or text message, of selected system alarms • View current, power and power factor with ASCO Power Managers Connected to the System • View transfer switch event log • Provides transfer switch test schedule
Typical Network Architecture ASCO 5110 (72A) Serial Modules RS-485
ASCO 5150 (72E) Connectivity Module
ASCO 5200 Power Manager
To Additional Automatic Transfer Switches
Generator 1
ASCO ATS 1
Ethernet Switch
ASCO POWERQUEST ® 32.15 Software
ASCO ATS 2
ASCO 5110 (72A) Serial Modules RS-485
ASCO 5150 (72E) Connectivity Module ASCO 5200 Power Manager
To Additional Automatic Transfer Switches
Generator 2
ASCO ATS 3
12
ASCO ATS 4
4000 SERIES POWER MONITORING & CONTROL
5110 Serial Module The 5110 Serial Module is used to allow local or remote communications with ASCO POWERQUEST ® communication products. The module is used to connect the 4000 SERIES transfer switches to a serial network via an RS-485 interface. The module has two port connectors used for ATS & Power Manager connectivity. The serial connection is accomplished from a 5-pin terminal header/socket block. RS- 485 serial networks allow for up to 32 modules to be set up in a daisy chain configuration to connect to POWERQUEST ® systems.
Fig. 11: Serial Module 72A
5150 Connectivity Module The 5150 Connectivity Module is used to bring several different serial devices that communicate at different baud rates and with different protocols to a common Ethernet media. The module is used to connect 4000 SERIES transfer switches, and ASCO Remote Annuciators to a standard Ethernet TCP/IP network with standard 10base T(RJ-45) connectors. The module has customized embedded JAVATM applets (program applications for an internet browser) for each monitored device that loads automatically to a standard Web Browser. The module is designed to communicate with up to 8 clients such as Web applications (web pages), POWERQUEST ® , or third party Modbus® devices simultaneously over an Ethernet connection. Fig. 12: Connectivity Module 72E
5350 Remote Annunciator The ASCO Power Transfer Switch Remote Annunciator is a stand-alone, industrial grade interface device providing you with the most critical transfer switch status indication and transfer/retransfer control for up to eight switches. Ethernet technology is built in for faster and more reliable communications. LEDs indicate switch status and position, while separate push buttons individually initiate transfer switch operation and testing. Transfer switch annunciators can be set up in multiple locations to monitor various transfer switches, allowing redundant and distributed annunciation. Fig. 13: ASCO Remote Annuciator
13
32.15 ASCO 32.15 POWER INTERFACE SOFTWARE The ASCO 32.15 Power Interface is a computer-based monitoring and control software package. When combined with ASCO 72E/72A Communications Interface modules and the ASCO 5200 SERIES Power Manager, it provides a centralized and comprehensive monitoring and control interface of power transfer switches and engine generators. A one-line diagram, power metering information, transfer switch controls and event-log data, and engine-generator screens are available to users with password protected controls.
Summary Screen
Current and Historical Alarms The Current Alarm screen displays all currently active alarms. It provides the date of the alarm, along with IP and Name of the device with the issue. In addition, a detailed description of the alarm is provided to help the operator in pinpointing the issue. All historical alarms can be viewed as well by selecting the “Historical” tab.
L
E
E 14
N
N
Convenient One-Line Diagram • Colored icons highlighted to show source availability and which source is connected to load.
32.15 Transfer Switch Detail Screen • ATS rating and identification data is displayed. • Allows remote testing and time delay bypass. • Voltage, frequency, phase sequence, voltage unbalance and time delay settings can be checked. • Viewing of engine exercise schedules. • Displays phase to phase voltage on normal and emergency. • Provides complete system status message from 4000 series microprocessor controller. • View event log on the last 99 events for each ATS. • Arrange test schedules for transfer switches. • Provides for monitoring of local site or remote sites.
Power Manager Detail Screen • Voltage: phase to phase; phase to neutral and voltage unbalance. • 3 phase currents and neutral (optional). • Frequency. • Kilowatt hours - normal and emergency. • Status and control of four relay outputs. • Status of eight digital inputs. • Device ratings: CT and PT ratio.
Engine-Generator Details • Voltage: Phase to phase; Phase to neutral • Current for each phase. • Kilowatts and kilowatt hours total. • Frequency and power factor. • Status and control of four digital outputs which can be customized by the user. • Status of eight digital inputs. • “Alarm Enabled” selection. These alarms flash the “engine-generator” icon on the summary screen. • Digital inputs for engine malfunctions are derived from engine mounted sensors (supplied by others).
15
Solutions 5500 SERIES Thin Web Server The ASCO Thin Web Server is an internet-based thin client application, which provides monitoring and control of transfer switches and engine generators from anywhere in the world. With ASCO 72E/72A Communications Interface modules and ASCO 5200 SERIES Power Managers, it brings the power interface to your browser with your user name and password. Alarms and event logs are provided through the browser, while simultaneously transmitting an email indicating that an alarm has occurred with one or more transfer switches.
Fig. 24: Thin Web Server
Fig. 25: Thin Web's html interface screen shot
Communications Products for 4000 SERIES Transfer Switches Description
Acc. Option
Catalog No.
Serial Module
72A
5110
Connectivity Module
72E
5150
Power Manager with Display*
85L
5220D
Thin Web Server*
—
5510E
Software Package*
—
32.15
* These products are available as separate items only. They can be ordered by catalog numbers shown in above chart.
Solutions Comparison ASCO Connectivity Solution Guide Feature Quantity of Monitored / Controlled Power Transfer Switches per LAN
32.15 32
5500 5350 5150 Thin Web Server Connectivity Module Remote Annunciator 64
1024+
8
4
8
1024+
0
Control & Monitoring Capability
Yes
Yes
No
Yes
Embedded Web Pages
No
Yes
Yes
Yes
Ethernet Network Compatible
Yes
Yes
Yes
Yes
Monitor Multiple Protocols & Baud Rates (ASCO I, ASCO II, Modbus)
No
No
Yes
Yes
Intranet
Internet
Intranet
Intranet
Number of Monitored / Controlled Gensets
Monitor Multiple Sites Multiple Client Access
No
Up to 8
Up to 8
Up to 8
Client Software Required
Yes
Internet Explorer
Internet Explorer
Internet Explorer*
Monitors Dissimilar ASCO Controllers on Common LAN
No
No
Yes
Yes
Communicates with ASCO Remote Annuciators
No
No
Yes
Yes
Email / Paging Alarms
No
Yes
No
No
No
Yes**
Historical Trending Option Alarms
* Internet Explorer only required for initial communications setup. ** Historical trending not available on Remote Annuciator.
16
POWERQUEST ®
No
Yes
Solutions
Remote Access Computer
Local Computer Ethernet RS 485
Ethernet Switch Internet Firewall Pager ASCO 5500 Thin Web Server
Email Server
Ethernet
Monitoring and Control
ATS Annunciator
Modbus/RTU RS 485 Building Management Computer ASCO Digital Paralleling System
Ethernet Switch
ASCO 5110 (72A) Serial Modules
ASCO 5150 (72E) Connectivity Modules
To Additional Automatic Transfer Switches
ASCO ATS 1
ASCO ATS 2
To Additional Automatic Transfer Switches
ASCO ATS 1
ASCO ATS 2
17
4000 SERIES ORDERING INFORMATION To order an ASCO 4000 SERIES Power Transfer Switch, complete the following catalog number:
4
A
TS
A
+
Neutral Code*
Product A
N
Automatic
NonAutomatic
+
Phase Poles
---
No Neutral
CTS
Closed Transition
A
Solid Neutral
DTS
Delayed Transition
B
TS
Conventional 2-Position
3
2 3
Switched Neutral
400
+
N
+ 5X +
C
Voltage Code
Grp Code
Enclosure
+
Amperes 30
1000
70
1200
100
1600
125
2000
A B C D E F
150
2600
H
200 1
3000
230 1
4000
J K L M N P Q R
260 400 600
115 120 208 220 230 240 380 400 415 440 460 480 550 575 600
800
*Note:
5 5Xoptional accessories
---
No enclosure
C
Type 1 enclosure
F
Type 3R enclosure
G
Type 4 enclosure
H
Type 4X enclosure
L
Type 12 enclosure
M
Type 3R secure double door
N
Type 4 secure double door
P
Type 4X secure double door
Q
Type 12 secure double door
R
Type 3RX secure double door (Stainless Steel)
1. 200 and 230 amp switch limited to 480 volts maximum. 2. Type 304 Stainless steel is standard. To provide an improved reduction in corrosion in salt or marine environments, specify optional type 316 stainless steel.
The Example Catalog Number above is 4ATSA3400N5XC (X is used to specify optional accessories).
Transfer Switch Configurations 4ATS, 4NTS, 4ADTS, 4NDTS, 4ACTS, 4NCTS
Sizes of UL-Listed Solderless Screw-Type Terminals for External Power Connections Switch Rating amps
Max # of Conductors per Terminal
Range of AL- CU Conductor Sizes
30 -230 1 ATS,NTS
One
#14 to 4/0 AWG
150 DTS, CTS
One
#4 AWG to 600 MCM
Two
#1/0 AWG to 250 MCM
260-400
#4 AWG to 600 MCM
Two
#1/0 AWG to 250 MCM
600
Two
#2 AWG to 600 MCM
800-1200
Four
#1/0 AWG to 600 MCM
1600-20002
Six
#1/0 AWG to 600 MCM
2600, 3000
Twelve
#1/0 AWG to 600 MCM
Twelve
#2/0 AWG to 600 MCM
4000 2
18
One
2
Notes: 1. 200 and 230 amp rating for copper conductors only. 2. All main terminals are rear connected. 1600 & 2000 amp switches are available in optional front connected arrangement. Specify optional accessory 40MY for 1600 amp and 40NY for 2000 amp. WCR rating limited to 85,000 amp rms symmetrical. see pages 20, 21 for enclosure dimensions.
2
2
START-UP COMMISSIONING, SERVICE & SCHEDULED MAINTENANCE
A SCO Power Technologies 50 Hanover Road F l o r ha m Pa r k , N J 0 7 9 3 2 USA ASCO Services Inc. , provides a wide range of technical services to users of automatic transfer switches in emergency and standby power systems. These services include comprehensive scheduled maintenance programs, modifications, upgrades and emergency repairs. Systems serviced range in complexity from a single automatic transfer switch to multiple transfer switches and engine generators. ASCO Services is a wholly owned subsidiary and the exclusive OEM service arm of ASCO Power Technologies, the world’s largest manufacturer of power transfer switching and control equipment. Serving the needs of ASCO’s customers is a major focus; however, ASCO Services is also routinely called upon to perform regular maintenance and emergency repairs on equipment manufactured by others.
ASCO Services offers comprehensive maintenance agreements that detail the preventive care needed to keep emergency power systems ready to respond. A service agreement is an effective way to budget in advance and avoid unexpected expenditures. A 35 point checklist is utilized to assure critical systems and components are kept in top operating condition. These preventive programs can be customized for national accounts. This customization permits central corporate control of costs and scheduling. Periodic reports provide detailed information as to activity, maintenance performed and corrective action.
8 0 0 8 0 0 A SCO www.ascopower.com www.ascoapu.com
ASCO Services deploys more than 75 service personnel strategically located throughout the nation to provide 24-hour response in emergency situations. Each region is manned by experienced personnel who receive ongoing support and training in the newest equipment concepts, design and controls. Because equipment can be utilized for a long number of years, field representatives also receive education on older designs. This knowledge can be invaluable in addressing total system concerns, evaluating problems and providing solutions on site. Service vans are equipped with parts and advanced testing equipment that facilitate these on-the-spot repairs. ASCO Services 1-800-800-ASCO.
Emerson Network Power. The global leader in enabling Business-Critical ContinuityTM.
EmersonNetworkPower.com Outside Plant
AC Power Connectivity
Embedded Computing Embedded Power
DC Power
Infrastructure Management & Monitoring
Power Switching & Controls Precision Cooling
Racks & Integrated Cabinets Services Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co. Publication 3144 R3
19
© July, 2010
Printed in the U.S.A.
4000 SERIES DESIGNED TO FIT ANYWHERE*
4000 SERIES DESIGNED TO FIT ANYWHERE* Critical Loads Demand ASCO
2-Position Transfer Switching 4ATS, 4NTS Switch Rating Amps
Poles
Width Height Depth inches (mm) inches (mm) inches (mm)
Enclosed UL Type 1 2
ASCO 4000 SERIES Power Transfer Switches Protecting: Healthcare Facilities Web Hosting, Internet Data Centers Commercial Buildings / Industrial Buildings
30, 70, 100, 125, 150, 200, 230 260, 400 600 800, 1000 1200 1600, 2000 1 1600, 2000 (front connected)3 2600, 3000 1 4000 1
2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral C 2, 3 or 3 with neutral A/B
18 (457) 24 (610) 24 (610) 34 (864) 38 (965) 38 (965) 38 (965) 38 (965)
48 (1219) 56 (1422) 63 (1600) 72 (1829) 87 (2210) 91 (2311) 87 (2210) 91 (2311)
13 (330) 14 (356) 17 (432) 20 (508) 23 (584) 48 (1219 23 (584) 60 (1524)
2, 3 or 3 with neutral A/B
60 (1524)
91 (2311)
72 (1829)
10-1/4 (260) 25 (635) 30 (762) 31 (787) 28 (711) 28 (711) 70 (1778)
5-1/2 (140) 8 (203) 9-7/8 (251) 12-7/8 (327) 26-1/4 (667) 30-3/4 (781) 53 (1272)
Notes: 1. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back. 2. Consult ASCO for dimensions on enclosures other than UL type 1. 3. Optional arrangement.
Open Configuration 30, 70, 100, 125,150, 200, 230 260, 400 600 800, 1000, 1200 1600, 2000 2600, 3000 4000
Distributed Power / Load Management
As we become more dependent on the quality and reliability of electrical power, interruption or complete loss of power can create serious and even crippling financial losses, or impose dangers to life and safety. ASCO Power Technologies (ASCO) provides the solutions to handle the transfer of critical loads to emergency sources reliably and with state of the art products. Using ASCO products can mean the difference between a minor inconvenience and a major catastrophe. You’ll find ASCO Power Transfer Switches wherever there is a critical load to be protected.
2
When flexibility in power switching is a must, ASCO offers a variety of product solutions to meet virtually every application requirement, including distributed generation applications. That’s why the 4000 SERIES is available in open, delayed, closed and closed soft load configurations. Additionally, switched or overlapping neutral options provide for reliable operation of ground fault protection systems and reduction of voltage transients from unbalanced load switching.
Poles
Width inches (mm)
2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral C 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/C
24 (610) 24(610) 34 (864) 38 (965) 38 (965) 38 (965) 38 (965) 60 (1524)
56 (1422) 63 (1600) 72 (1829) 87 (2210) 91 (2311) 87 (2210) 91 (2311) 91 (2311)
150, 260, 400
2, 3 or 3 with neutral B
18-1/2 (470)
25 (635)
8 (203)
600 800, 1000, 1200 1600, 2000 2600, 3000 4000
2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B
19 (483) 27 (686) 33-1/4 (845) 33-1/4 (845) 60 (1524)
30 (762) 31 (787) 28 (711) 28 (711) 70 (1778)
9-7/8 (251) 12-7/8 (327) 26-1/4 (667) 30-3/4 (781) 53 (1272)
Switch Rating Amps
Height Depth inches (mm) inches (mm)
Enclosed UL Type 1 2 150, 260, 400 600 800, 1000 1200 1600, 2000 1 1600, 2000 (front connected) 3000 1 4000 1
14 (356) 17(432) 20 (508) 23 (584) 48 (1219) 23 (584) 60 (1524) 72 (1829)
Open Configuration 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B
10-1/4 (260) 18-1/2 (470) 19 (483) 27 (686) 33-1/4 (845) 33-1/4 (845) 60 (1524)
Notes: 1. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back. 2. Consult ASCO for dimensions on enclosures other than UL type 1.
Telecom Central Offices Process Manufacturing / Wafer Fabrication Plants /
Closed Transition and Delayed Transition Transfer Switching 4ACTS, 4NCTS, 4ADTS, 4NDTS
Shipping Weights1 2-Position Transfer Switching 4ATS, 4NTS Switch Rating Amps
Poles
Enclosed lb (kg)
Open lb (kg)
30, 70, 100, 125 30, 70, 100, 125 30, 70, 100, 125 150, 200, 230 150, 200, 230 150, 200, 230 260, 400 260, 400 260, 400 600 600 600 800, 1000 800, 1000 800, 1000 1200 1200 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 2600, 3000 4000 4000 4000
2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B
67 (31) 70 (32) 73 (33) 69 (32) 72 (33) 75 (34) 216 (98) 223 (101) 230 (105) 316 (143) 324 (147) 332 (151) 400 (182) 420 (192) 446 (203) 685 (312) 705 (321) 731 (333) 1110 (503) 1160 (525) 1210 (548) 1365 (620) 1430 (649) 1495 (679) 1969 (893) 2149 (975) 2328 (1056)
15 (7) 18 (8) 21 (10) 17 (8) 20 (9) 23 (11) 82 (37) 89 (40) 102 (46) 88 (40) 96 (44) 104 (47) 150 (68) 170 (78) 196 (90) 150 (68) 170 (78) 196 (90) 370 (167) 420 (190) 470 (213) 405 (184) 470 (213) 535 (243) 1258 (571) 1451 (658) 1623 (736)
Notes: 1. Open weights include transfer switch and control panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions.
Shipping Weights Closed Transition and Delayed Transition Transfer Switching 4ACTS, 4NCTS, 4ADTS, 4NDTS
* All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
Switch Rating Amps
Poles
Enclosed lb (kg)
Open* lb (kg)
150, 260, 400 150, 260, 400 150, 260, 400 600 600 600 800, 1000 800, 1000 800, 1000 1200 1200 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 2600, 3000 4000 4000 4000
2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B
235 (107) 242 (110) 250 (113) 335 (152) 343 (156) 352 (159) 420 (192) 450 (205) 480 (219) 710 (324) 740 (337) 770 (351) 1300 (590) 1350 (612) 1400 (635) 1555 (706) 1620 (735) 1685 (765) 1969 (893) 2149 (975) 2328 (1056)
101 (46) 108 (49) 115 (52) 107 (48) 115 (52) 124(56) 175 (80) 205 (94) 235 (108) 175 (80) 205 (94) 235 (108) 505 (229) 555 (252) 605 (274) 540 (245) 660 (300) 725 (329) 1258 (571) 1451 (658) 1623 (736)
Notes: 1. Open weights include transfer switch and control panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions.
20
* All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
21
4000 SERIES DESIGNED TO FIT ANYWHERE*
4000 SERIES DESIGNED TO FIT ANYWHERE* Critical Loads Demand ASCO
2-Position Transfer Switching 4ATS, 4NTS Switch Rating Amps
Poles
Width Height Depth inches (mm) inches (mm) inches (mm)
Enclosed UL Type 1 2
ASCO 4000 SERIES Power Transfer Switches Protecting: Healthcare Facilities Web Hosting, Internet Data Centers Commercial Buildings / Industrial Buildings
30, 70, 100, 125, 150, 200, 230 260, 400 600 800, 1000 1200 1600, 2000 1 1600, 2000 (front connected)3 2600, 3000 1 4000 1
2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral C 2, 3 or 3 with neutral A/B
18 (457) 24 (610) 24 (610) 34 (864) 38 (965) 38 (965) 38 (965) 38 (965)
48 (1219) 56 (1422) 63 (1600) 72 (1829) 87 (2210) 91 (2311) 87 (2210) 91 (2311)
13 (330) 14 (356) 17 (432) 20 (508) 23 (584) 48 (1219 23 (584) 60 (1524)
2, 3 or 3 with neutral A/B
60 (1524)
91 (2311)
72 (1829)
10-1/4 (260) 25 (635) 30 (762) 31 (787) 28 (711) 28 (711) 70 (1778)
5-1/2 (140) 8 (203) 9-7/8 (251) 12-7/8 (327) 26-1/4 (667) 30-3/4 (781) 53 (1272)
Notes: 1. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back. 2. Consult ASCO for dimensions on enclosures other than UL type 1. 3. Optional arrangement.
Open Configuration 30, 70, 100, 125,150, 200, 230 260, 400 600 800, 1000, 1200 1600, 2000 2600, 3000 4000
Distributed Power / Load Management
As we become more dependent on the quality and reliability of electrical power, interruption or complete loss of power can create serious and even crippling financial losses, or impose dangers to life and safety. ASCO Power Technologies (ASCO) provides the solutions to handle the transfer of critical loads to emergency sources reliably and with state of the art products. Using ASCO products can mean the difference between a minor inconvenience and a major catastrophe. You’ll find ASCO Power Transfer Switches wherever there is a critical load to be protected.
2
When flexibility in power switching is a must, ASCO offers a variety of product solutions to meet virtually every application requirement, including distributed generation applications. That’s why the 4000 SERIES is available in open, delayed, closed and closed soft load configurations. Additionally, switched or overlapping neutral options provide for reliable operation of ground fault protection systems and reduction of voltage transients from unbalanced load switching.
Poles
Width inches (mm)
2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral C 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/C
24 (610) 24(610) 34 (864) 38 (965) 38 (965) 38 (965) 38 (965) 60 (1524)
56 (1422) 63 (1600) 72 (1829) 87 (2210) 91 (2311) 87 (2210) 91 (2311) 91 (2311)
150, 260, 400
2, 3 or 3 with neutral B
18-1/2 (470)
25 (635)
8 (203)
600 800, 1000, 1200 1600, 2000 2600, 3000 4000
2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B
19 (483) 27 (686) 33-1/4 (845) 33-1/4 (845) 60 (1524)
30 (762) 31 (787) 28 (711) 28 (711) 70 (1778)
9-7/8 (251) 12-7/8 (327) 26-1/4 (667) 30-3/4 (781) 53 (1272)
Switch Rating Amps
Height Depth inches (mm) inches (mm)
Enclosed UL Type 1 2 150, 260, 400 600 800, 1000 1200 1600, 2000 1 1600, 2000 (front connected) 3000 1 4000 1
14 (356) 17(432) 20 (508) 23 (584) 48 (1219) 23 (584) 60 (1524) 72 (1829)
Open Configuration 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B
10-1/4 (260) 18-1/2 (470) 19 (483) 27 (686) 33-1/4 (845) 33-1/4 (845) 60 (1524)
Notes: 1. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back. 2. Consult ASCO for dimensions on enclosures other than UL type 1.
Telecom Central Offices Process Manufacturing / Wafer Fabrication Plants /
Closed Transition and Delayed Transition Transfer Switching 4ACTS, 4NCTS, 4ADTS, 4NDTS
Shipping Weights1 2-Position Transfer Switching 4ATS, 4NTS Switch Rating Amps
Poles
Enclosed lb (kg)
Open lb (kg)
30, 70, 100, 125 30, 70, 100, 125 30, 70, 100, 125 150, 200, 230 150, 200, 230 150, 200, 230 260, 400 260, 400 260, 400 600 600 600 800, 1000 800, 1000 800, 1000 1200 1200 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 2600, 3000 4000 4000 4000
2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B
67 (31) 70 (32) 73 (33) 69 (32) 72 (33) 75 (34) 216 (98) 223 (101) 230 (105) 316 (143) 324 (147) 332 (151) 400 (182) 420 (192) 446 (203) 685 (312) 705 (321) 731 (333) 1110 (503) 1160 (525) 1210 (548) 1365 (620) 1430 (649) 1495 (679) 1969 (893) 2149 (975) 2328 (1056)
15 (7) 18 (8) 21 (10) 17 (8) 20 (9) 23 (11) 82 (37) 89 (40) 102 (46) 88 (40) 96 (44) 104 (47) 150 (68) 170 (78) 196 (90) 150 (68) 170 (78) 196 (90) 370 (167) 420 (190) 470 (213) 405 (184) 470 (213) 535 (243) 1258 (571) 1451 (658) 1623 (736)
Notes: 1. Open weights include transfer switch and control panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions.
Shipping Weights Closed Transition and Delayed Transition Transfer Switching 4ACTS, 4NCTS, 4ADTS, 4NDTS
* All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
Switch Rating Amps
Poles
Enclosed lb (kg)
Open* lb (kg)
150, 260, 400 150, 260, 400 150, 260, 400 600 600 600 800, 1000 800, 1000 800, 1000 1200 1200 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 2600, 3000 4000 4000 4000
2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B
235 (107) 242 (110) 250 (113) 335 (152) 343 (156) 352 (159) 420 (192) 450 (205) 480 (219) 710 (324) 740 (337) 770 (351) 1300 (590) 1350 (612) 1400 (635) 1555 (706) 1620 (735) 1685 (765) 1969 (893) 2149 (975) 2328 (1056)
101 (46) 108 (49) 115 (52) 107 (48) 115 (52) 124(56) 175 (80) 205 (94) 235 (108) 175 (80) 205 (94) 235 (108) 505 (229) 555 (252) 605 (274) 540 (245) 660 (300) 725 (329) 1258 (571) 1451 (658) 1623 (736)
Notes: 1. Open weights include transfer switch and control panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions.
20
* All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
21
START-UP COMMISSIONING, SERVICE & SCHEDULED MAINTENANCE
A SCO Power Technologies 50 Hanover Road F l o r ha m Pa r k , N J 0 7 9 3 2 USA ASCO Services Inc. , provides a wide range of technical services to users of automatic transfer switches in emergency and standby power systems. These services include comprehensive scheduled maintenance programs, modifications, upgrades and emergency repairs. Systems serviced range in complexity from a single automatic transfer switch to multiple transfer switches and engine generators. ASCO Services is a wholly owned subsidiary and the exclusive OEM service arm of ASCO Power Technologies, the world’s largest manufacturer of power transfer switching and control equipment. Serving the needs of ASCO’s customers is a major focus; however, ASCO Services is also routinely called upon to perform regular maintenance and emergency repairs on equipment manufactured by others.
ASCO Services offers comprehensive maintenance agreements that detail the preventive care needed to keep emergency power systems ready to respond. A service agreement is an effective way to budget in advance and avoid unexpected expenditures. A 35 point checklist is utilized to assure critical systems and components are kept in top operating condition. These preventive programs can be customized for national accounts. This customization permits central corporate control of costs and scheduling. Periodic reports provide detailed information as to activity, maintenance performed and corrective action.
8 0 0 8 0 0 A SCO www.ascopower.com www.ascoapu.com
ASCO Services deploys more than 75 service personnel strategically located throughout the nation to provide 24-hour response in emergency situations. Each region is manned by experienced personnel who receive ongoing support and training in the newest equipment concepts, design and controls. Because equipment can be utilized for a long number of years, field representatives also receive education on older designs. This knowledge can be invaluable in addressing total system concerns, evaluating problems and providing solutions on site. Service vans are equipped with parts and advanced testing equipment that facilitate these on-the-spot repairs. ASCO Services 1-800-800-ASCO.
Emerson Network Power. The global leader in enabling Business-Critical ContinuityTM.
EmersonNetworkPower.com Outside Plant
AC Power Connectivity
Embedded Computing Embedded Power
DC Power
Infrastructure Management & Monitoring
Power Switching & Controls Precision Cooling
Racks & Integrated Cabinets Services Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co. Publication 3144 R4
19
© July, 2010
Printed in the U.S.A.
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 1
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 2
Critical Loads Demand ASCO
ASCO 7000 SERIES Power Transfer Switches Protecting: Healthcare Facilities Web Hosting, Internet Data Centers Commercial Buildings / Industrial Buildings Telecom Central Offices Process Manufacturing / Wafer Fabrication Plants Distributed Power / Load Management
As we become more dependent on the quality and reliability of electrical power, interruption or complete loss of power can create serious and even crippling financial losses, or impose dangers to life and safety. ASCO Power Technologies (ASCO) provides the solutions to handle the transfer of critical loads to emergency sources reliably and with state of the art products. Using ASCO products can mean the difference between a minor inconvenience and a major catastrophe. You’ll find ASCO Power Transfer Switches wherever there is a critical load to be protected.
2
When flexibility in power switching is a must, ASCO offers a variety of product solutions to meet virtually every application requirement, including distributed generation applications. That’s why the 7000 SERIES is available in open, delayed, closed and closed soft load configurations. Additionally, switched or overlapping neutral options provide for reliable operation of ground fault protection systems and reduction of voltage transients from unbalanced load switching. ASCO Power Transfer Switches are the first CE Marked, IEC 60947-6-1 compliant Transfer Switches in the world.
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 3
The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World.
7000 SERIES ASCO Power Transfer Switches are the standard of the industry. High speed transfer of loads between alternate sources of power, regardless of ampacity size, is achieved by a reliable, field proven solenoid operating mechanism. When combined with a programmable microprocessor controller with keypad and LCD display, they offer the most advanced method of transferring all types of loads, such as motors, electronic drives, UPS's and microprocessor based systems. 7000 SERIES Power Transfer Switches are available open or enclosed, in ampacity sizes from 30 through 4000 Amperes with the largest selection of optional accessories offered anywhere. All switching configurations are available with an integrally mounted bypass-isolation switch and/or rated for use in service entrance applications. Fig. 1: Three Pole 7000 SERIES Automatic Transfer Switch rated 1600 Amperes (shown with optional front connected terminals and Power Manager).
7000 SERIES Power Transfer Switches Product Features • Conventional two-position transfer configuration, plus closed and delayed transition modes of operation. All configurations available with either automatic or nonautomatic control. • UL listed to 1008 Transfer Switch Equipment & CSA certified to CSA 22.2 No.178-1978 Automatic Transfer Switches. • Qualified and certified to IEC 60947-6-1, CE marked (optional). (Limited to certain accessories.) • Rated up to 600 VAC, 30 through 4000 Amperes. • Reliable and field proven solenoid operating mechanism. • High withstand and close-on ratings including short time withstand current rating for optimum flexibility in circuit breaker coordination (600-4000 Amperes).
• Front replaceable main and arcing contacts (800-4000 Amperes). • Programmable microprocessor controller with keypad and LCD display. • Centrally located terminal block for customer control connections (260-4000 Amperes). • 16mm, industrial grade control switches and indicating lights. • Switch position LED indicators and source acceptability lights. • Standard ground conductor connections. • Four auxiliary contacts, two contacts closed when switch is in normal position and two contacts closed when switch is in emergency position. • Local/remote communications capability for interfacing with ASCO POWERQUEST ® communication products.
• Solid, switched, or overlapping neutral conductor options.
3
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 4
7000 SERIES Power Switching Solutions
Closed Transition Transfer Switching ASCO Automatic Closed Transition Transfer Switches feature main contacts that overlap, permitting the transfer of electrical loads without power interruption. The switch transfers in a make-before-break mode if both sources are within acceptable parameters. Control logic continuously monitors source conditions and automatically determines whether the load transfer should be open (conventional non-overlap mode) or closed transition. Available 150 through 4000 Amperes. Closed Transition Transfer within 5 electrical degrees is achieved passively, without control of engine generator set. Therefore, no additional control wire runs are required between the ATS and engine generator set governor. Plus, protective relaying may not be required under normal operation since the contact overlap time is less than 100 milliseconds (consult your local utility on protective relay requirements). Failure to synchronize indication and extended parallel time protection is built-in to all 7000 SERIES closed transition controls to prevent abnormal operation. Fig. 2: Four pole, Closed Transition Transfer Switch rated 1000 Amperes in Type 1 enclosure.
Delayed Transition Transfer Switching ASCO Delayed Transition Transfer Switches are designed to provide transfer of loads between power sources with a timed load disconnect position for an adjustable period of time. Applications include older style variable frequency drives, rectifier banks, and load management applications. • Available in 150 through 4000 Amperes. • Utilizes reliable, field proven solenoid operating mechanisms. • Mechanical interlocks to prevent direct connection of both sources. • Indicator light (16mm, industrial grade type LED) for load disconnect position. • Adjustable time delay for load disconnect position.
Fig. 3: Four pole, Delayed Transition Transfer Switch rated 2000 Amperes.
4
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 5
7000 SERIES Power Switching Solutions Non-Automatic Transfer Switching ASCO Non-Automatic Transfer Switches are electrically operated units which are operated with manual control switches mounted locally or at remote locations. • Sizes from 30 through 4000 Amperes. • Microprocessor based controller provides for addition of optional accessories. • Controller prevents inadvertent operation under low voltage conditions. • Low control circuit operating currents allow for long line runs between remotely mounted manual control switches and the transfer switch. • Source acceptability lights inform operator if sources are available to accept load. • Standard inphase monitor can be activated for transferring motor loads. Fig. 4: Three pole Non-Automatic, electrically operated 400 ampere switch shown in Type 1 enclosure.
Withstand and Close-On Ratings for all 7000 SERIES Products
5
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 6
7000 SERIES Power Switching Solutions Automatic Transfer Bypass-Isolation Switches
Fig. 6: Rated 600- 1200 Amps
Fig. 5: Rated 150-600 Amps
ASCO Automatic Transfer & Bypass-Isolation Switches are available in open transition, closed transition and delayed transition designs. The bypass and isolation features allow the primary automatic transfer switch to be inspected, tested, and maintained without any interruption of power to the load. They also provide redundant power transfer in the event the ATS is disabled or removed from service.
Fig. 7: Rated 800-3000 Amps
Fig. 8: Rated 4000 Amps
• Transfer switch is drawout design for ease of maintenance. • Bypass and isolation handles are permanently mounted. The bypass switch has dead front quick-make, quick-break operation for transferring of loads between live sources. • Bypass switch is fully rated for use as a manual 3-position transfer switch. • Bypass and isolation functions are simple, requiring a total of two operating handles.
• Available 150 to 4000 Amperes. • Allows bypass-isolation without load interruption. • Bypass switch and transfer switch have identical electrical ratings. • Heavy duty mechanical interlocks prevent undesirable operation. • Bypass contacts carry current only during bypass mode.
• No toggle switches, push buttons, selector switches or levers are required for bypass-isolation operation. • Mechanical indicators show bypass and transfer switch positions. • 800 -1200 ampere available in shallow depth, front connected or rear connected designs.
Transfer Switch Drawout Features (150-4000 Amperes) Automatic Secondary Disconnects
Automatic Shutters (optional on 1600-4000amps) Fig. 9: Bypass-Isolation Transfer Switch secondary disconnects and optional automatic shutters.
6
• Automatic secondary disconnects remove all control power as switch is withdrawn. • Drawout carriage provides for easy transfer switch maintenance and/or removal via commercially available breaker hoists.
Self Aligning Jaws
• Optional transfer switch lifting yoke kit available • Optional automatic shutters which close when the transfer switch is withdrawn to provide bus isolation, specify accessory 82C.(1600-4000A only)
Fig. 10: Bypass-Isolation Transfer Switch self aligning power jaws.
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 7
7000 SERIES Power Switching Solutions Bypass and Isolation Handles - Simple as 1, 2, 3 LED Indicators
1
Bypass switch position
Source availability
Isolation handle position Transfer switch position
Bypass to Normal
Push in bypass handle and turn it counter clockwise Bypass Handle
*Standard on switches up through H 1200A. Specify ACC 82E for G frame 1600-4000A
E
L
Isolation Handle
Not in “auto” flashing LED Fig. 11: Transfer Bypass Status Panel*
Bypass Switch
N Automatic Transfer Switch
2
Test Position Bypass Switch
E
L Isolation Handle
Mechanical bypass switch position flags
Turn isolation handle counter clockwise until window shows “Test”
3
N Automatic Transfer Switch
Isolation Position Bypass Switch
Isolation handle
Padlocking provisions
Mechanical isolation handle position window (connected/test/isolate) Fig. 12: Bypass-Isolation Switch user interface
E
L Isolation Handle Turn isolation handle counter clockwise until window shows “Isolate”
N Automatic Transfer Switch
Key: Represents Current Flow In test position control panel remains energized to allow for electrical operation of a transfer switch.
7
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 8
7000 SERIES Service Entrance Power Transfer Switches The ASCO Service Entrance Power Transfer Switch combines automatic power switching with a disconnect and overcurrent protective device on the utility source. The power transfer switch meets all National Electric Code requirements for installation at a facility’s main utility service entrance. Service entrance rated transfer switches generally are installed at facilities that have a single utility feed and a single emergency power source. A circuit breaker serves as the utility disconnect and links are provided to disconnect both neutral and ground connections. This product is either UL 1008 or UL 891 listed and is available up to 600V and 4000A in Standard, Delayed, Closed Transition, Soft Load, and Bypass Isolation Configurations.
Fig. 13: Ground and neutral disconnect links
Standard Features • Available from 150 to 4000 Amperes • ASCO 7000 SERIES Power Transfer Switch is UL 1008 Listed • Standard UL Type 1 Enclosure • Disconnect and overcurrent protective device on the utility source: molded case circuit breaker 150 to 2000 Amp; insulated case 3000 to 4000 Amp • Disconnect link on Neutral • Disconnect link on Ground • Ground and Neutral Bus, all silver-plated copper • Solderless screw type terminals for External Power Connections • Meets all NEC requirements for use as service entrance • Internet enabled monitoring and control • Service entrance breakers rated 100% for 1000 Amps and above; 80% below 1000Amps
Ground Disconnect Link
Circuit Breaker
Neutral Disconnect Link
Load
Utility
N
Ground Fault Current Transformer* Switched Neutral
Ø
ATS GFCT Ground Fault Current Transformer ATS - Automatic Transfer Switch Ø
N
Emergency
One line diagram of a typical service entrance rated transfer switch available in Solid, Switched or Overlapping Neutral * Ground fault trip protection provided on sizes of 1000 Amperes and above
Optional Features • Enclosures - Secure Double Door - UL Type 3R w/strip heater & thermostat - UL Type 4 or 4X - UL Type 12
• Connections - Crimp lugs - Bus Riser on Normal, Emergency or Load
• Protective Relays/Metering - Accessory 85L , see page 15
• Surge Suppression
- Accessory 73, Surge protector (see pg. 14) ASCO POWERQUEST ® products (see pages 16-21) • - ASCO 72E Ethernet Connectivity module, page 17 - ASCO 5310/5350 Remote annunciators, page 17 - ASCO 5400 Power Quality Meters, page 17 • Additional Breaker(s) - Circuit Breaker on Emergency - Load Distribution Panel • Optional high AIC ratings on breakers Consult ASCO for additional features
8
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 9
7000 SERIES Service Entrance Power Transfer Switches Ordering Information To order an ASCO 7000 SERIES Service Entrance Power Transfer Switch, complete the following catalog number. 7 A US + A + 3 + 400 + N + 5X + C Neutral Code*
Product A
Automatic US
N
NonUB Automatic CUS CUB DUS DUB
Phase Poles
Conventional 2A Solid Neutral Position (standard) Open Transition B Switched Bypass Neutral Closed Transition C Overlapping Closed Transition Neutral Bypass Delayed Transition Delayed Transition Bypass
2 3
Amperes
Voltage Code
70, 100 150, 200 225, 250 400, 600 800,1000 1200,1600, 2000,2500, 3000 4000
C D E F H J K L M N P Q R
208 220 230 240 380 400 415 440 460 480 550 575 600
Grp Code
Enclosure
5 C Type 1 enclosure 5XM Type 3R secure optional double door accesN Type 4 secure sories double door P Type 4X secure double door (31b SS) Q Type 12 secure double door
*Note. Switches rated 150, 600-3000 amps available with 2, 3 or either conventional switched neutral (4 poles) or overlapping neutral (optional). For 4 pole applications on switches rates 150 to 400 amps (bypass switches only) and 4000 amps specify overlapping switched neutral (optional). Conventional switched neutral is provided on delayed transition transfer products when specified.
The Example Catalog Number above is 7AUSA3400N5XC (X is used to specify optional accessories).
Dimensions and Weights for non-bypass configurations Type 1 and 3R Enclosures4 Switch Rating Phase Neutral Poles Code amps 70, 100 ,150, 200, 225
250, 400
600 , 800 1
1
10001, 12001 16001, 20001 25001, 30001
2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 3 3 3 3
STD B, C STD B, C STD C STD C STD B, C STD B, C STD B, C STD B, C STD B, C STD B, C
Switch Rating Phase Neutral Poles Code amps 70, 100 ,150, 200, 225
250, 400
6001, 8001
10001, 12001 16001, 20001 25001, 30001
2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 3 3 3 3
STD B, C STD B, C STD C STD C STD B, C STD B, C STD B, C STD B, C STD B, C STD B, C
Type 1 Dimensions, In. (mm) Width Height Depth 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 36.5 (927) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965)
48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 48.5 (1232) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311)
13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 13.25 (337) 28 (711) 28 (711) 28 (711) 28 (711) 48 (1218) 48 (1218) 48 (1218) 48 (1218) 48 (1218) 48 (1218) 72 (1829) 72 (1829)
Approx. Shipping Weight Lb. (kg) 400 (185) 408 (188) 408 (188) 416 (192) 400 (185) 408 (188) 408 (188) 416 (192) 800 (370) 820 (378) 820 (378) 846 (390) 1085 (501) 1105 (510) 1105 (510) 1134 (523) 2590 (1198) 2640 (1218) 4590 (2118) 4655 (2148)
Type 3R Dimensions, In. (mm) Width Height Depth
Approx. Shipping Weight Lb. (kg)
48(1219) 48(1219) 48(1219) 48(1219) 48(1219) 48(1219) 48(1219) 48(1219) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 95.5(2426) 96(2438) 96(2438)
520 (236) 530 (240) 530 (240) 548 (249) 520 (236) 530 (240) 530 (240) 548 (249) 990 (458) 1010 (467) 1010 (467) 1036 (479) 1305 (604) 1325 (613) 1325 (613) 1354 (626) 2890 (1337) 2940 (1360) 5350 (2474) 5415 (2504)
36(914) 36(914) 36(914) 36(914) 36(914) 36(914) 36(914) 36(914) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041) 41(1041)
16 (406) 16 (406) 16 (406) 16 (406) 16 (406) 16 (406) 16 (406) 16 (406) 34(864) 34(864) 34(864) 34(864) 62(1575) 62(1575) 62(1575) 62(1575) 62(1575) 62(1575) 85(2159) 85(2159)
Ampere Interrupting Capacity (AIC) Ratings AIC Rating (kA) Switch Rating amps Standard Optional 70 - 225
25
35
250
25
35
400
35
35
600, 800
65
N/A
1000,1200
65
N/A
1600, 2000
65
100
2500, 3000
100
N/A
4000
100
N/A
Notes: 1. Unit is designed for top and bottom cable entry for all services and load. 2. Enclosures for 600 — 3000 amps are free standing. 3. When temperatures below 32° F can be experienced, special precautions should be taken, such as the inclusion of strip heaters, to prevent condensation and freezing of this condensation. This is particularly important when environmental enclosures (Type 3R, 4 & 12) are ordered for installation outdoors. 4. Dimensional data is approximate and subject to change. Certified dimensions available upon request.
9
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 10
7000 SERIES Microprocessor Controller
The 7000 SERIES Microprocessor Based Controller is used with all sizes of Power Transfer Switches from 30 through 4000 Amperes. It represents the most advanced digital controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and diagnostic functions required for most emergency and standby power applications. Because of severe voltage transients frequently encountered with industrial distribution systems, the microprocessor logic board is separated and isolated from the power board as shown below. This improves electrical noise immunity performance and helps assure compliance with the rigorous transient suppression standards highlighted below.
Fig. 14: 7000 SERIES Microprocessor Controller.
Fig.15: Microprocessor Power and Logic PC Boards.
7000 SERIES Microprocessor Based Controller Emission Standard - Group 1, Class A Generic Immunity Standard, from which: Electrostatic Discharge (ESD) Immunity Radiated Electromagnetic Field Immunity Electrical Fast Transient (EFT) Immunity Surge Transient Immunity Conducted Radio-Frequency Field Immunity Voltage Dips, Interruptions and Variations Immunity
10
EN 55011:1991 EN 50082-2:1995 EN 61000-4-2:1995 ENV 50140:1993 EN 61000-4-4:1995 EN 61000-4-5:1995 EN 61000-4-6:1996 EN 61000-4-11:1994
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 11
7000 SERIES Microprocessor Controller Features • Digital microprocessor. • Touch pad programming of features and settings without the need for meters, or variable power supplies.
• Password protection to prevent unauthorized tampering of settings.
• Sixteen (16) selectable operating voltages available in a single Controller.
• Remote monitoring and control with ASCO POWERQUEST ® communications products. Specify optional accessory 72E.
• On-board diagnostics provide control panel and ATS status information to analyze system performance.
• Load shed option for bus optimization applications. Specify optional accessory 30B.
• Displays and counts down active timing functions.
• Historical event log
• Selectable multi-language display (English, German, Portuguese, Spanish, or French. For others contact ASCO).
• Statistical ATS systems monitoring information
Voltage and Frequency Sensing
Time Delays
• 3-Phase under and over voltage settings on normal and emergency sources.
• Engine start time delay - delays engine starting signal to override momentary normal source outages - adjustable 0 to 6 seconds.
• Under and over frequency settings on normal and emergency. • True RMS Voltage Sensing with +/- 1% accuracy; Frequency Sensing Accuracy is +/- 0.2%.
• Transfer to emergency time delay - adjustable 0 to 60 minutes.
• Selectable settings: single or three phase voltage sensing on normal and emergency; 50 or 60Hz.
• Emergency source stabilization time delay to ignore momentary transients during initial generator set loading - adjustable 0 to 6 seconds.
• Phase sequence sensing for phase sensitive loads.
• Retransfer to normal time delay with two settings:
• Voltage unbalance detection between phases.
• Power failure mode - 0 to 60 minutes. • Test mode - 0 to 10 hours.
Status and Control Features • Output contact (N/O or N/C) for engine-start signals. • Selection between “commit/no-commit” on transfer to emergency after engine start and normal restores before transfer. • Advanced inphase algorithm which automatically measures the frequency difference between the two sources and initiates transfer at appropriate phase angles to minimize disturbances when transferring motor loads.
• Unloaded running time delay for engine cooldown adjustable 0 to 60 minutes. • Pre and post transfer signal time delay for selective load disconnect with a programmable bypass on source failures - adjustable 0 to 5 minutes. This signal can be used to drive a customer furnished relay, or for (2) sets of double throw contacts rated 3 amps at 480 volts AC, specify ASCO optional accessory 31Z.
• Event log displays 99 logged events with the time and date of the event, event type and event reason.
• Fully programmable engine exerciser with seven independent routines to exercise the engine generator, with or without loads, on a daily, weekly, bi-weekly or monthly basis.
• Output signals for remote indication of normal and emergency source acceptability
• Contains all alarm signals, logic and time delays for use with closed transition switches.
• Statistical ATS/System monitoring data screens which provide:
• Insynch time delay - 0 to 3 seconds.
• Total number of ATS transfers.
• Failure to synchronize - 1 to 5 minutes.
• Number of ATS transfers caused by power source failure.
• Extended parallel - 0.1 to 1.0 seconds.
• Total number of days ATS has been in operation. • Total number of hours that the normal and emergency sources have been available.
• Delayed transition load disconnect time delay adjustable 0 to 5 minutes.
11
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 12
7000 SERIES User Controls and Indicators Control Switches and Indicating Lights for Conventional 2-Position Switches • Switch position indicating lights (16 mm, industrial grade LEDs). • Source acceptability indicating lights with true indication of the acceptability of each source, as determined by the voltage, frequency, voltage unbalance, and phase sequence settings of the control panel (16mm, industrial grade LEDs). • Three position (16mm, industrial grade type) selector switch: • Automatic: Normal maintained position. • Test: Momentary position to simulate normal source failure for system test function.
Fig. 16: 7000 SERIES User Controls and Indicators.
• Reset Delay Bypass: Momentary position to bypass transfer and re-transfer time delay.
Control Switches and Indicating Lights for Closed Transition Switches • Extended Parallel Time - Provides visual indication when the pre-set extended parallel time has been exceeded. The controls automatically open the emergency or normal main contacts. Separate contact also available to shunt trip external breaker. • Failure To Synchronize - Visually displays a failure to synchronize alarm if the time delay settings is exceeded, during closed transition transfer operation. • TS Locked Out - Prevents transfer in either direction if the extended parallel time is exceeded. • Alarm Reset - Resets extended parallel and failure to synchronize alarms.
Fig. 17: 7000 SERIES User Controls and Indicators.
• Closed Transition Bypass - Pushbutton allows transfer between sources in an open transition mode.
7000 SERIES Power Control Center The 7000 SERIES microprocessor controller is a Power Control Center which allows the user to easily access detailed information on: system status; power source parameters; voltage, frequency and time delay settings; optional feature settings; historical event log; and system diagnostics. A four line, (20) character LCD has a backlit display which enables easy viewing under all conditions. The user can navigate through all screens using only six buttons, which also allows selection of: (18) different source parameter settings; (16) standard time delays; (12) standard feature settings; up to seven independent engine exercise routines; and even the language (English, German, Spanish, French, etc.) which appears on the display.
Fig. 18: 7000 SERIES Power Control Center.
12
Since the Power Control Center must be visible and operable through the enclosure door, it has been qualified for use in industrial and outdoor applications. This includes installation in Type 3R (outdoor/rainproof), 4 (weatherproof) and 12 (indoor/industrial) enclosures. For applications with regular exposure to direct sunlight a double door for UV protection is recommended.
11240_Brochure_r1_92344_Broch 10/15/12 7:59 AM Page 13
7000 SERIES Power Control Center Screens Status System Status Normal OK Load on Normal Displays system status in clear, concise language. Message shown indicates normal source is acceptable and the load is connected to the normal source.
Source Status Normal Source Vab=480V....................ABC Vbc=480V.........Vunbal=1% Vca=480V................60.0Hz Displays voltage for each phase, frequency, phase rotation and voltage unbalance for both normal and emergency sources.
Time Delay Status
Inphase Transfer Mode
Normal OK
Emerg OK
TD.Engine.Cooldown: 4min15s
Waiting for In-Sync -45o 0.02Hz
Active time delay status displays time remaining until next control event.
Displays the relative phase angle between sources and frequency differential to indicate the controller is awaiting an inphase condition.
Settings Voltage and Frequency Settings
Time Delay Settings
Normal Voltage Dropout.............85%.408V Pickup...............90%.432V O.V. Trip.........110%.528V
TD N>E Xfer Signal Bypass if N Fail: No Pre Xfer: 0 min 20S Post Xfer: 0 min 20S
Provides voltage and frequency setting values for normal and emergency sources. Voltage pick-up, dropout and trip settings are set in percentage of nominal voltage and are also displayed in rms voltage values.
Engine Exerciser P1..................Engine.Exerciser Enable:.....Yes....WLoad:....Yes Start:19h30. ALL MON Run.Time:...............2h15min Seven independent programs, load/no load selection, flexible run times and daily, weekly, bi-weekly and monthly exercise routines.
Provides direct reading display for setting time delays.
Feature Settings Shed Load Direction: Inphase: No
From E TD/0.25
Standard features can be activated with the keypad. As an example, when enabled, the “shed load” option causes the transfer switch to transfer the load off of the specified source. If desired, the load shed transfer can be made inphase.
Data Logging ATS Statistics ATS Statistics ATS Total Xfers: 46 SRC Fail Tot Xfers: 20 Days Energized: 36.5 Instant availability of statistical information on total number of ATS transfers, number of transfers caused by power failures and total days controller has been energized, plus more.
Historical Event Log 16.AUG02/95..........13h10:17 Eng.Start...............NormFail. 15.AUG02/95...........13h10:25 Xfer.N>E................................ Displays detailed information for last 99 events, including time of occurrence, length of event, date and reason for event.
13
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 14
7000 SERIES Optional Accessories Time Delays 2C
1G
1GB
Provides an extended time delay on engine starting. The standard feature one time delay is adjustable from zero to six seconds. Accessory 2C allows this time delay to be adjustable from zero to sixty minutes in one second intervals factory set at five minutes. Similar to accessory 2C except using 24 volt DC external input signal. 7000 SERIES controller remains active when both power sources are de-energized* Same as accessory 1G except using 120 volt AC external input*
Extension Harness 37B
Six foot (6’) extension harness to increase distance between transfer switch and control panel on open-type units.
Communications 72E
5150 Ethernet Connectivity Module offers communication to transfer switch and metering with embedded webpages. An Industrial Ethernet Switch mounted in the enclosure used in conjunction with 5150 Connectivity Module (acc. 72E) metering device. Includes 2 available Ethernet ports and 2 multimode ST Fiber connectors.
72SW
* add suffix 1 to include external power to power manager or power meter when applicable
Manual Controls for Automatic Transfer Switches
Surge Protection
6C
ASCO Pulsar 450 rated 65KA
6D
Reset switch for manual retransfer to normal with automatic retransfer in the event of emergency source failure. Selector switch for automatic/manual retransfer to normal. Automatic bypass if emergency fails.
Indicators 14A/14B Additional auxiliary contact sets to indicate switch position. Two sets are standard. Specify total number of sets if more are required. 18B
Two-pole, double-throw contacts operate when emergency source voltage is present at transfer switch terminals.
18G
Two-pole, double-throw contacts operate when normal source voltage is present at transfer switch terminals.
99
“Push-to-Test” feature on all pilot light indicators.
73AC1 73AC2 73AC3
Normal source protection. (3Ø, 4wire WYE) Emergency source protection. (3Ø, 4wire WYE) Load side protection. (3Ø, 4wire WYE)
Note: Other distribution voltages available (Contact ASCO).
Special Applications 45
Custom Alphanumeric nameplate mounted on the front of the switch
111A Generator - to - Generator for Standby Applications 111B Generator - to - Generator for Prime Power Applications 125 Seismic Certification to the requirements of the international building code for electrical equipment 131 Certification of compliance with the American Recovery & Reinvestment ACT (Buy American Provision) - Must be specified at time of order placement
Customer Control Circuits
Bypass-Isolation Switch Options
30A
Load-shedding circuit initiated by opening of a customer-supplied contact.
14A1
Auxiliary contact to close in “Bypass to Normal” position.
30B*
Load-shedding circuit initiated by removal of customer-supplied control voltage. *(Specify voltage).
14B1
Auxiliary contact to close in “Bypass to Emergency” position.
14T
31Z
Selective load disconnect control contacts (two provided) which operate with time delay prior to and/or after load transfer and retransfer.
Auxiliary contact to close when transfer switch is in “Automatic” position.
14U
Auxiliary contact to close when transfer switch is in “Isolate” position.
Terminal block for all customer control connections on 30-150 amp only (standard on all other sizes).
14V
Auxiliary; contact to close when transfer switch is in “Test” position. Automatic shutters for bus isolation when transfer switch is withdrawn. (see page 6 for details) LED Bypass status indicator, optional on G frame 1600A-4000A only. Standard for all other size switches
43R
Note: An externally operable quick-make, quick-break (QMQB), manual handle is available on some 7000 SERIES product configurations. (Consult ASCO for guidance.)
82C
Neutral Conductor Options
82E
• Solid neutral, with fully-rated terminals. (AL-CU) UL Listed. • Conventional neutral switching pole. • Overlapping neutral transfer contacts. Allows for proper ground-fault sensing and avoids generator voltage transients during transfer. Note: Specify neutral option in catalog number, see page 22 for instructions.
14
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 15
7000 SERIES Optional Accessories ASCO 5200 SERIES METERING Power Manager
Fig. 19: ASCO 5210 SERIES Power Meter.
The ASCO 5200 SERIES Power Meters are microprocessor based metering devices that provides real-time measurement of single and three phase power systems. The 5200 SERIES uses digital signal processing technology to measure voltage and current per phase; real, reactive and apparent power, and bi-directional energy. All measurements can be viewed locally with a backlit liquid crystal display and/or displayed remotely with ASCO POWERQUEST ® products.
Fig. 20: ASCO 5220 SERIES Power Manager.
Direct voltage input for systems up to 600 Volts AC can be monitored without the use of external potential transformers (PTs). Measures three phase currents and a fourth current input is available for measuring current in the neutral conductor. The 5200 SERIES includes one discrete input for transfer switch position.
Power Metering • Voltage: Line - Line: VAB, VBC, VCA, VAVERAGE Line - Neutral: VAN, VBN, VCN, VAVERAGE • Frequency: 45.0 to 66.0 Hertz • Current: IA, IB, IC, IAVERAGE • Unbalance %: Voltage, Amps • Real Power: KWA, KWB, KWC, KWNET • Reactive Power: KVARA, KVARB, KVARC, KVARNET • Apparent Power: KVAA, KVAB, KVAC, KVANET • Real Energy: KWHIMPORT, KWHEXPORT, KWHNET • Reactive Energy: KVARHIMPORT, KVARHEXPORT, KVARHNET • Power Factor: PFA, PFB, PFC, PFNET
Configurable Designations • Local - A four line, 20 character LCD backlit display. • 5220 Power Manager provides user programmable setpoints based on twelve metering and I/O parameters. Each setpoint allows the user to select the parameter, the trip & reset levels, the trip & reset time delays and the alarm type or relay output to trigger. This can be used for protective relaying and peak shaving applications. • 100 event data logging feature.
Integrated ATS Features When configured on load of ATS: • Displays ATS position. • Displays power data as a function of ATS position (normal/emergency). • Accumulates energy data separately for normal and emergency sources.
5220 Power Manager Data Access • Eight digital inputs, four relay outputs. • Input/Output 15-character, user definable screen display for identification of input/output signals.
Communications • Modbus RTU and TCP/IP capability • Ethernet compatible when combined with 5150 Connectivity Module (72E).
Optional Configurations and Connection Arrangements Connected To: Load Normal Emergency Load (BPS only)
5210 Acc. 135L Acc. 135L Acc. 135E N/A
5220 Acc. 85L Acc. 85N Acc. 85M Acc. 85SB*
Add suffix A1 to above metering designation if neutral conductor monitoring is required Note: Accessory 85 and 135 includes component mounting, CTs, shorting blocks and all necessary interwiring. *Bypass & isolation switch contacts wired to discrete Power Manager inputs.
Note: The ASCO Power Manager is also available as a separate unit for monitoring electrical parameters anywhere in the power distribution system.
15
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 16
PowerQuest Power Monitoring and Control Systems ®
FULFILL YOUR NEED Drill down for a closer look - Each transfer switch, generator, breaker and any other power equipment has its own dedicated screens.
It’s the new ASCO PowerQuest® Power Monitoring and Control family.
Critical Power Management System (CPMS) HVAC
The PowerQuest® family is the most comprehensive communication, monitoring and control solution ever offered by ASCO. It empowers you. It fulfills your need to test, manage loads, optimize the bus bar, remotely monitor and otherwise be aware of the status of your facility's utility source and on-site power. You have both the Power to Know and the Power to Do. Whether you require standard monitoring and control, or a comprehensive Critical Power Management System, PowerQuest can satisfy your needs. Hardware. Software. Installation and testing. Service. And upgrades and technology refreshes. A truly complete solution for all your communication, monitoring and control needs. The following PowerQuest® pages can help you determine– easily– the type of PowerQuest system you need for your ASCO power switching and controls, and third-party equipment.
16
Paralleling Control Switchgear
UPS Static Transfer Switches
Transfer Switches
Security
Fire Alarm Monitoring
Generators
Building Management System (BMS)
Internet
CPMS Display Terminal
Remote Display Terminal
PowerQuest® provides monitoring, alarming and control of Critical Power Management Systems, which comprise transfer switches, paralleling control switchgear, gensets, circuit breakers, distribution and other gear. It also integrates with building management systems. BE EMPOWERED PowerQuest® can enable you to: • Monitor and control power transfer switches, paralleling control switchgear, gensets, breakers, bus bars and other equipment • Monitor normal and emergency voltages and frequency and their settings • Know transfer switch position and source availability • Transfer and re-transfer loads for system testing • View and adjust transfer switch time-delay settings • Know each transfer switch’s rating and identification • Receive automatic alerts on system operation via e-mail, pager, or selected system alarms • View current, power and power factor • View transfer switch event log and know the transfer switch test schedule
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 17
7000 SERIES PowerQuest Monitoring & Control Components ®
Building-block components can be configured easily to provide exactly the degree of monitoring, control and communication you want for your on-site power system.
5150, 5160 Connectivity Modules
An ASCO 5150 Connectivity Module (left) provides 100 Mbps Ethernet Connectivity for ASCO Transfer Switches and Power Meters and includes AES 128-bit Encryption, as per NIST, for enhanced security. The ASCO 5160 Remote Connectivity Unit (RCU) (right) provides 10 Ethernet and Dual-Fiber Optic connections in a NEMA 3R enclosure.
5210, 5220 Power Meters
ASCO 5210 (left) and 5220 (right) Power Meters measure, displays and provides single- or 3-phase Energy and Power information with Ethernet via the ASCO 5150 Communication Module.
5310, 5350 Annunciators
ASCO 5310(left) and 5350(right) ATS Remote Annunciators provide distributed monitoring of transfer switch position and source availability as well as transfer test and re-transfer control.
5010 Remote Display Unit,(left) 5490 Critical Power Quality Meter, (right)
Enterprise Critical Power Management System
ASCO 5400 SERIES Power Quality Meters The ASCO Power Quality Meters provide intelligent power analysis, energy measurement and event recording for critical and sensitive loads. Its unique continuous waveform and harmonic recording capabilities ensure all events are captured, improves response time, and helps identify corrective action to power quality related issues.
5700 SERIES provide various levels of monitoring, control and management capability of power equipment. It seamlessly monitors ASCO transfer switches as well as generators, breakers, paralleling bus, panel boards and other power equipment via a 5221 PMU. It consists of servers and touch screen interfaces.
17
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 18
7000 SERIES PowerQuest Monitoring & Control The Power To Know Selecting the system that provides your level of need-to-know information and control...
18
You Need...
Your Application Is...
Desired Capabilities
Basic monitoring, remote alarming and control, or, if you simply want to know transfer switch status or perform monthly transfer testing
Residential, light commercial and retail establishments
Local or remote, floor-level monitoring and control, or as part of a larger, facility-wide monitoring and control system
A ‘specify-your-own’ Critical Power Management System (CPMS) that includes gensets, circuit breakers, and reports on energy, trending, power demand, bypass status, diagnostics, alarming, and component-level monitoring and control.
Commercial, retail, telecom, agriculture, municipal, such as waste water treatment, light industrial plants, educational campuses and healthcare facilities requiring distributed power and load management
Local, floor-level, or facilitylevel monitoring and control; 5700 systems can be configured in three capability levels: • Essential (single building) • Professional (multiple buildings, single campus) • Enterprise (multiple campuses)
A Critical Power Management System providing systemwide monitoring, alarming and control of transfer switches, paralleling control switchgear, gensets and distribution, both on and off site; also integrates PLCs, building management systems and on-site, simulator training. Power quality and a range of other information is provided.
Regional and global networks of data centers, financial institutions, Web hosting companies and healthcare campuses that operate expansive and sophisticated on-site power systems that are essential for providing 24/7 power reliability
Local floor-level monitoring and control, and remote system-wide monitoring and control seamlessly integrated with building management systems; communication paths can be Ethernet, Webbased PC’s and monitors; simulator training that mimics the live system allows conducting ‘what if’ scenarios, without risking system operation.
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 19
Identifies the ASCO products and components required to provide the functionality you need. Products
Required Components
Functionality
ASCO Series 185 and Series 300 Automatic Transfer Switches
Connectivity Modules and Annunciators
Locally monitor switch position, source availability and the status of on-site power system devices via customized Web page. Initiate tests and push-button remote transfer. Aural, visual alarms.
ASCO 4000 Series and 7000 Series Automatic Transfer Switches, including 7000 Series Bypass-Isolation
Standard components, plus Power Control System Management and Operator Interface Terminals
Monitor voltage and phase currents. Capture/store more data points. Display data on screen up to 42” inches. Interface with power control system, BMS. Integrate with Group 5 Controller. Get email alerts. For single buildings, single campuses and global facilities. Provides Energy, Alarm, and Outage/Test Reports that can be used to fulfill Joint Commission Requirements.
ASCO 7000 Series Automatic Transfer Switches, including Bypass-Isolation and 7000 Series Generator Paralleling Control Switchgear
Standard and Configurable components, plus higher performance Power Control System and Data Management Screens, and an on-site Simulator Training System
Interact fully with incoming utility service boards, mission critical paralleling gear, transfer switches, UPSs, STSs and PDUs...and interface with Building Management Systems. Capture, store and analyze quantities of data to optimize on-site power operation. Use your display devices and/or ASCO 42” LCD screen. Highly customize your GUI with sophisticated HMI/SCADA software.
19
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 20
PowerQuest 5700 Critical Power Management System ®
Utility
Generator
24 VDC QTY 8, 14 Awg 3P Volts/Amps
24 VDC QTY 4, 14 Awg 3P Volts/Amps
Generator
24 VDC QTY 8, 14 Awg 3P Volts/Amps
5160 RCU 24VDC or 120 VAC (Requires UPS)
5221 Power Manager Units
7000 ATS 24VDC 19” 5702 Operator Touch Panel (up to 100 with 5790 Server)
5350 Annunciator
5160 RCU 24VDC or 120 VAC (Requires UPS)
20
To RCU and Additional Networked Devices
19” 5702 Operator Touch Panel (up to 100 with 5790 Server)
Tx/Rx (pair of Fiber)
300 ATS 24VDC
5160 RCU 24VDC or 120 VAC (Requires UPS)
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 21
Breaker
24 VDC QTY 4, 14 Awg 3P Volts/Amps
UPS/Distribution
19” 5702 Operator Touch Panel (up to 100 with 5790 Server)
7000 ATS
24 VDC QTY 8, 14 Awg 3P Volts/Amps
5350 Annunciator ATS Status Annunciation Transfer Test Supports 8 ATS’s 24VDC/120VAC/220VAC
5710 CPMS Server • Drives 3 Remote 5702 Panels •Supports 32 Power Devices •Basic Monitoring and Control •Standard Performance
5700 CPMS Servers Note - Select One Server to install in Centralized Office 50° to 95°F (10°C to 35°C)
5750 CPMS Server Essential Features PLUS: • 5 Reporting Packages • BMS Modbus • Drives 10 Remote Support 5702 Panels •Remote E-Mail • Supports 64 Power Alarming Devices • Historical Trending
5790 CPMS Server Professional Features PLUS: •Drives 100 5702 Touch Panels •Redundant Power •Redundant Storage
To RCU and Additional Networked Devices
AWG Wire Size and Distance by others Category 6 Ethernet (300 Feet Max) Multi-Mode Fiber, 1300nm, 50/125um, ST Connectors (6500) Feet Max
•Redundant Processors •Ultimate Performance •128 Power Devices •Expanded Storage •Inter-facility Messaging
NOTES 1. This Drawing is to be used as a Model only; Actual network architecture will depend on equipment placement, cable length and type. 2. 5700 Series Products Operating Temperature is 50° to 95°F (10°C to 35°C) For altitudes above 2950 feet, the maximum operating temperature is derated 1°F/550 ft.
21
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 22
7000 SERIES Ordering Information To order an ASCO 7000 SERIES Power Transfer Switch, complete the following catalog number: 7
A
TS
A
+
Neutral Code*
Product A
N
Automatic
NonAutomatic
TS
Conventional 2-Position
TB
Open Transition Bypass
CTS
Closed Transition
CTB
M
Manually Operated
Closed Transition Bypass
DTS
Delayed Transition
DTB
Delayed Transition Bypass
+
---
No Neutral
A
Solid Neutral
B
C
3
+
400
Phase Poles
Amperes
2 3
30 70 100 150 200* 230 * 260 400 600 800 1000 1200 1600 2000 2600 3000 4000
Switched Neutral
Overlapping Neutral
N
+ 5X +
C
Voltage Code
Grp Code
Enclosure
+
A B C D E F H J K L M N P Q R
115 120 208 220 230 240 380 400 415 440 460 480 550 575 600
5 5Xoptional accessories
---
No enclosure
C
Type 1 enclosure
F
Type 3R enclosure
G
Type 4 enclosure
H
Type 4X enclosure (stainless steel)
L
Type 12 enclosure
M
Type 3R secure double door
N
Type 4 secure double door
P
Type 4X secure double door
Q
Type 12 secure double door
R
Type 3RX secure double door (Stainless Steel)
*Notes: Conventional switch neutral is provided on delayed transition transfer products when specified. 200 and 230 amp switch limited to 480 volts maximum, on 7ATS, 7CTS and 7DTS only.
The Example Catalog Number above is 7ATSA3400N5XC (X is used to specify optional accessories).
Transfer Switch Configurations
Transfer/Bypass Configurations
7A TS, 7N TS, 7A DTS, 7A CTS, 7N DTS, 7N CTS
7A TB, 7N TB, 7A DTB, 7A CTB, 7N DTB, 7N CTB
Sizes of UL-Listed Solderless Screw-Type Terminals for External Power Connections
Sizes of UL-Listed Solderless Screw-Type Terminal for Power Connections
Switch Rating amps
Max # of Conductors per Terminal
Range of AL- CU Conductor Sizes
Switch Rating amps
Max # of Conductors per Terminal
Range of AL-CU Conductor Sizes
30 -2303
One
#14 to 4/0 AWG
One
# 4 AWG to 600 MCM
150*, 260, 400
One
#4 AWG to 600 MCM
150, 200, 230 260,400
Two
# 1/0 AWG to 250 MCM
Two
#1/0 AWG to 250 MCM
6004
Two
# 2 AWG to 600 MCM
*150 for CTS and DTS Only
600
Two
#1/0 AWG to 600 MCM
800,1000,1200
Four
# 1/0 AWG to 600 MCM
800-12001
Four
#1/0 AWG to 600 MCM
1600-20004
Six
# 1/0 AWG to 600 MCM
#1/0 AWG to 600 MCM
2600, 30004
Ten
# 2 AWG to 600 MCM
Twelve
#1/0 AWG to 600 MCM
4000
Twelve
# 2 AWG to 600 MCM
Twelve
#2/0 AWG to 600 MCM
1600-2000
2
2600, 3000 4000
2
2
Six
Notes: 1. Unit is designed for top cable entry of emergency and load and bottom entry of normal. Optionally, the switch may be supplied with reverse source and/or bottom entry load, when specified. 2. All main terminals are rear connected.
22
4
4
3. 200 and 230 amp rating for copper conductors only for transfer switch configurations only. 4. All main terminals are rear connected. A front connected version is available in 600 and 1200 amp ratings only with top cable entry only. See pages 25-27 for dimensional data and additional information. 5.Type 304 stainless steel standard. Specify 316 ST. Steel for installations subject to salt water and corrosive environments
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 23
7000 SERIES Designed to Fit Anywhere* 2-Position Transfer Switching 7A TS, 7N TS (Non-Bypass) Switch Rating Amps
Poles
Width Height Depth inches (mm) inches (mm) inches (mm)
Enclosed UL Type 1 2 30, 70, 100, 125, 150, 200, 230 260, 400 600 800, 1000 1200 1600, 2000 1
2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C
18 (457) 24 (610) 24 (610) 34 (864) 38 (965) 38 (965)
48 (1219) 56 (1422) 63 (1600) 72 (1829) 87 (2210) 91 (2311)
13 (330) 14 (356) 17 (432) 20 (508) 23 (584) 48 (1219)
1600, 20003 (front connected)
2, 3 or 3 with neutral A/B/C
38 (965)
87 (2210)
23 (584)
2600, 3000 1
2, 3 or 3 with neutral A/B/C
38 (965)
91 (2311)
60 (1524)
2, 3 or 3 with neutral A/C
60 (1524)
91 (2311)
72 (1829)
2, 3 or 3 with neutral B/C 2, 3 or 3 with neutral B/C 2, 3 or 3 with neutral B/C 2, 3 or 3 with neutral B/C 2, 3 or 3 with neutral B/C
10-1/4 (260) 18-1/2 (470) 19 (483) 27 (686) 33-1/4 (845)
10-1/4 (260) 25 (635) 30 (762) 31 (787) 28 (711)
5-1/2 (140) 8 (203) 9-7/8 (251) 12-7/8 (327) 26-1/4 (667)
2600, 3000
2, 3 or 3 with neutral B/C
33-1/4 (845)
28 (711)
30-3/4 (781)
4000
2, 3 or 3 with neutral C
70 (1778)
53 (1272)
4000 1
Open Configuration 30, 70, 100, 125,150, 200, 230 260, 400 600 800, 1000, 1200 1600, 2000
60 (1524)
Notes: 1. Enclosures are free-standing with removable top, sides, and back. 2. Consult ASCO for dimensions on enclosures other than UL type 1. 3. Order accessory 40MY for 1600A and 40NY for 2000A F/C design.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
** For S Frame dimensions contact ASCO.
Shipping Weights 2-Position Transfer Switching 7A TS, 7N TS Switch Rating Amps 30, 70, 100, 125 30, 70, 100, 125 30, 70, 100, 125 150, 200, 230 150, 200, 230 150, 200, 230 260, 400 260, 400 260, 400 600 600 600 800, 1000 800, 1000 800, 1000 1200 1200 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 2600, 3000 4000 4000 4000
Poles 2 3 3 with B/C 2 3 3 with B/C 2 3 3 with B/C 2 3 3 with B/C 2 3 3 with B/C 2 3 3 with B/C 2 3 3 with B/C 2 3 3 with B/C 2 3 3 with B/C
Enclosed* lb (kg) 67 (31) 70 (32) 73 (33) 69 (32) 72 (33) 75 (34) 216 (98) 223 (101) 230 (105) 316 (143) 324 (147) 332 (151) 400 (182) 420 (192) 446 (203) 685 (312) 705 (321) 731 (333) 1110 (503) 1160 (525) 1210 (548) 1365 (620) 1430 (649) 1495 (679) 1969 (893) 2149 (975) 2328 (1056)
Open* lb (kg) 15 (7) 18 (8) 21 (10) 17 (8) 20 (9) 23 (11) 82 (37) 89 (40) 102 (46) 88 (40) 96 (44) 104 (47) 150 (68) 170 (78) 196 (90) 150 (68) 170 (78) 196 (90) 370 (167) 420 (190) 470 (213) 405 (184) 470 (213) 535 (243) 1258 (571) 1451 (658) 1623 (736)
*All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
** For S Frame dimensions contact ASCO.
23
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 24
7000 SERIES Designed to Fit Anywhere*
Closed Transition and Delayed Transition Transfer Switching 7A DTS, 7A CTS, 7N DTS, 7N CTS Switch Rating Amps
Poles
Width inches (mm)
Height Depth inches (mm) inches (mm)
2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/B 2, 3 or 3 with neutral A/C
24 (610) 24(610) 34 (864) 38 (965) 38 (965) 38 (965) 38 (965) 60 (1524)
56 (1422) 63 (1600) 72 (1829) 87 (2210) 91 (2311) 87 (2210) 91 (2311) 91 (2311)
14 (356) 17(432) 20 (508) 23 (584) 48 (1219) 23 (584) 60 (1524) 72 (1829)
150, 260, 400
2, 3 or 3 with neutral B
18-1/2 (470)
25 (635)
8 (203)
600 800, 1000, 1200 1600, 2000 2600, 3000 4000
2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral B 2, 3 or 3 with neutral C
19 (483) 27 (686) 33-1/4 (845) 33-1/4 (845) 60 (1524)
30 (762) 31 (787) 28 (711) 28 (711) 70 (1778)
9-7/8 (251) 12-7/8 (327) 26-1/4 (667) 30-3/4 (781) 53 (1272)
Enclosed UL Type 1 2 150, 260, 400 600 800, 1000 1200 1600, 2000 1 1600, 20003 (front connected) 3000 1 4000 1
Open Configuration
Notes: 1. Enclosures are freestanding with removable top, sides, and back. 2. Consult ASCO for dimensions on enclosures other than UL type 1. 3. Order accessory 40MY for 1600A and 40NY for 2000A front connected design.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
** For S Frame dimensions contact ASCO.
Shipping Weights Closed Transition and Delayed Transition Transfer Switching 7A DTS, 7A CTS, 7N DTS, 7N CTS
24
Switch Rating Amps
Poles
Enclosed* lb (kg)
Open* lb (kg)
150, 260, 400 150, 260, 400 150, 260, 400 600 600 600 800, 1000 800, 1000 800, 1000 1200 1200 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 2600, 3000 4000 4000 4000
2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B 2 3 3 with B/C
235 (107) 242 (110) 250 (113) 335 (152) 343 (156) 352 (159) 420 (192) 450 (205) 480 (219) 710 (324) 740 (337) 770 (351) 1300 (590) 1350 (612) 1400 (635) 1555 (706) 1620 (735) 1685 (765) 1969 (893) 2149 (975) 2328 (1056)
101 (46) 108 (49) 115 (52) 107 (48) 115 (52) 124(56) 175 (80) 205 (94) 235 (108) 175 (80) 205 (94) 235 (108) 505 (229) 555 (252) 605 (274) 540 (245) 660 (300) 725 (329) 1258 (571) 1451 (658) 1623 (736)
Notes: 1. Open weights include transfer switch and control panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
** For S Frame dimensions contact ASCO.
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 25
7000 SERIES Designed to Fit Anywhere*
Automatic Transfer Bypass-Isolation Switching with Transfer Switch Engaged 7A TB, 7N TB Switch Rating amps
Power Connection Configuration
Width Height Depth inches (mm) inches (mm) inches (mm)
Poles
Enclosed UL Type 1 150, 200, 230, 260, 4001, 600 800 1, 3 1000, 1200 800, 1000, 12001, 2 1600, 20001,2 2600, 30001, 2 40001,2
Front Connected Front Connected Front Connected Side/Rear Connected Side/Rear Connected Side/Rear Connected Rear Connected
2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 3 or 3 with neutral A/B/C 3 or 3 with neutral A/C
34 (864) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 60(1524)
85 (2159) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311)
28 (711) 32 (813) 34 (864) 48 (1219) 60 (1524) 72 (1829) 96 (2438)
61-1/2 (1553)4 72 (1829) 72 (1829) 91 (2311)
28(711)4 38 (965) 38 (965) 96 (2438)
Open Configuration 150, 200, 230, 260, 4001 600, 800, 1000, 12001, 2 1600, 2000, 2600, 30001, 2 40001,2
Front Connected Rear Connected Rear Connected Rear Connected
2, 3 or 3 with neutral B/C 2, 3 or 3 with neutral B/C 2, 3 or 3 with neutral B/C 3 or 3 with neutral A/C
19-3/4 (500)4 38 (965) 38 (965) 60(1524)
Notes: 1. Handles extend 6-1/4 inches (159mm). 2. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch drawout). Side or rear access required. 3. Specify optional accessory 40J Y for 800 Amp front, 40KY for 1000 Amp, and 40LY for 1200 Amp - connected arrangement. All service and load cables limited to top entry only. 4. Contact ASCO for details.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
** For S Frame dimensions contact ASCO.
Shipping Weights Automatic Transfer Bypass-Isolation Switching with Transfer Switch Engaged 7A TB, 7N TB Switch Rating amps
Poles
Enclosed* lb (kg)
Open* lb (kg)
150, 200, 230, 260, 400, 600 150, 200, 230, 260, 400, 600 150, 200, 230, 260, 400, 600 800, 1000, 1200 800, 1000, 1200 800, 1000, 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 4000 4000
2 3 3 with B/C 2 3 3 with B/C 2 3 3 with B/C 3 3 with B/C 3 3 with B/C
990 (450) 1050 (477) 1110 (505) 1510 (685) 1580 (717) 1650 (748) 2180 (989) 2360 (1070) 2540 (1152) 2730 (1240) 3360 (1525) 6300 (2858) 6900 (3130)
Contact ASCO Contact ASCO Contact ASCO 920 (417) 990 (449) 1060 (481) 1300 (589) 1550 (702) 1800 (815) 1690 (768) 1980 (899) — —
Notes: 1.Open weights include transfer switch, bypass-isolation switch and controller. 1600-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions. *All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
** For S Frame dimensions contact ASCO.
25
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 26
7000 SERIES Designed to Fit Anywhere*
Automatic Transfer Bypass-Isolation in Closed Transition and Delayed Transition Switching. 7A DTB6, 7A CTB, 7N DTB6, 7N CTB Switch Rating amps
Power Connection Configuration
Depth Width Height Depth inches (mm) inches (mm) inches (mm) inches (mm)
Poles
Enclosed UL Type 1 150, 200, 230, 260, 4001, 600 800 1, 3 1000, 1200 800, 1000, 12001, 2 1600, 20001,2 2600, 30001, 2 40001,2
Front Connected Front Connected Front Connected Side/Rear Connected Side/Rear Connected Side/Rear Connected Rear Connected
2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 2, 3 or 3 with neutral A/B/C 3 or 3 with neutral A/B/C 3 or 3 with neutral A/C
34 (864) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 60(1524)
85 (2159) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311) 91 (2311)
28 (711) 32 (813) 34 (864) 48 (1219) 60 (1524) 72 (1829) 96 (2438)
Open Configuration 150, 200, 230, 260, 4001 600, 800, 1000, 12001, 2 1600, 2000, 2600, 30001, 2 40001,2
Front Connected Rear Connected
2, 3 or 3 with neutral B/C 2, 3 or 3 with neutral B/C
19-3/4 (500)4 38 (965)
61-1/2 (1553)4 72 (1829)
22-1/4 (565)4 38 (965)
Rear Connected Rear Connected
2, 3 or 3 with neutral B/C 3 or 3 with neutral A/C
38 (965) 60(1524)
72 (1829) 91 (2311)
38 (965) 96 (2438)
Notes: 1. Handles extend 6-1/4 inches (159mm). 2. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch drawout). Side or rear access required. 3. Specify optional accessory 40J Y for 800 Amp front, 40KY for 1000 Amp, and 40LY for 1200 Amp - connected arrangement. All service and load cables limited to top entry only. 4. Contact ASCO for details.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
** For S Frame dimensions contact ASCO.
Shipping Weights Automatic Transfer Bypass-Isolation in Closed Transition and Delayed Transition Switching. 7A DTB, 7A CTB, 7N DTB, 7N CTB Switch Rating amps
Poles
Enclosed* lb (kg)
Open* lb (kg)
150, 200, 230, 260, 400, 600 150, 200, 230, 260, 400, 600 150, 200, 230, 260, 400, 600 800, 1000, 1200 800, 1000, 1200 800, 1000, 1200 1600, 2000 1600, 2000 1600, 2000 2600, 3000 2600, 3000 4000 4000
2 3 3 with A/B 2 3 3 with A/B 2 3 3 with A/B 3 3 with A/B 3 3 with C
990 (450) 1050 (477) 1110 (505) 1560 (708) 1630 (739) 1700(771) 2315 (1050) 2495 (1132) 2675 (1213) 2730 (1240) 3360 (1525) 6300 (2858) 6900 (3130)
Contact ASCO Contact ASCO Contact ASCO 970 (440) 1040 (472) 1110(503) 1435 (651) 1685 (764) 1935 (878) 1690 (768) 1980 (899) — —
Notes: 1. Open weights include transfer switch, bypass-isolation switch and controller. 1600-4000 amp enclosures require ventilation openings, refer to drawings for details. Export shipments may require a wooden box, contact ASCO for weights and dimensions.
*All dimensions and weights shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
26
** For S Frame dimensions contact ASCO.
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 27
7000 SERIES Designed to Fit Anywhere* Optional Front Connected Design Saves Valuable Space Cable Compartment
800 Amp Optional Front Connected Design
32.00 Ground Bus Load Lugs
17.00
Normal Lugs Field Wiring Terminal Block (TB) Bypass Switch Manual Operation Handle
Emergency Lugs
Bypass Handle
38.76 Isolation Handle
Group 5 Controller User Interface
91.00
Controls and Indication
*All dimensions and weights 59.05 REF
Isolation Handle
Transfer Switch Compartment
35.24
shown are approximate and should not be used for construction purposes. Certified dimensions can be furnished upon request.
12.42 REF
39.00 CG
Front Views (Covers Installed)
Right Side Views (Covers Removed)
1000-1200 Amp Optional Front Connected Design 38.00
34.00 Cable Access Hinge Cover
Ground Bus Field Wiring Terminal Block (TB)
Emergency Lugs
Load Lugs Normal Lugs
Bypass Switch Manual Operation Handle
Group 5 Controller User Interface
91.00
6.22 REF Isolation Handle
Controls and Indication 59.05 REF
Isolation Handle Transfer Switch Compartment
27
11240_Brochure_r1_92344_Broch 10/15/12 8:00 AM Page 28
Emerson Network Power. The global leader in enabling Business-Critical ContinuityTM.
EmersonNetworkPower.com Outside Plant
AC Power Connectivity
Embedded Computing Embedded Power
DC Power
Infrastructure Management & Monitoring
Power Switching & Controls Precision Cooling
Racks & Integrated Cabinets Services Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2012 Emerson Electric Co. Publication 3040 R13
© October, 2012
Printed in the U.S.A.
ENGINEERING GUIDE Submittal Data
DGC-2020 Gen-Set Controller Blue Star’s Digital Gen-Set Controller (DGC-2020) is a highly advanced integrated gen-set control system. The DGC-2020 is perfectly focused, combining rugged construction and microprocessor technology to offer a product that will hold up to almost any environment and flexible enough to meet your application’s needs. This device provides gen-set control, transfer switch control, metering, protection and programmable logic in a simple, easy to use, reliable, rugged, and cost effective package. Highlights UL
Recognized, CSA & CE approved
Microprocessor Complete
based
Remote
communication options
Rugged
encapsulated construction
system metering
Standard Features Generator Engine
Extremely
Metering
Gen-set Engine
Metering
16
Control
7
Programmable Inputs
Contact Outputs: (3) 30ADC and (4) Programmable 2ADC
Rated Contacts
Protection:
- Oil Pressure
Wide
- Engine Temperature
UL
- Overspeed
HALT
- Overcrank BESTCOMS
Rugged, Fully Encapsulated Design
Recognized, CSA Certified, CE Approved
IP54
Plus:
Ambient Temperature Range (Highly Accelerated Life Test) Tested
Front Panel Rating with Integrated Gasket
NFPA110
Level One Compliant
- Programming and Setup Software
Real
- Intuitive and Powerful
Emergency
- Remote Control and Monitoring
Current
- Programmable Logic
Generator
- USB Communications
LCD
SAE
J1939 Engine ECU Communications (Where Applicable)
Time Clock with Battery Backup and Event Log Stop Pushbutton
Sensing: 5A CT inputs Frequency: 50/60 Hz
Display Heater to -40˚F
Event
Recording (up to 99 occurrences)
Standard Gen-Set Monitoring Generator Engine
parameters: voltage, current, frequency, real power (Watts), apparent power (VA), and power factor
parameters: oil pressure, coolant temperature, RPM, battery voltage, fuel level, engine runtime, and various J1939 supported
parameters where applicable
Standard Engine Control Functions Cranking Control Cyclic
or Continuous (Fully Programmable)
Successful Start Counter Counts
Starts
and Records Successful Engine
Timers
Alarm
Engine
Cooldown Timer (Specify)
Engine
Maintenance Interval Timer (Specify)
Pre-Alarm
Time Delays for Weak/Low
Battery Voltage Alarm
Time Delay for Overspeed
Time Delay for Sender Failure
Arming
Time Delays After Crank Disconnect:
- Low Oil Pressure - High Coolant Temperature - Pre-Crank Delay Continuous/Cyclic
Cranking Timing Sequence
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
1 of 3
DGC-2020 Gen-Set Controller Front Panel LED Indicators:
Run:
Green – Indicates controller is in the RUN mode
Off:
Red – Indicates controller is in the OFF mode
Auto:
Green – Indicates unit is in the AUTO mode
Not
in Auto: Red – Indicates DGC-2020 is not in AUTO mode
Supplying
Load: Green – Indicates system is supplying current to a connected load
Alarm:
Red – Indicates an alarm situation by continuous illumination A pre-alarm will flash
Standard Engine Protection Functions Pre-Alarms (Warnings)
Battery
Charger Failure
Low
Oil Pressure
Engine
Sender Unit Failure
High
Coolant Temperature
Engine
kWe Overload
Low
Coolant Temperature
Battery Weak
Maintenance
Overcharge (High Voltage)
Battery (Low Voltage)
Alarms (Shutdowns)
Interval Timer
Low
Fuel Level
Fuel
Leak Detect
Low
Oil Pressure
High
Coolant Temperature
Overspeed Overcrank Fuel
Sender Failure
All alarms and pre-alarms can be configured via the BESTCOMSPlus PC software or the front panel.
Optional Features Generator
Protection - 27(2), 32, 40Q, 51(2), 59(2), 81O, 81U
Enhanced
Modbus
Expandable
Generator Protection - 51 and 47
Selection
of Integrating Reset or Instantaneous Reset Characteristics for Overcurrent Protection
Remote
Communication to RDP-110 / NFPA-110 Compliant Remote Annunciator
Additional Remote
(8) Programmable 2ADC Contacts
Dial-out and Dial-in Capability with Internal Modem
Generator Protection Undervoltage Overvoltage
(27)
(59)
Underfrequency Overfrequency
Communications with RS-485
(81U)
(81O)
Overcurrent Phase
Automatic Remote
Emergency Stop
Multilingual High
I/O Capability via J1939 CANBUS
Transfer Switch Control Capability
Fuel Level Pre-Alarm
Critical
Low Fuel Level Alarm
Analog
Meters
(51)
Imbalance (57)
Reverse Loss
Power (32)
of Excitation (400)
Phase
Imbalance (47)
Generator
Overcurrent (51)
All generator protection features are programmable as alarms or pre-alarms.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
2 of 3
DGC-2020 Gen-Set Controller Contact Outputs For those applications where more output contacts are needed, the DGC-2020 can be adapted to include 8 additional 2ADC rated dry contact outputs. These are real contacts and not the solid-state type that require additional external circuitry to properly operate. These contacts are fully programmable via the easy-to-use BESTCOMSPlus PC software and can be assigned to numerous user-defined functions. Internal Modem The DGC-2020 can provide long distance communication by adding an internal modem. There are two modems available, one for US and one for European telephone systems. When a modem is selected, the user can access the DGC-2020 from virtually anywhere via a dedicated telephone line. The user can monitor and control the gen-set as if standing right in front of it. The DGC-2020 can also dial out for preprogrammed circumstances to alert the user of selected situations. RS-485 Communication When the RS-485 option is selected, the user can send and receive information from the DGC-2020 via the RS-485 communications port and Modbus protocol. This feature allows the DGC-2020 to be fully integrated into the building management system. Please see the instruction manual for the Modbus register list. Enhanced Generator Protection In addition to the standard generator protection (27, 59, 81O, 81U) the DGC-2020 can be equipped with a more sophisticated generator protection system. This option provides an overcurrent element (51) with 17 selectable time current characteristic curves and a voltage phase balance protection function. Transfer Switch Control (Mains Failure) The DGC-2020 monitors utility (mains) and determines if it is providing power that is suitable for the loads. If the utility supply goes outside of predetermined levels, the generator is started and the utility is disconnected from the load and the generator is connected. When the utility returns to acceptable levels for a sufficient time, the generator is disconnected and the utility is reconnected to the load. It also includes appropriate adjustable timers or time delays for establishing stable utility operation. Contact Expansion Module (CEM) The CEM add-on module increases the contact input and contact output capability adding 10 contact inputs and 24 form C contact outputs. This module communicates to the DGC-2020 via SAE J1939 CANBUS and allows the user to program the functionality of these inputs and outputs in the BESTCOMS programmable logic program. The user can add labels for the inputs and outputs that appear on BESTCOMS front panel, and in the programmable logic. All the functionality can be assigned to these inputs and outputs as if they were an integrated part of the DGC-2020. The CEM-2020 module has all of the environmental ratings, like the DGC-2020, including a model for UL Class1 Div2 applications (consult price list for part number). The output ratings of the form C contacts are: (12 contacts) 10A @ 30VDC and (12 contacts) 2A @ 30VDC. The 2A rated contacts are gold flash contacts for low current circuits. The CEM-2020 terminals accept a maximum wire size of 12 AWG while the chassis ground requires 12 AWG wire. The CEM-2020 provides the user with the flexibility to use the same model DGC-2020 gen-set controller for simple applications or more complicated applications that require contact functionality or duplication of contacts for remote annunciation. Flexibility is one of the benefits of the DGC-2020, and this add-on module enhances that benefit even further. ModBus TCP/RTU (NetBiter RTU-TCP Gateway) NetBiter® RTU-TCP Gateway connects the fully enhanced DGC-2020 with Ethernet and mobile networks. The gateway acts as a transparent bridge translating DGC-2020 Modbus registers allowing control systems, such as PLCs, SCADA, etc. to communicate over Ethernet. One gateway is required per generator allowing multiple generator sets to be accessed and monitored simultaneously. Note: This option does not interface with BESTCOMSPlus software. Features include: connectivity between serial Modbus devices and the Modbus TCP; RS-232, RS-485 and RS-422 connectivity; Ethernet and mobile network connectivity; 10/100 Mbit/s Ethernet; web-based configuration; DIN rail mounting; and network and serial status indicators. Load Share Module 2020 (LSM-2020) The LSM is an easy to connect and use add-on module for the DGC-2020 to allow the DGC-2020 to control the kW load sharing of multiple generator sets. The LSM-2020 is remotely mounted and communicates to the DGC-2020 via J1939 CANbus communications.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
3 of 3
Remote Annunciator The RDP-110 is a powerful remote display to match Blue Star’s DGC-2020 control panel. It may be powered from the engine starting batteries at 12 or 24VDC or an AC source at 120VAC. The RDP-110 uses RS-485 communications between itself and the DGC to reduce the number of wires required to activate all the alarms to four. The RS-485 communications can be used on remote displays up to 4000 feet away from the DGC. The RDP-110 has 18 LEDs to indicate Alarms, Pre-Alarms and operating conditions of the emergency standby generator system. It has an audible alarm horn rated at 80db (from a distance of two feet). The RDP-110 also comes complete with a conduit box for easy installation. The RDP-110 is available in two mounting configurations: surface and semi-flush mount.
Standard Features Annunciation
of 16 alarms and pre-alarms as detected by the DGC
RS-485
Annunciation
of 2 status indicators
Two
Audible Lamp
alarm horn
Power
mounting configurations
Conduit
Test and Alarm Silence switches
communications box included
Designed
supply inputs for 12, 24VDC or 120VAC (at the RDP-110 location)
UL
for use in harsh environments
recognized & CSA certified
Specifications Power Input DC
Voltage: 8-32VDC (2W max.)
AC
Voltage: 84-144VAC (5VA max.)
Communications Port RS-485
interface with DGC
Isolation
1800VDC
RFI (Radio Frequency Interference)
Type
tested using a 5W handheld transceiver operating at random
frequencies centered around 144MHz and 440MHz with the antenna located within six inches of the device in both vertical and horizontal planes
Environmental and Physical Operating
for one minute between chassis ground and
Storage
temperature: -40°F to +158°F
temperature: -40°F to +185°F
AC voltage input. 700VDC for one minute between any of
Salt
the following groups:
Vibration:
Fog: Qualified to ASTM 117B-1989 The device withstands 2g in each of three mutually
- Chassis ground
perpendicular planes, swept over the range of 10 - 500Hz for a total
- Battery and RS-485 terminals
of six sweeps, 15 minutes each sweep, without structural damage or
- AC voltage inputs
Operating Range
Up
degradation of performance Shock: Weight:
15g 6.5 pounds (3 kilograms)
to 4000 ft. from the DGC
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
1 of 2
Remote Annunciator Front Panel LED Indicators A
Green LED illuminates when power is applied to the RDP-110
B
Green LED Turns ON when the generator is supplying more than two percent of rated current
C
Pre-Alarm Conditions (Yellow LEDs)
D
Pushbuttons Lamp
Test Pushbutton exercises the audible alarm and tests all LEDs
Alarm
Silence Pushbutton silences the audible alarm
E
Alarm Conditions (Red LEDs)
F
Red LED illuminates when the DGC is not in AUTO
G
Audible alarm annunciates when DGC is not in AUTO and when alarms and pre-alarms occur
H
Dashboard line indicates the front panel outside edges when semi-flush mounted
Outline Diagram: Rear and Side Views
Wiring Diagram
Please consult Blue Star electrical drawings for verification.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
2 of 2
Industrial Generators Blue Star utilizes the highest quality generators available. Our industrial generators provide consistent performance, quality design, and great durability required for long life and versatility. Generators used by Blue Star are UL Listed (unless specified otherwise), which guarantees that each one meets the rigorous demands of industrial power generation and will provide safe and effective service for the life of the generator. Blue Star generators range from 20 kWe through 2000 kWe.
Standard Features Enhanced
Ventilation Created by a high-efficiency fan that optimizes internal airflow patterns, maximizes heat transfer, and minimizes hot spot differentials for extended winding life.
Fully
Guarded For operator safety and generator protection. No rotating or electrically energized parts are exposed. All openings are covered by louvers or screens.
Large
Conduit Box Provides ample space for easy connections and allows load line access from all sides, top, or bottom.
Design
Specs and Agency Approvals All Blue Star generators are UL Listed (unless specified otherwise) and meet NEMA MG1-22, BS5000, CSA C22.2, IEC 34-1 and VDE 0530 requirements.
Class
H Insulation System Utilizes an unsaturated polyester varnish for optimal insulation life and superior moisture protection.
Optimized
Windings Provide low reactances and exceptional motor starting capability. The stator windings utilize a 2/3 pitch to minimize harmonic distortion and facilitate parallel operation.
Permanent
Magnet Generator (optional) Ensures 300% short circuit current during fault conditions and provides the regulator with input power isolated from load distortion.
Shielded
Heavy-Duty Bearing Resists contamination and gives a minimum B-10 life of 40,000 hours.
Automatic
Voltage Regulator Provides accurate 1% regulation, under-speed protection, stability adjustment to optimize transient performance, and EMI filtering to commercial standards. Fully encapsulated for rugged durability in virtually any environment.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
SE350 Voltage Regulator VOLTAGE ADJUSTMENT
The screwdriver adjustable potentiometer adjusts the generator output voltage. Adjustment clockwise increases the generator output voltage.
When using a remote voltage adjust rheostat, remove the jumper wire across terminals 6 and 7 and install a 2000 ohm 1/2 watt
(minimum) rheostat. This will give ±10% voltage variation from
the nominal. (For ±5% voltage variation use a 1000 ohm 1/2 watt rheostat).
STABILITY ADJUSTMENT
System stability is the ability of the generator to respond to load
SPECIFICATION
SE350 REGULATOR
sluggish and faster to respond to toad transients. If the stability
Sensing & Power Input
190-240 Vac
Burden
500 VA
Output Power- Continuous
73 Vdc at 3.5 Adc (255w)
Output Power - Forcing(240 Vac Input Power)
105 Vdc at 5 Adc (525w)
Regulation
1 .0%
Remote Voltage Adjustment Range
± 10% with 2000 ohm rheostat ± 5% with l000 ohm rheostat
Frequency Compensation
Adjustable
Roll Off Frequency
54-61 Hz for 60 Hz 45-51 Hz for 50 Hz
Weight
6.5 oz.
Operating Temperature
- 40°C to + 60°C
Storage Temperature
- 65°C to + 85°C
Power Dissipation
8 watts maximum
Size
3.94” L X 2.66” W X 2.20: H
transients. Decreasing the stability makes the generator less
of the regulator is decreased too much, the generator will tend to hunt under steady state conditions.
The screwdriver adjustable potentiometer adjusts the system
stability. Adjustment clockwise increases the stability. Increasing the stability increases the response time of the regulator.
Conversely, decreasing the stability decreases the response time of the regulator.
V/HZ ROLL-OFF FREQUENCY ADJUSTMENT
The roll off point is the frequency where the generator voltage
starts to decrease. This reduces the Kilowatt load to the engine, which allows the engine to recover in speed under heavy load transient conditions.
Use jumper to select 50 HZ or 60 Hz mode. The screwdriver
adjustable potentiometer sets the roll-off frequency from 54-61 Hz in the 60 Hz setting or from 45-51 Hz in the 50 Hz setting. The SE350 has the roll-off point preset to 58 Hz in the 60 Hz
mode and 48 Hz in the 50 Hz mode. To change the roll-off point, adjust engine speed to the desired rated speed. (50 or 60 Hz). Set the voltage to the desired setting at rated speed. Adjust
engine speed to the desired roll-off point. Turn the potentiometer counterclockwise until the voltage starts to drop off. Then adjust
Voltage Buildup
the potentiometer clockwise until the voltage returns to rated voltage. Re-adjust engine speed to rated speed.
EMI Suppression
Internal provisions for automatic voltage build up from generator residual voltage as low as 10 Vac. Internal Electromagnetic Interference Filter (EMI Filter )
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
DVR2000E+ Digital Voltage Regulator Advanced Features CAN
Bus Communication - Allows for the integration of the DVR2000E+ as a node on a CAN Network for the purpose of controlling or monitoring regulator performance
True
RMS Single and Three Phase Voltage Sensing - Connect in the sensing mode required per the application. Sense 100 to 600 Volts ±10% at 50 or 60 Hz
True
Three Phase Power Monitoring - Additional CT inputs monitor current on all three phases if required
Generator
Soft Start - Controlled increase to rated voltage limits overshoot during voltage build-up in AVR regulation modes if required
Frame
Specific PID Selection - Regulator tuned to specific frame size and gain settings
Four
Digit HMI Display - Clearly displayed whether changing settings or monitoring regulator status
Expandable
Platform - Features include shunt power capability and RTD monitoring through expansion modules
Specifications Voltage
Regulation – 0.25% over the entire load range at rated power factor and constant generator frequency
Output
Power – 75VDC, 3.0ADC continuous rating and 150VDC, 7.5ADC forcing capability for one minute
Exciter
Field DC Resistance – 18 to 25Ω range
Voltage
Adjustment – Minimum of ±10% of nominal voltage range. Remote adjustment can be made from up to 150 feet from voltage regulator
Input
Power – 180 to 240VAC, 250 to 300 Hz PMG power supply
Operating Storage Ingress Shock
Temperature – From -40°C to +85°C (-40°F to +185°F) Protection – IP52 (front side mounted in conduit box); IP10 (rear side with protective cover)
– 20g in 3 perpendicular planes
Vibration Weight
CAN
– 1 G at 5 to 26 Hz; 0.050” double amplitude (27 to 52 Hz); 7g at 53 to 500 Hz
– 3 lb. (1361g)
Humidity Salt
Temperature – From -40°C to +70°C (-40°F to +158°F)
Testing – Per MIL-STD-705B, Method 711-D
Fog Testing – Per MIL-STD- 810E Protocol – SAE J1939
Regulator
Sensing – 100 to 600VAC, 50/60 Hz, 1-phase/3-phase
EMI
Compatibility Immunity - Meets EN 61000-6-2: 2005 Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments Emission - Meets EN 61000-6-4: 2007 Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – Emission standard for industrial environments
EMI
Compatibility Tests Immunity - Electrostatic Discharge (ESD): IEC 61000-4-2 | Radiated RF: IEC 61000-4-3 | Electrical Fast Transient (EFT) / Burst: IEC 61000-4-4 Conducted RF: IEC 61000-4-6 | Power Frequency and Magnetic Field: IEC 61000-4-8 Emission - Radiated RF: EN 61000-6-4: 2007, 30 MHz to 1000 MHz This regulator meets MIL-STD-461C, Part 9 for radiated and conducted emissions and radiated susceptibility when mounted in the generator conduit box.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Radiators Blue Star radiators offer a variety of styles and configurations including radiator and charged air assemblies, radiator and aftercooler assemblies with durable core construction. Our radiators are compact and efficient meeting the most stringent enclosure footprint requirements. All radiators are sized for 50˚C (122˚F) ambient. The single-source design ensures a perfect match with your genset package.
Radiator Features Standard Radiator Package Engine-specific Complete All
tank design with variant coolant connection locations and sizes (dependant on engine size)
cooling package with mounting foot and plumbing kit
steel construction of top and bottom tanks
Dual
Core designs -
- Jacket Water / Charged Air Circuit
- Jacket Water / After Cooler Circuit
Individual
radiators designed to meet manufacturer’s specific requirements
Top
tank has built in expansion capacity - no need for an external recover tank
Full
or partial deration system built into the top tank
Standard Corrosion
cooling package includes fan shroud & fan guard preventive options:
- Hot dipped galvanizing on all steel parts or stainless steel
- Epoxy coated cores
Fan-On Radiator Design Engine-specific Rigid
tank design with variant coolant connection locations and sizes (dependant on engine size)
built construction for fan support
High
speed bearings within pillow blocks
Dual
Core designs with variable jacket water / after cooler circuit designs
All
steel construction of top and bottom tanks
Individual
radiators designed to meet manufacturer’s specific requirements
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Gen-Set Enclosures Blue Star gen-set enclosures are specifically designed for optimal protection against the elements. They are designed to protect the entire system from even the most extreme environments, and to reduce sound levels to most specified requirements. Blue Star’s vast flexibility allows the design of standard enclosures to meet most specifications or requirements. All standard enclosure models are constructed of 14 gauge steel and feature a pitched roof for increased structural integrity and superior watershed. All enclosures feature a rugged UL listed powder coat finish as standard for a long lasting and durable finish in standard white, tan or gray. Custom colors are available as specified. Enclosure Design Features UL
2200 Listed models available
Level
2 & 3 enclosures are 150 MPH wind rated through 600 kWe
Lockable
gasketed doors with draw down latches and Stainless
Steel hinges
Pitched
roof for high structural integrity and superior watershed
Above-door Optimal
drip guards
airflow means no cooling system de-rates
Internally
All
Stainless Steel fasteners
Sound
UL
listed extreme-wear powder coat finish
Stainless
mounted exhaust silencers standard up to 600 kWe
attenuation options Steel and Aluminum enclosure options
Level 1
Weather Protective Enclosure (WPE)
Blue Star Level 1 enclosures have the rugged construction and weather protection required for most outdoor environments. These enclosures will effectively protect the gen-set through high wind (100 MPH), rain, and other weather conditions. Weather protective enclosures feature standard hinged lockable doors, a pitched roof to prevent water accumulation, and an extreme-wear UL listed powder coat finish.
Level 2
Weather Proof Enclosure (WPF)
Blue Star Level 2 enclosures feature complete weather proofing for any environment. These enclosures have all of the great features of the Level 1 enclosure, plus: dual side air intake baffles, a rear door, and offers the complete unit UL 2200 listing. The superior design of these enclosures offer an even lower dBA rating, but sound attenuation options are also available to further reduce sound levels.
Level 3
Sound Attenuated Enclosure (SAE)
Blue Star Level 3 enclosures feature the same great weather proofing and standard features as the Level 2 enclosure models, but with a greater emphasis on reducing sound levels. Standard Level 3 features include high performance 1.5” type D sound attenuating foam, a separate front exhaust chamber and dual side air intake baffles to ensure that your system runs exceptionally quiet. These features make this enclosure among the best in the industry for noise reduction and quality.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Sound Attenuation Foam Polydamp® Type D Acoustical Foam, (PAF) is an acoustical grade, open cell, flexible ether based urethane foam designed to give maximum sound absorption for a given thickness. It has excellent resistance to heat, moisture and chemicals. All applications use 1.5” foam as standard.
Foam Characteristics
Sound Absorption: Nominal values of random incidence sound absorption coefficient per ASTM C384-77 for Plain/Tuffylm
Frequency (Hz) Foam Thickness
125
250
500
1000
2000
4000
(1.5 in) 38.1 mm
15/20
27/49
60/96
77/93
90/82
98/67
(2.0 in) 50.8 mm
20/30
40/66
90/98
100/96
96/85
100/75
Test Standard
U.S. Standard
Density, Nominal: (lb/ft3-kg/m3)
ASTM-D-3574-91
1.85
Tensile Strength: (PSI-KPa)
ASTM-D-3574-91
12
Elongation, %
ASTM-D-3574-91
120
Tear Resistance: (lb/in - N/M)
ASTM-D-3574-91
1.3
IFD: (PSI - KN/M2)
ASTM-D-3574-91
30
Compression Set (50%): %
ASTM-D-3574-91
10
Air Permeability (Tested at 1” thickness): (Rayles/M)
ASTM C-522
Continuous
-45˚F (-43˚C) TO 212˚F (100˚C)
Intermittent
250˚F (121˚C)
Flame Resistance UL94
HF-1
FAR.853(B)
PASS
SAEJ-369(B)
PASS
MVSS-302
PASS
DIN
PASS
Humidity Resistance Excellent; no significant decrease in tensile strength or elongation after 5 hrs. of steam autoclave at 250˚F (121˚C) per ASTM D3574-86, Test J. Chemical Resistance Excellent - no significant change in strength after 4 weeks immersion in common solvents, alkalies, acids, and water.
Thermal Conductivity (BTU/hr. ft2, ˚F/in.)
Service Temperature
Estimated Service Life: ASTM C-177
0.25
Min. 10 years at 80F (27˚C) and 95% R.H.
Adhesive Characteristics P4 is a high performance unsupported acrylic pressure sensitive
Adhesive Thickness (Nominal)
0.004”
Color of Adhesive
Water Clear
resistance as well as excellent long term aging and the ability to
Release Liner
76 lb Polycoated bleached kraft paper
withstand environmental extremes.
Service Temperature
-40˚F +200˚F
adhesive exhibiting aggressive tack, high peel and shear, and good heat resistance. In addition, it has good chemical and plasticizer
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Sub-Base Fuel Tanks Blue Star sub-base fuel tanks are listed and manufactured under UL 142 standards for steel above ground tanks, which guarantees that every fuel tank meets the structural and mechanical integrity requirements for mounting a generator set directly on top of the tank. This provides a convenient, efficient, and safe way to store fuel for your gen-set. Sub-Base Fuel Tank Standard Features Double
walled secondary containment UL 142 Listed
Electrical Heavy
stub-up openings are standard to provide generator set wiring provisions through the base tank
gauge steel construction
Durable
two part catalyzed epoxy finish paint
Standard
fittings: fuel supply with check valve (sized per unit), fuel return (sized per unit), 2” NPT for normal vent, 2” - 6” NPT for emergency
vent (sized per unit), 2” NPT for manual fill, 1 1/2” NPT for fuel level gauge, and 3/8” NPT basin drain (plugged). Removable 1/2” supply dip tube standard (size may vary with gen-set model). 1 1/2” NPT for leak detection Interior Direct Low
tank baffle: Separates cold engine supply fuel from hot returning fuel
reading fuel level gauge
fuel level and fuel leak alarms
Design Options High Full
and critical low fuel level shutdowns or alarms
pumping control systems for a true day tank system with a full array of electrical options
Additional Custom Fuel Fill
Tank Fittings
Fuel Tank Designs (sizes and shapes)
Heater
/ Spill Containment
Blue star offers two distinctive types of double wall sub-base fuel tanks, those with an electrical stub up area (standard) and those without. Each type can be customized to any specification to meet your specific requirements.
ELECTRICAL
UL 142 double wall secondary containment sub-base fuel tank with stub-up.
>
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
MC Series Circuit Breakers Blue Star’s MC (Molded Case) Series Circuit Breakers are the highest quality in the industry. They will protect the power system and corresponding equipment from damaging fault currents circuits and overloads. MC Series Features UL
489 listed
Broad
product line to meet virtually any application need
Reduced
downtime: tripped breakers can be easily spotted and immediately reset
Eliminates Offers
single phasing: a common trip bar disconnects all poles simultaneously
flexibility through use of a wide variety of accessory devices and attachments
Repetitive Breakers
Circuit Breaker Type TEB
operation: no fuses to replace
can be easily tested: fuses must be destroyed to confirm calibration accuracy
Ampere Rating 10-100
No. Poles 2 3 2
TED
10-150
TQD
3
AC
120
240
-
-
480
100-225
3
240
2
480
3
600
2
240
3
240
250-400
TJJ
125-400
TJK6
250-600
TKM8
300-800
TKM12
600-1200
2 3 2 3 2 3 2 3
240
277
480
600
H
10
-
-
-
6.3125
-
-
18
10
10
-
10
-
65
22
22
-
-
-
18
-
-
-
35
-
-
600 240
TJD
Dimensions (in.)
480
2
70-250
VAC 120/ 240
100-225
SFH
UL Listed Interrupting Ratings (kA)
Maximum Voltage Rating
-
14
W 2.75 4.125
D 3.375
2.75 6.3125
4.125
3.375
2.75
2.625
4.125
2.625
10.12
4.12
3.81
-
10.125
8.25
3.8125
22
6.5625
600
-
-
42
-
30
22
10.125
8.25
3.8125
600
-
-
42
-
30
22
10.125
8.25
3.8125
600
-
-
42
-
30
22
15.5
8.25
5.5
600
-
-
42
-
30
22
15.5
8.25
5.5
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
BC1206A Series Battery Chargers The BC1206A charger is built to stand up to the punishing power generation environment. It is engineered to exacting performance specifications, including cULus listing for an extra margin of safety. Features
Automatic 12V 6A, 2-Stage charge rate
UL 1236 listed
Watertight, shock proof and corrosion proof
LED status indicators
Reverse polarity protected
Short circuit protected
EMI/RFI Shielded
Specifications Specifications Output Voltage:
Reverse Polarity Protection 12VDC
Input Rating
Available as Standard:
Yes
Short Circuit / Overload Protection
Input Voltage Range:
100 - 130VAC
Maximum Short Circuit Current:
8A (typical)
Input Current Rating:
1.6A maximum
Current Limit:
7A (+/- 10%)
Float - Maintenance Stage
Operating Temperature Range
Float Voltage:
13.3VDC
Minimum Temperature:
-20˚ C
Float Current:
0.1 A
Maximum Temperature:
50˚ C
LED Status:
Green LED On
Agency Certification
Full Load - Bulk Stage
This product is listed under UL 1236 for battery chargers.
Full Load Voltage:
12.0 - 14.1VDC
Warranty
Full Load Current:
0.2 - 6.0A
Warranty Period:
1 Year
LED Status:
Red LED On
Weight
3.5 Pounds
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
BC2405A Series Battery Chargers The BC2405A charger is built to stand up to the punishing power generation environment. It is engineered to exacting performance specifications, including cULus listing for an extra margin of safety. Features
Automatic 24V 5A, 2-Stage charge rate
UL 1236 listed
Watertight, shock proof and corrosion proof
LED status indicators
Reverse polarity protected
Short circuit protected
EMI/RFI Shielded
Specifications Specifications Output Voltage:
Reverse Polarity Protection 24VDC
Input Rating
Available as Standard:
Yes
Short Circuit / Overload Protection
Input Voltage Range:
100 - 130VAC
Maximum Short Circuit Current:
8A (typical)
Input Current Rating:
3.0A maximum
Current Limit:
7A (+/- 10%)
Float - Maintenance Stage
Operating Temperature Range
Float Voltage:
27.1VDC
Minimum Temperature:
-40˚ C
Float Current:
0.1A
Maximum Temperature:
50˚ C
LED Status:
Green LED On
Agency Certification
Full Load - Bulk Stage
This product is listed under UL 1236 for battery chargers.
Full Load Voltage:
24.0 - 27.1VDC
Warranty
Full Load Current:
0.1 - 5.0A
Warranty Period:
1 Year
LED Status:
Red LED On
Weight:
4.5 Pounds
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
NRG Series Battery Chargers Blue Star’s NRG series chargers are the most advanced and feature-rich battery chargers available. NRG battery chargers maximize starting system reliability by utilizing a 10 or 20 amp output, microprocessor controlled power and an array of other features. Highlights Fully
automated battery charging
Easy
Watertight,
to understand interface with
state-of-the-art system status display
Battery-fault
alarm
Increases
shock and corrosion proof
battery life and watering
intervals by 400% or more
cULus
listed
Specifications AC Input Voltage: Input
110-120/208-240 VAC, +/-10%, single phase, field selectable
current: 10A charger: 6.6/3.3 amps maximum | 20A charger: 12.6/6.3 amps maximum
Frequency: Input
60 Hz +/-5% standard; 50/60 Hz +/-5% optional
protection: 1-pole fuse, soft-start, transient suppression
Charger Output Nominal
voltage ratings: 12/24 volt nominal
Optional
voltage rating: 12/24 volt, field selectable
Battery
settings: Six discrete battery voltage programs
- Low or high S.G. Flooded - Low or high S.G. VRLA (sealed) - Nickel cadmium 9, 10, 18, 19 or 20 cells Regulation: Current:
10 or 20 amps nominal
Electronic Charge
current limit: 105% rated output typical – no engine cranking disconnect required
characteristic: Constant voltage, current limited, 4-rate automatic equalization
Temperature Output
+/-0.5% line and load regulation
compensation: Enable or disable anytime, remote sensor optional
protection: Current limit, 1-pole fuse, transient suppression
Housing Dimensions Amps
Width (in.)
Depth (in.)
Height (in.)
Weight (lbs.)
10
7.66
6.5
12.5
23
20
13.95
6.83
13.06
42
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
1 of 2
NRG Series Battery Chargers User Interface, Indication and Alarms Digital
Meter: Automatic meter alternately displays output volts, amps4
Accuracy Alarms
+/-2% volts, +/-5% amps
LED and Form C contact(s) per table
Alarms Systems Functions Alarm
Alarm Code “1” 1
Alarm Code “C”
AC Good
LED
LED
Float Mode
LED
LED
Fast Charge
LED
LED
Temp Comp Active
LED
AC Fail
LED
NFPA 110
LED 2
Low Battery Volts
LED and Form C contact
High Battery Volts
LED and Form C contact
Charger Fail
LED2
LED and Form C contact
Battery Fault
LED2
LED and Form C contact
Controls AC
Input Voltage Select: Field-selectable switch 12/24-volt Output Select: Field-selectable two-position jumper Battery Program Select: Field-selectable six-position jumper Meter Display Select: Field-selectable three-position jumper Fast Charger Enable/Disable: Field-selectable two-position jumper Optional
Environmental Operating
Temperature: -4˚F - 140˚F (-20˚C - 60˚C), meets full specification to 113˚F (45˚C) Over Temperature Protection: maintains safe power device temperature Humidity: 5% to 95%, non-condensing
Construction
Housing/configuration
Material: Non-corroding aluminum. Configuration options: - Fully enclosed: cUL listed enclosure - Open frame: cUL recognized Dimensions: See drawings and dimensions for details Printed Circuit Card: Surface mount technology, conformal coated
Agency Standards
Safety:
Alarms “1” available only on 10A charger
LED and Form C contact
- cUL listed to UL 1236 (required for UL 2200 gensets) - CSA standard 22.2 no. 107.2-M89 - CE: 50/60 Hz units DOC to EN 60335 Agency Marking: - 60 Hz: cULus listed - 50/60 Hz: cULus listed plus CE marked
Form C contact provides summary alarm of these conditions. BBHH chargers include this alarm configuration. Contacts rated 2A @ 30VDC resistive Battery fault alarm indicates these fault conditions: Battery disconnected - Battery polarity reversed - Mismatched charger and battery voltage - Open or high resistance charger to battery connection- Open battery cell or excessive internal resistance Three-position jumper allows user to select from three display settings: alternating volts / amps (normal), constant volts, or constant amps
Temp
Compensation Enable: Standard. Can be disabled or re-enabled in the field Remote Temp Comp Enable: Connect optional remote sensor to temp comp port
Vibration
(10A unit): UL 991 Class B (2G sinusoidal) Immunity: ANSI/IEEE C62.41, Cat. B, EN50082-2 heavy industrial, EN 61000-6-2 Seismic Certification: IBC 2000, 2003, 2006 Maximum Sds of 2.28G Transient
Cooling:
Natural convection Degree: Listed housing: NEMA-1 (IP20). Optional IP21 drip shield. Optional NEMA 3R Damage Prevention: Fully recessed display and controls Electrical connections: Compression terminal blocks Protection
EMC:
- Emissions: FCC Part 15, Class B; EN 50081-2 - Immunity: EN 61000-6-2 NFPA standards: NFPA 70, NFPA 110. (NFPA 110 requires Alarms “C”) Optional Agency Compliance: Units with Alarms “1” configuration available with additional compliance to UL category BBHH and NFPA 20
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
2 of 2
Industrial Gen-Set Batteries Engine Starting Batteries Built to Handle Extreme Conditions Blistering heat and bitter cold are ruthless battery killers. That’s why Blue Star utilizes the Exide pioneered climatized battery. Designed to offer you long-life and high-performance starting power that will get your gen-set running even under extreme conditions. Blue Star’s “all-climate” Exide batteries stand up to the harshest temperatures and are available in sizes and configurations to fit almost any application.
Standard Features Unique
Manifold Vent - Virtually eliminates corrosion by venting gases away from terminals and cables
Heavy
Exclusive
Convenient
Armored
Protective
Polyethylene
Computer
TRP™ Construction – Rib reinforced TRP™ container significantly improves the vibration and impact resistance Plate Cell Bonding - Vibration is the number one killer of commercial batteries. To solve this problem, the cells of every Exide battery are bonded Enveloped Separator Design – Super tough polyethylene material reduces electrical resistance and provides higher cranking performance
Center
Lug Design - Suppresses the vibration inherent in traditional construction for improved performance (where applicable)
Duty Cases - Reinforced polyethylene or hard rubber cases stand up to the demands of standby gen-sets Lifting Slots - a handle is built in the top of the battery for easy carrying and transportation Bottom Design - Waffled bottom design provides protection against nuts, bolts, or stones that might become lodged under the battery Designed Radical Grids - An improved state-of-the-art design which adds power and resists vibration
Threaded
Accessory Ports - Features a sealed “O” ring that does
not work loose during severe service (78DT only)
TTP™
- Through-the-Partition inter-cell connectors create a shorter current path to deliver more power to the terminals
Specifications NEMA Type
Dimensions (Inches)
BCI Group Size
Part Number
CCA at 0˚F
CCA at 32˚F
Length
Width
Height
Weight (lbs.)
78DT
78DT-72
850
1000
10-3/16
6-13/16
8-1/8
54
4D
COM-4D-P
1000
1200
19-9/16
8-5/16
10
95
8D
COM-8D-P
1155
1380
20-7/8
11
10
117
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Battery Heaters Blanket Style Battery Heaters Thermostatically controlled battery thermal wraps provide optimum heating regardless of ambient temperature. At
80˚F (27°C), the battery will achieve maximum
cold cranking amps Battery
is constantly maintained at 80˚F (27°C)
Provides
greater heat rise than plates or pads
Thermostat
will eliminate battery damage caused
by overheating
Part Number
Length
Voltage
Watts
14212
26”
120
50
14211
44”
120
80
14136
56”
120
100
Pad Style Battery Heaters Thermostatically controlled battery pads provide optimum heating regardless of ambient temperature. Preset
thermostat maintains 80°F (27°C) battery warmth for quick starts
Complete
with 8 ft. (2.4m) grounded cord
Dimensions:
9” (22.8cm) Length x 6” (15.1cm) Width x 3/4” (1.8cm) Height
Part Number
Voltage
Watts
11662
120
200
14210
240
200
Note: This product not available in Canada (CSA approved model not available)
CAUTION: Battery heaters are not recommended for Nickel Cadmium batteries.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
TPS Series Block Heaters The TPS engine block heater is designed to preheat diesel and gaseous engines. It is simple to install, lightweight, and heats engines up to 12L displacement. Thermosiphon circulation of the coolant delivers even heat throughout the entire engine block. Features
cULus Listed
CE Compliant
Various temperature settings available, including an
optional adjustable thermostat 90˚ - 130˚F (32˚ - 54˚C)
Can be supplied with UL marked 120 or 240V NEMA plug
Specifications Part Number
Volts
Watts
Amps
Male Plug
Outlet Size
13224
120
500
4.2
Yes
5/8
14209
240
500
2.1
Yes
5/8
10014
120
1000
8.4
Yes
5/8
10015
240
1000
4.2
Yes
5/8
10016
120
1500
12.5
Yes
5/8
10017
240
1500
6.3
Yes
5/8
10018
120
1800
15
Yes
5/8
10019
240
2000
8.3
Yes
5/8
(Inches)
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
CB / CL Series Engine Block Heaters Features Constant
circulation of coolant through the
engine achieves even heat distribution One-piece,
heavy-duty, pressure
die-cast aluminum tank with a bolt-on flange element assembly Fixed
thermostat ON: 100˚F, OFF: 120˚F
(optional temp ranges available) All
parts replaceable - easy to service
CSA
and cULus approved
Classified Models
weather tight
available for Class I, Group D
(Hazardous Locations) applications Various
voltages and 3 phase units
available
Easy
Starts
Saves
warm-up time
Saves
fuel
Prolongs
Reduces 90%
of engine wear is due to low
jacket water temp upon start-up
battery life
Stops
Protects
the Environment
Reduces
“white smoke” upon start-up
Engine
Engine Wear
destructive condensation
Extends
engine life
is ready for full power operation
Reduces
noise pollution
Specifications Part Number
Volts
Watts
Phase
Amps
10591
120
2500
1
20.8
11376
208
2500
1
12.0
10592
240
2500
1
10.4
14208
480
2500
1
5.2
11136
120
3000
1
25.0
11137
208
3000
1
14.4
10593
240
3000
1
12.5
11138
480
3000
1
6.3
11139
208
4000
1
19.2
10594
240
4000
1
16.7
11140
480
4000
1
8.3
11141
208
5000
1
24.0
10595
240
5000
1
20.8
11142
480
5000
1
10.4
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
DuraLite Air Cleaner (Single Stage) DuraLite Air Cleaners are tough, non-metallic, lightweight, self-supporting and completely disposable. They are also easy to install, durable, and reliable. They are designed to function well under high and severe pulsation conditions found in many applications. Vibration-resistant media is potted into molded housings of rugged ABS plastic – so they don’t fall apart as other designs might. They can be mounted vertically or horizontally.
SPECIFICATIONS
No serviceable parts - Air cleaner housing and filter are one unit
Designed to withstand severe intake pulsation
Economical replacement cost
Self-supporting, sturdy
Very reliable: only one critical seal
Lightweight and compact in size
Non-metallic, non-corrosive
Completely disposable - acceptable for normal trash pick-up (DuraLite should not be incinerated)
Easily installed and maintained
Minimal removal clearance needed: only 1.5”
Three airflow styles available to fit virtually any engine intake configuration
Various media available for specific genset applications: high pulsation, high humidity, etc.
Temperature tolerance: 180°F/83°C continuous 220°F/105°C intermittent
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Donaldson Dual Stage Air Cleaner The Donaldson two-stage FRG radial seal air cleaners provide improved reliability, better durability and reduced weight
compared to axial seal style air cleaner designs. Airflow ranges from 82 - 1600 cfm. Ideal for severe duty applications.
Air Cleaner Features Two
stage filter system: the first stage removes up to 85% of incoming dust
Inlet
on side, outlet on end (G flow)
Already
tapped to accept filter service indicator
Vacuator
TM Valve automatically releases the pre-cleaned dust
Durable,
long-lasting finish
Composed
of two materials: injected molded, high strength polymer service cover and a metal body
(the service cover is accessed by latches)
Filter Features The Radial Seal filter inside the air cleaner is quite different from the conventional filters. It’s one piece, molded urethane endcaps encase the filter media and liners – reducing components, adding reliability and lowering cost. The glued-on gasket found on the metal end cap of conventional filters is gone – the inside surface of the filter’s open end is actually the sealing surface. For added engine protection during filter service, consider a model with a safety filter.
Two-Stage Filtration Air cleaner has an integral pre-cleaning stage that separates up to 85% of the incoming dust. The primary filter stops the rest, resulting in engine air that is 99.99% free of dust.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Restriction Indicators ServiSignal™ Mini Indicator Small enough to fit just about anywhere (only 42 mm high), the Donaldson ServiSignal™ shows a highly visible, bright red flag in the full-view window when restriction limit is reached. Resets manually via top button after air cleaner service. The lnformer™ for Graduated, Continuous Readings The Informer, when mounted on the air cleaner provides a continuous reading whether the engine is running or is shut down. Reset button is on top.
Mechanical Indicators Restriction Limits Part Number
Fitting
mbar
Pa
In H2O
X002250
37
3700
15
1/8” - 27 NPT
X002251
50
5000
20
1/8” - 27 NPT
X770052
62
6200
25
1/8” - 27 NPT
X002254
75
7500
30
1/8” - 27 NPT
X002278
50
5000
20
1/8” - 27 NPT
X002277
62
6200
25
1/8” - 27 NPT
X002275
75
7500
30
1/8” - 27 NPT
ServiSignalTM Mini Indicators
InformerTM Indicators
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
CPJ Series Critical Grade Silencers Blue Star’s “CPJ” Series is the accumulation of research and development offering a compact silencer without compromising performance. It incorporates a unique combination of resonator chambers, acoustically packed internal components and diffusers to achieve a stunning level of performance for its size. All CPJ series silencers are critical grade silencers and are packed with insulation to greatly reduce radiated noise and exterior shell temperature.
Standard Construction Features Available
in sizes from 2 inch to 12 inch
Multitude
of inlet/outlet design styles to meet almost any requirement
Packed
with fiberglass insulation to reduce shell temperature and noise levels
Fully
welded double shell carbon steel weldment construction, corrosive resistant
High
density fiberglass acoustic blanket good to 1500°F, wrapped with 304 Stain-
less Steel wire mesh cloth and encased in a carbon steel perforated facing Black
phenolic resin based finish paint
Optional Construction Features and Accessories Stainless
Steel construction
Aluminum
construction
Aluminized Vertical Round
Air
ASME
Steel construction
Acoustic
mounting bands mounting saddles
Horizontal
and vertical shell lugs
Special
code construction
Oversized
mounting legs
Horizontal
leak test
High
flanges
shell lagging
temperature acoustic pack material
Contact
factory for additional features to meet
your requirements
finish per specification
Model #
Part #
Inlet Size
Outlet Size
Flanged Connection
WT (lbs)
CPJS-02
10660
2.0” ID
2.0” OD
No
12
CPJS-25
10661
2.5” ID
2.5” OD
No
18
CPJS-03
10662
3.0” ID
3.0” OD
No
20
CPJS-35
10663
3.5” ID
3.5” OD
No
30
CPJS-04
10664
4.0” ID
4.0” OD
No
31
CPJS-05
10665
5.0” ID
5.0” OD
No
50
CPJS-06
10666
6.0” ID
6.0” OD
Yes
50
CPJS-08
10667
8.0” ID
8.0” OD
Yes
120
CPJS-10
10668
10.0” ID
10.0” OD
Yes
180
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
JI Series Industrial Grade Silencers Blue Star JI Series Standard Application Heavy-duty
industrial grade silencer for heavy-duty stationary and mobile power units Silencing is sufficient for commercial or industrial areas where ambient noise is relatively high Designed
Standard Construction Features Aluminized
Steel standard for silencers up to 26 inch body diameter larger than 26 inch body diameter standard carbon steel Can be mounted vertically or horizontally Standard high temperature (1200°F) satin black finish Fully welded steel construction 1/2” NPT Drains standard Standard NPT inlet and outlet connections on sizes 2 inch to 3.5 inch Standard 125/150# ASA drilled plate flanges on inlet and outlet of silencers 4 inch and larger Two-chamber design Silencers
Optional Construction Features and Accessories Stainless
Steel and Aluminum construction Special inlet and outlet connections Special inlet and outlet locations Special finishes available Vertical mounting legs Horizontal mounting saddles Mounting bands
Horizontal
and vertical shell legs acoustical designs Internal and external shell lagging Inspection openings Air leak tests ASME code construction Complete line of engine exhaust accessories Special
Engine Exhaust Silencer and Optional Accessories Exhaust
Silencer Connector (Stainless Steel) Silencer Mounting Band Rain Cap
Mitered
Tail Pipe Extension Elbows Mating Flanges / Gaskets Wall Thimble
Flexible
Exhaust
Model #
Part #
A
B
D
WT.
Model #
Part #
A
B
C
E
F
WT.
JIE-02
11402
2”
6”
24”
12
JIS-02
11403
2”
6”
22”
5.5”
3”
12
JIE-25
11404
2.5”
8”
24”
18
JIS-25
11405
2.5”
8”
22”
6.5”
3.7”
18
JIE-03
11406
3”
8”
25”
20
JIS-03
11407
3”
8”
22”
7”
4.2”
20
JIE-35
11408
3.5”
10”
31”
30
JIS-35
11409
3.5”
10”
29”
8”
5”
30
JIE-04
11410
4”
10”
32”
31
JIS-04
11411
4”
10”
29.5”
8.5”
5.5”
31
JIE-05
11412
5”
12”
44”
45
JIS-05
11413
5”
12”
41.6”
10”
7.6”
50
JIE-06
11414
6”
12”
44”
50
JIS-06
11415
6”
12”
41.6”
10”
7.6”
50
JIE-08
11416
8”
18”
56”
120
JIS-08
11417
8”
18”
54.5”
13”
10.5”
120
JIE-10
11418
10”
22”
72”
180
JIS-10
11419
10”
22”
69”
15”
15”
180
JIE-12
11420
12”
26”
72”
250
JIS-12
11421
12”
26”
69.5”
17”
17”
250
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
JC Series Critical Grade Silencers Blue Star JC Series Standard Application Heavy-duty
critical grade silencer for heavy-duty stationary and mobile power units JC Series silencers provide a high degree of silencing where the ambient noise level is low and a high quality silencer is required Designed
Standard Construction Features Aluminized
Steel standard for silencers up to 26 inch body diameter larger than 26 inch body diameter standard carbon steel Can be mounted vertically or horizontally Standard high temperature (1200°F) satin black finish 1/2” NPT Drains standard Fully welded steel construction Standard NPT inlet and outlet connections on sizes 2 inch to 3.5 inch Standard 125/150# ASA drilled plate flanges on inlet and outlet of silencers 4 inch and larger Multi-chamber design Silencers
Stainless
Steel and Aluminum construction Special inlet and outlet connections Special inlet and outlet locations Special finishes available Vertical mounting legs Horizontal mounting saddles Mounting bands
and vertical shell legs acoustical designs Internal and external shell lagging Inspection openings Air leak tests ASME code construction Complete line of engine exhaust accessories
AT T E N U AT ION (db)
Optional Construction Features and Accessories
Representative Attenuation Curve for “JC” Series Silencer 40
30
20
10
Horizontal Special
0
63
125
250 500 1000 2000 OCTAVE BAND CENTER FREQUENCY (Hz)
4000
8000
Engine Exhaust Silencer and Optional Accessories Exhaust
Silencer Connector (Stainless Steel) Silencer Mounting Band Rain Cap
Mitered
Tail Pipe Extension Elbows Mating Flanges / Gaskets Wall Thimble
Flexible
Exhaust
Model #
Part #
A
B
D
WT.
Model #
Part #
A
B
C
E
F
WT.
JCE-02
11450
2”
6”
42”
29
JCS-02
11451
2”
6”
39.7”
5.5”
7.2”
29
JCE-25
11452
2.5”
8”
42”
38
JCS-25
11453
2.5”
8”
39.8”
6.5”
7.4”
38
JCE-03
11454
3”
8”
43”
43
JCS-03
11455
3”
8”
40.6”
7”
7.4”
43
JCE-35
11456
3.5”
10”
55”
72
JCS-35
11457
3.5”
10”
53”
8”
9.2”
72
JCE-04
11458
4”
10”
56”
72
JCS-04
11459
4”
10”
53.5”
8.5”
9.2”
72
JCE-05
11460
5”
12”
68”
81
JCS-05
11461
5”
12”
65.6”
10”
12.2”
81
JCE-06
11462
6”
12”
68”
84
JCS-06
11463
6”
12”
65.6”
10”
12.2”
84
JCE-08
11464
8”
18”
92”
249
JCS-08
11465
8”
18”
90.5”
13”
16.5”
249
JCE-10
11466
10”
22”
108”
370
JCS-10
11467
10”
22”
105”
15”
20”
370
JCE-12
11468
12”
26”
120”
506
JCS-12
11469
12”
26”
117”
17”
21.5”
506
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
JH Series Hospital Grade Silencers Blue Star JH Series Standard Application Heavy-duty
hospital grade silencer for heavy-duty stationary and mobile power units JH Series are premium, critical degree silencers for use in low-ambient noise area where the standard critical grade silencer will not adequately suppress noise Designed
Standard Construction Features Aluminized
Steel standard for silencers up to 26 inch body diameter larger than 26 inch body diameter standard carbon steel Fully welded steel construction Can be mounted vertically or horizontally Standard high temperature (1200°F) satin black finish 1/2” NPT Drains standard Standard NPT inlet and outlet connections on sizes 2 inch to 3.5 inch Standard 125/150# ASA drilled plate flanges on inlet and outlet of silencers 4 inch and larger Multi-chamber design Effectively attenuates the full range of sound frequencies Silencers
Stainless
Steel and Aluminum construction Special inlet and outlet connections Special inlet and outlet locations Special finishes available Vertical mounting legs Horizontal mounting saddles Mounting bands
Horizontal
and vertical shell legs acoustical designs Internal and external shell lagging Inspection openings Air leak tests ASME code construction Complete line of engine exhaust accessories Special
AT T E N U AT ION (db)
Optional Construction Features and Accessories
Representative Attenuation Curve for “JH” Series Silencer 50 40 30 20 10 0
63
125
250 500 1000 2000 OCTAVE BAND CENTER FREQUENCY (Hz)
4000
8000
Engine Exhaust Silencer and Optional Accessories Exhaust Flexible
Silencer
Mitered
Tail Pipe Extension Elbows Mating Flanges / Gaskets Wall Thimble
Connector (Stainless Steel) Silencer Mounting Band Rain Cap
Exhaust
Model #
Part #
A
B
D
WT.
Model #
Part #
A
B
C
E
F
WT.
JHE-02
11474
2”
10”
44”
55
JHS-02
11475
2”
10”
41.5”
8.5”
5.5”
55
JHE-25
11476
2.5”
12”
46”
75
JHS-25
11477
2.5”
12”
42.5”
10”
7.75”
75
JHE-03
11478
3”
12”
46”
75
JHS-03
11479
3”
12”
42.5”
10”
7.75”
75
JHE-35
11480
3.5”
14”
60”
110
JHS-35
11481
3.5”
14”
56.5”
11”
9.5”
110
JHE-04
11482
4”
14”
60”
115
JHS-04
11483
4”
14”
56.5”
11”
9.5”
115
JHE-05
11484
5”
18”
68”
180
JHS-05
11485
5”
18”
66.5”
13”
10.5”
180
JHE-06
11486
6”
18”
68”
185
JHS-06
11487
6”
18”
66.5”
13”
10.5”
185
JHE-08
11488
8”
26”
96”
460
JHS-08
11489
8”
26”
93.5”
17”
17.5”
460
JHE-10
11490
10”
30”
110”
680
JHS-10
11491
10”
30”
108”
19”
20”
680
JHE-12
11492
12”
36”
126”
855
JHS-12
11493
12”
36”
122”
22”
23”
855
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Compression Mounts (Dome Style Fail-Safe)
• Chemical and oil resistant black rubber
Part Number
A
B
C
D
E
F
G
H
Axial Spring Rate LBS/IN
Axial Max. Recommended Deflection
Axial Loads in LBS @ Max. Deflection
K61-40
3.25"
4.12"
5.38”
1.66”
1/2”
.53”
.12”
N/A
3000
.125”
375
K61-50
3.25"
4.12"
5.38”
1.66”
1/2”
.53”
.12”
N/A
6400
.125”
800
K61-60
3.25"
4.12"
5.38”
1.66”
1/2”
.53”
.12”
N/A
7400
.125”
925
K61-70
3.25"
4.12"
5.38”
1.66”
1/2”
.53”
.12”
N/A
11500
.125”
1425
K62-C40
3.94"
5.00"
6.25”
1.66”
3/4”
.53”
.12”
N/A
4150
.125”
525
K62-C50
3.94"
5.00”
6.25”
1.66”
3/4”
.53”
.12”
N/A
8300
.125”
1000
K62-C60
3.94"
5.00”
6.25”
1.66”
3/4”
.53”
.12”
N/A
10000
.125”
1250
K62-C70
3.94"
5.00”
6.25”
1.66”
3/4”
.53”
.12”
N/A
15600
.125”
1950
K62-S40
3.94"
5.00”
6.25”
1.66”
5/8”
.53”
.12”
N/A
4150
.125”
525
K62-S50
3.94"
5.00”
6.25”
1.66”
5/8”
.53”
.12”
N/A
8300
.125”
1000
K62-S60
3.94"
5.00”
6.25”
1.66”
5/8”
.53”
.12”
N/A
10000
.125”
1250
K62-S70
3.94"
5.00”
6.25”
1.66”
5/8”
.53”
.12”
N/A
15600
.125”
1950
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Center Bonded Vibration Mounts (Two Piece) The K190 mounts are designed for heavy duty applications where there are dynamic forces in multiple directions. These are two-piece mounts installed through a mounting hole in a support structure. The mounts are fail-safe when used with snubbing washers. The mounts isolate in all directions. • Chemical and oil resistant black rubber
Part Number
Diameter
Diameter
Mounting Hole dia.
Elastomer Diameter
Flange Thickness
Support Structure Thickness
Installed Length
Radius Required
Shore A Durometer
Axial Spring Rate LBS/IN
Recommended Deflection
Axial Load In LBS @ Max. Deflection
Radial Spring Rate LBS/IN
Maximum Axial
Radial Load in LBS @ Max. Deflection
Maximum Radial
Recommended Deflection
K1901-40
.39”
1.25” / 1.25”
.74”
.78”
.50”
.125” / .125”
.98”
.03”
40
900
.05”
45
N/A
N/A
N/A
K1901-50
.39”
1.25” / 1.25”
.74”
.78”
.50”
.125” / .125”
.98”
.03”
50
1600
.05”
80
N/A
N/A
N/A
K1901-60
.39”
1.25” / 1.25”
.74”
.78”
.50”
.125” / .125”
.98”
.03”
60
2200
.05”
110
N/A
N/A
N/A
K1901-70
.39”
1.25” / 1.25”
.74”
.78”
.50”
.125” / .125”
.98”
.03”
70
3700
.05”
185
N/A
N/A
N/A
K1902-40
.39”
1.31” / 1.31”
.75”
.79”
.485”
.375” / .375”
1.25”
.04”
40
1000
.05”
50
2900
.012”
35
K1902-50
.39”
1.31” / 1.31”
.75”
.79”
.485”
.375” / .375”
1.25”
.04”
50
1800
.05”
90
4500
.012”
55
K1902-60
.39”
1.31” / 1.31”
.75”
.79”
.485”
.375” / .375”
1.25”
.04”
60
2500
.05”
130
6600
.012”
80
K1902-70
.39”
1.31” / 1.31”
.75”
.79”
.485”
.375” / .375”
1.25”
.04”
70
4100
.05”
200
10000
.012”
120
K1902-30
.39”
1.31” / 1.31”
.75”
.79”
.485”
.375” / .375”
1.25”
.04”
30
650
.05”
34
2100
.012”
24
K1902-30S
.39”
1.31” / 1.31”
.75”
.79”
.485”
.155” / .155”
1.125”
.04”
30
N/A
N/A
N/A
N/A
N/A
N/A
K1902-40S
.39”
1.31” / 1.31”
.75”
.79”
.485”
.155” / .155”
1.125”
.04”
40
N/A
N/A
N/A
N/A
N/A
N/A
K1902-50S
.39”
1.31” / 1.31”
.75”
.79”
.485”
.155” / .155”
1.125”
.04”
50
N/A
N/A
N/A
N/A
N/A
N/A
K1902-60S
.39”
1.31” / 1.31”
.75”
.79”
.485”
.155” / .155”
1.125”
.04”
60
N/A
N/A
N/A
N/A
N/A
N/A
K1902-70S
.39”
1.31” / 1.31”
.75”
.79”
.485”
.155” / .155”
1.125”
.04”
70
N/A
N/A
N/A
N/A
N/A
N/A
K1903-40
.531”
1.88” / 1.88”
1.25”
1.30”
.78"
.500 / .563”
1.94”
.06”
40
1600
.07”
110
2400
.025”
60
K1903-50
.531”
1.88” / 1.88”
1.25”
1.30”
.78”
.500 / .563”
1.94”
.06”
50
2200
.07”
150
3200
.025”
80
K1903-60
.531”
1.88” / 1.88”
1.25”
1.30”
.78”
.500 / .563”
1.94”
.06”
60
2800
.07”
200
5100
.025”
120
K1903-70
.531”
1.88” / 1.88”
1.25”
1.30”
.78”
.500 / .563”
1.94”
.06”
70
5500
.07”
380
8300
.025”
210
K1904-40
.657”
2.55” / 2.55”
1.50”
1.58”
.90”
.750 / .875”
2.45”
.09”
40
2500
.09”
220
4500
.03”
130
K1904-50
.657”
2.55” / 2.55”
1.50”
1.58”
.90”
.750 / .875”
2.45”
.09”
50
3100
.09”
280
6000
.03”
180
K1904-60
.657”
2.55” / 2.55”
1.50”
1.58”
.90”
.750 / .875”
2.45”
.09”
60
4300
.09”
380
9600
.03”
280
K1904-70
.657”
2.55” / 2.55”
1.50”
1.58”
.90”
.750 / .875”
2.45”
.09”
70
7100
.09”
640
13000
.03”
390
K1905-40
.938”
3.50” /3.50”
2.25”
2.30”
1.00”
1.00 / 1.125”
2.90”
.12”
40
2300
.10”
230
3100
.048”
150
K1905-50
.938”
3.50” /3.50”
2.25”
2.30”
1.00”
1.00 / 1.125”
2.90”
.12”
50
4300
.10”
430
4500
.048”
210
K1905-60
.938”
3.50” /3.50”
2.25”
2.30”
1.00”
1.00 / 1.125”
2.90”
.12”
60
6800
.10”
680
7700
.048”
370
K1905-70
.938”
3.50” /3.50”
2.25”
2.30”
1.00”
1.00 / 1.125”
2.90”
.12”
70
9200
.10”
920
10300
.048”
500
K1906-40
1.06”
4.88” / 4.88”
2.50”
2.55”
1.25”
1.00 / 1.125”
3.40”
.12”
40
4800
.12”
580
370
.057”
210
K1906-50
1.06”
4.88” / 4.88”
2.50”
2.55”
1.25”
1.00 / 1.125”
3.40”
.12”
50
6500
.12”
780
5700
.057”
320
K1906-60
1.06”
4.88” / 4.88”
2.50”
2.55”
1.25”
1.00 / 1.125”
3.40”
.12”
60
10700
.12”
1280
9200
.057”
520
K1906-70
1.06”
4.88” / 4.88”
2.50”
2.55”
1.25”
1.00 / 1.125”
3.40”
.12”
70
13600
.12”
1630
10900
.057”
620
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Vibration Isolation Pads These ultra durable neoprene pads can be used to effectively control noise and vibration, particularly in applications involving power generation equipment. These pads are available in a multitude of sizes to meet the needs of almost any installation application. They have a smooth pattern on both sides and are colored black. Features
60 durometer neoprene
Solid construction (unlike waffle pads) offers higher loading per square inch
Max loading: 1015 PSI
Sizes to fit almost any application
1/4” thickness
Aids in sound dampening by reducing high frequency noise
Easily cut to any desired shape
Can be used in multiple layers to increase deflection
Chemical and oil resistant
-40˚F to 194˚F temperature range
Specifications Pad Size (inches)
Part #
Max Load Per Pad
Mounting Hole Size
2 x 4 x 1/4
10155
8120 lbs.
9/16”
2 x 6 x 1/4
10156
12180 lbs.
11/16”
2 x 8 x 1/4
10157
16240 lbs.
13/16”
3 x 8 x 1/4
10158
24360 lbs.
13/16”
2 1/2 x 10 x 1/4
10159
25375 lbs.
13/16”
3 x 12 x 1/4
10160
36540 lbs.
13/16”
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
TJ Vibration Isolators Steel compression springs isolate loads up to 7840 lbs per mount. Moderate spring deflections generally result in usage under medium through high speed equipment such as engine generator sets. Non-Earthquake Rated
Specifications
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
RJJEQ Vibration Isolators Steel compression springs isolate loads up to 5880 lbs per mount. Moderate spring deflections generally result in usage under medium through high speed equipment such as engine generator sets. Earthquake Restraints Pre-Approval # OPA-0012 has been granted by California’s Office of Statewide Health Planning and Development (OSHPD).
Specifications
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Digital Electric Powered Governor Systems The ProAct control system is a combination of a 16-bit microprocessor control and a limited-angle rotational torque motor (actuator). The system features user-friendly menus to provide extreme flexibility in the development of special control schemes for different types of engines (requires optional display module). 75°
rotary output allows direct coupling to fuel rack, eliminating linkage
Alternate
All-electric
3
actuator requires no drive or hydraulic supply
Programmable
digital electronics permit tailoring control to various applications
Actuators
are extremely fast, electronically positioned in both directions
dynamics for dual fuel applications or cogen/standby speed-activated switches
Start
fuel limit and maximum fuel limit for derating
Manifold
pressure fuel limiting
Two-slope
torque limiting
Specifications Two different ProAct actuators are available. The ProAct I actuator provides 1.4 Nm (1.0 lb-ft) of torque in steady state and 3.55 J (2.62 ft-lbs) of work over 75° of travel. The ProAct II provides 2.7 Nm (2.0 lb-ft) of torque in steady state and 7.11 J (5.24 ft-lbs) of work over the 75° of rotation. The control has two complete sets of dynamic adjustments to aid when operating with such conditions as two different fuels, or in parallel/stand-alone electrical generation. A four-slope gain schedule is available in each set of dynamics. This permits programming for extremely responsive yet extremely stable operation of carbureted engines. Adjustment of the ProAct control is done through a hand held programmer (optional). The programmer allows access to all of the tunable items. The programmer is separate from the control, and will normally be unplugged and removed during governor system operation. This provides security against unauthorized tampering with system adjustments. The control may be tuned or monitored with a PC rather than with the hand held programmer, if desired.
Actuator
Output Shaft 0.500-36 inch serration on output shaft. Opposite side used for feedback device. (Other configurations available upon request.) Operating Temperature Range –40 to +100°C (–40 to +212°F) operating environment. Contact Woodward for extreme temperature installation procedures. Feedback Brushless Hall effect feedback device directly connected to actuator shaft. Installation May be mounted on 2.250 inch (57.15 mm) diameter male pilot concentric to the terminal shaft using four bolts through the actuator or with four 0.312-18 inch bolts into the base (M8-6H metric optional). The actuator may be mounted in any attitude. May be connected directly to butterfly shaft, or may be linked to rack or valve. Weight The ProAct I and ProAct II actuators each weigh 6.9 kg (15.25 lbs). Construction All external surfaces are resistant to water and salt water corrosion. Actuator is waterproof at normal water hose pressure. Do not high-pressure wash. Vibration and Shock Tested Tested to US MIL-STD-810C. MIN Fuel Return Spring The actuator is equipped with a light spring return toward min fuel to prevent drift in case of position signal interruption. Normal operating conditions do not require spring return, as the actuator is powered in both the increase and decrease directions. Direction of Rotation All models are capable of either clockwise or counterclockwise rotation to increase fuel.
Control Speed Dynamics maps are field selectable for either low speed (8–300 rpm) or high speed (300–2100 rpm). Dynamics Two menus for engine dynamics are switch-selectable for alternate fuel, alternate loads, etc. Four different gain settings in each dynamics menu tailor governor response to various conditions depending on load or non-linearity in the fuel control system. Limiters Limiters set minimum, idle, and maximum fuel settings, and minimum and maximum torque schedules. Two-slope torque limit schedule with programselected breakpoint is available. Speed Switches Three speed switches are included with programmable on and off positions according to engine speed. The switches may be used to indicate cranking, idle, rated, or overspeed operation. Switch output is 500 mA when closed. Increase-speed trip points may vary from decrease-speed trip points. Droop Two droop schedules are available, with a programmable switch point between idle droop and rated droop. Speed Reference Programmable minimum and maximum limiters with 4–20 mA remote reference to raise and lower the rated speed. Rate of change of speed reference may be programmed with different rates for raise and lower. Accel and Decel Ramps Acceleration and deceleration times may be programmed to protect engines from damage or to protect processes from sudden changes. Supply Voltage Range 8–32 Vdc for ProAct I 18–32 Vdc for ProAct II
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Stainless Steel Fuel Flexes
PCS Series Flexible Connectors
Provide superior vibration isolation
Thermal expansion protection
Suitable for natural gas, LP vapor, water, and oil applications
Custom lengths and fittings available
Construction Materials
Flexible section:
(Hose & Braid: Type 321 Stainless Steel)
Fittings: Carbon Steel Schedule 40
Male pipe thread on both ends
Specifications Size (NPT)
Part Number
Overall Length
Max Working PSI @ 70˚ F
3/4”
10147
7”
750
1”
10148
8”
605
1 1/2”
11013
9”
525
2”
11133
10.5”
455
2 1/2”
11134
12”
345
3”
11135
12”
345
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Gen-Set Trailers Mobile Power Blue Star gen-set trailers are specifically designed and manufactured for the transportation of mobile generators. All trailers are built to last with heavy duty steel construction. Blue Star offers custom trailers to fit almost any size or specification up to 600 kWe. Standard Features
Design Options:
All
Single
Steel Formed or Structural Channel Construction
Adjustable 2
Tongue Mounted Jack
Hydraulic
5/16” Ball Coupler or 3” Pintle Eye
Safety DOT Six
Spare
Chains
Bolt-On
Plate Mount with Light
Drop
Pole Connector Plug
Breakaway
Surge Brakes
Tire With Mounting Bracket
Cable/Storage
Lighting / DOT Reflective Tape
License
or Double Wall Tank Integral to Trailer
or Torsion Axles
Wheel
Kit (Electric Brakes Only)
LED
Chocks
Lighting Package
Spring
Axles
Powder
Radial
Tires With Rims
Galvanneal
Two Tie
(2) Adjustable Rear Stabilizing Jacks
Single
Down Brackets for Shipping
Jeep
Two
Style Fenders
Durable
Coat Finish Construction
Point Lift
(2) Adjustable Front Stabilizing Jacks
Power
Two Part Catalyzed Epoxy Paint Finish
Box, Lockable
Fenders
Distribution Center
Diamond
Plate Accessories
Blue Star offers trailer designs according to the gross vehicle weight. Blue Star’s flexibility allows for custom designed trailers to fit almost any unique specification or requirement. All trailers meet DOT requirements. Trailer option voids UL 2200 listing.
Available Models Model
Number of Axles
Gross Vehicle Weight Rating
T7000-2
Two
7000 lbs.
T10000-2
Two
10000 lbs.
T12000-2
Two
12000 lbs.
T16000-2
Two
16000 lbs.
T20000-2
Two
20000 lbs.
T30000-3
Three
30000 lbs. Unit with Level 1 enclosure mounted on tandem axle trailer equipped with front storage option.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
UL 2200 Summary What Is UL 2200 Listing & Why Is It Important?
Underwriters Laboratories Inc. (UL) is the leading independent product safety certification organization in the United States. Founded in 1894, UL is an impartial and not-for-profit organization devoted to safety testing of a wide assortment of products. The UL Listing mark is widely recognized as a standard for various electrical and building codes and is often called for as a specification. The UL 2200 Listing is a comprehensive safety standard encompassing the design, construction and performance of stationary generators. This benchmark will be increasingly important to manufacturers, specifying engineers and end users alike, since national and municipal electrical codes will mandate UL 2200 Listing for all standby installations in coming years. When manufacturers bring their products to UL, they are subjecting them to extremely rigorous safety testing. Manufacturers not only enhance the value of their products, they are also strengthening their own brands among consumers who perceive a manufacturers commitment to safety. Because of the many rigorous tests, a manufacturer must follow stringent UL guidelines in creating, building and testing its products in-house to UL’s uncompromising standards. The Listing process involves numerous steps: creation of product, construction descriptions, process reviews, design modifications as needed and product testing. It is a comprehensive procedure focused upon manufacturing standards and product safety. With the addition of UL 2200 Listed product, Blue Star Power Systems has positioned itself as a leader in providing state-of-the-art electrical power generation and energy solutions.
Blue Star offers Diesel and Gaseous models ranging from 25 kWe to 500 kWe that are UL 2200 listed.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
ENGINEERING GUIDE Manuals
Gen-Set Installation Guide
IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS This guide contains important instructions for Blue Star Power Systems, Diesel and Gaseous Engine Driven Electric Generators. It should be followed during installation and maintenance of the generator unit.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
This guide contains important instructions for Blue Star Power Systems, Gas and Diesel Engine Driven Electric Generators. It should be followed during installation and maintenance of the generator Unit and batteries.
WARNING: California Proposition 65 WARNING: Engine exhaust produced by this product contains chemicals known to the state of California to cause cancer, birth defects and other reproductive harm. California Proposition 65 WARNING: Battery Posts, Terminals and related accessories contain chemicals known to the state of California to cause cancer, birth defects and other reproductive harm.
2|Page
Table of Contents FOREWORD ................................................................................................................................................... 4 APPLICABLE CODES AND STANDARDS .......................................................................................................... 4 PRODUCT IDENTIFICATION ........................................................................................................................... 5 SAFETY PRECAUTIONS AND WARNINGS ....................................................................................................... 5 SITE PLANNING AND SELECTION ................................................................................................................... 6 UNIT LIFTING PROVISIONS ............................................................................................................................ 8 MOUNTING PAD CONSTRUCTION ................................................................................................................ 8 MOUNTING AND VIBRATION ISOLATION...................................................................................................... 9 COOLING SYSTEMS AND AIR REQUIREMENTS ............................................................................................ 10 EXHAUST SYSTEMS...................................................................................................................................... 13 FUEL SYSTEMS ............................................................................................................................................. 13 DIESEL FUEL SYSTEMS ............................................................................................................................. 14 GASEOUS FUEL SYSTEMS ........................................................................................................................ 14 BATTERIES AND STARTING SYSTEMS .......................................................................................................... 18 ELECTRICAL REQUIREMENTS ...................................................................................................................... 19 AUTOMATIC TRANSFER SWITCHES ............................................................................................................. 22 The Appendices ....................................................................................................................................... 23
3|Page
FOREWORD This installation guide is intended to provide general instructions for the safe and reliable installation of your Blue Star engine generator set. It is of the utmost importance that each and every person who performs work on this equipment is trained and familiar with the equipment and the contents of this entire installation guide. Each installation is unique in some ways and may require variance or modification from the suggestions presented within this guide. If you are in doubt in any way during the installation process, please take a moment to consult with your authorized Blue Star Power Systems representative. They are trained and experienced in the installation and operation/maintenance of this equipment. Note: The procedures presented in this guide are suggestions. They are not intended to address every circumstance that can and will arise during the installation process. It is the responsibility of the Owner/Operator to arrange for these to be performed by licensed individuals that regularly engage in this type of work. It is the responsibility of the Owner/Operator to ensure that all aspects of the installation are performed in accordance with all Federal/State/county and local codes, and in accordance with the requirements of the authorities having jurisdiction.
APPLICABLE CODES AND STANDARDS Prior to installation, you should obtain and familiarize yourself with the following codes and standards that are referenced within this guide and that may/will govern how the equipment is installed: National Fire Protection Association (NFPA) NFPA 30: Storage, handling and use of flammable liquids. NFPA 37: Stationary combustion engines and gas turbines. NFPA 54: National Fuel Gas Code. NFPA 70: National Electrical Code. NFPA 77E: Arc Flash Safety. NFPA 99: Essential Electrical Systems for Health Care Facilities. NFPA 101: Life Safety Code Number Systems. NFPA 110 2010: Emergency and Standby Systems. National Electrical Manufacturers Association (NEMA) Local codes enforced by the authority having jurisdiction. The information presented within this guide is of the latest and up to date as of the publication date. Blue Star Power Systems, Inc. reserves the right to change/update this publication and the information 4|Page
contained within, without notice, obligation or liability whatsoever. Blue Star Power Systems does not guarantee the satisfactory results of any installation performed using the information contained in this guide. Nor will Blue Star Power Systems assume responsibility for any injury or damage to property as a result of the use of this guide. Persons engaging in product installation do so at their own risk. Once again, if you are in doubt in any way about the procedures for safe and proper installation of this product, stop now and consult your authorized Blue Star Power Systems representative. They are trained and experienced in the installation and operation/maintenance of this equipment.
PRODUCT IDENTIFICATION Locate and record the unit model and serial numbers from the unit nameplate (usually affixed near the controller) immediately after unpacking the equipment. Record the information in the space provided below for future reference when requesting assistance or information regarding this equipment. Unit Model Number:_____________________________________ Unit Serial Number:______________________________________
SAFETY PRECAUTIONS AND WARNINGS Important safety Instructions: Electromechanical equipment, including generator sets, transfer switch equipment and accessories can cause bodily harm and pose life threatening danger when improperly installed, operated, maintained or accessed. The terms DANGER, WARNING and CAUTION are used throughout this guide to alert the installer/operator to special instructions concerning particular procedures that may be hazardous if performed incorrectly. These safety alerts alone cannot eliminate the hazards that they signal. Strict adherence to these special instructions and common sense operation of the equipment are the best accident prevention measures. Observe all warning labels found on the equipment. Ensure that all warning labels remain affixed and intact, and are not obstructed with dirt, grease or other equipment. Blue Star Power Systems Inc. cannot anticipate every possible circumstance that may involve a hazardous situation. The warnings contained in this guide as well as the tags and labels affixed to the equipment, are therefore not to be considered all inclusive. Definitions: DANGER: Indicates the presence of a hazard that WILL cause severe personal injury, death or substantial property damage. WARNING: Indicates the presence of a hazard that CAN cause severe personal injury, death or substantial property damage. 5|Page
CAUTION: Indicates the presence of a hazard that CAN or WILL cause minor personal injury or property damage. HIGH VOLTAGE: Indicates that high voltage may be present in this vicinity or while performing this procedure. Additional Safety Precautions: DANGER: Risk of Electrical Shock. The equipment ground connection on this equipment must be suitably connected to earth ground in accordance with NFPA 70. This equipment shall not be used in “floating neutral” applications. WARNING: Be aware that once the engine starting batteries are connected, this equipment can and will start automatically. Use extreme caution or disconnect the engine starting batteries prior to servicing or making adjustments. CAUTION: Prior to servicing the unit, remove power to all energized circuits, such as a battery charger, coolant heaters, or any device that remains energized during servicing functions. CAUTION: Wear eye protection when operating or servicing this equipment. Flying debris and/or acid/gases from the engine starting batteries could be present during equipment operation and normal battery charging.
SITE PLANNING AND SELECTION Outdoor, enclosed units: Choose a site that allows adequate clearance around the unit for ancillary equipment, fuel storage/supply and routine servicing. The site should be level, not subject to flooding and in compliance with local codes and ordinances. The Unit is to be installed in a location that minimizes the risk of people coming in contact with hot surfaces. Unless specified otherwise, the maximum ambient operating temperature rating of the unit is 50° C/ 122°F. Allow adequate clearance for engine radiator air discharge so as not to restrict cooling air flow. CAUTION: Allow adequate clearance for engine exhaust discharge, keeping in mind the high temperatures and fumes associated with engine exhaust. Do not direct engine exhaust toward other structures or their air intake means. CAUTION: Internal combustion engines can produce high noise levels. Choose a location where sound levels during operation will not be objectionable. CAUTION: In northern climates, provide a suitable means to prevent the accumulation and penetration of blowing snow. 6|Page
WARNING: Open bottomed stationary engine generator sets must be installed over/on non combustible materials and shall be located such that it prevents the accumulation of combustible materials under or inside the generator set. Provide a suitable means to prevent the accumulation of leaves and debris. See the Mounting Pad Construction Section for typical foundation/inertia pad construction details. For any other application, consult a structural engineering firm for proper design to meet the application requirements.
Indoor Units: Engine generator sets must be protected from the elements, and be provided with adequate ventilation and cooling air. Considerations when selecting a room size and location: DO NOT USE THE GENERATOR ROOM FOR STORAGE OF ANY MATERIALS NOT ASSOCIATED WITH THE GENERATOR SET. The room should be sized to adequately accommodate the unit and all of the ancillary equipment such as fuel supply/storage, starting batteries and charging equipment, cooling and exhaust system components and automatic transfer switch equipment. Allow a minimum of three feet of clearance on each side and radiator end, and five feet on the end opposite the radiator for servicing The fuel storage tank for diesel driven units should be located as close as possible to the unit. Allow for clearance between hot components (such as exhaust system) and combustible materials. Consult local building/safety codes for specific applicable requirements. Fire rating codes and requirements must be adhered to. Utilizing a generator set with a unit mounted radiator/cooling system is the most cost effective solution when allowable. However, the room must be situated such that sufficient cooling air can be brought into and exhausted to allow proper cooling of the equipment. Utilizing opposing exterior walls for radiator cooling air supply and radiator discharge is the most effective and cost efficient when possible. Avoid utilizing the same wall for air intake and discharge. Consult your Blue Star Power Systems representative for installation guidance for remote cooled unit applications. Verify the load carrying capacity of the floor. Involve a structural engineering firm if in doubt or for applications where an inertia pad similar in Figure 2 in the Appendices cannot be utilized. See the exhaust system section for pertinent information regarding exhaust system considerations.
7|Page
Utility Power: Make sure there is an adequate source of utility power available to supply the ancillary equipment necessary for support while the gen-set is not in operation (Heaters, Chargers, Etc). WARNING: Open bottomed stationary engine generator sets must be installed over/on non combustible materials and shall be located such that it prevents the accumulation of combustible materials from accumulating under or inside the generator set.
UNIT LIFTING PROVISIONS For safety and convenience, all Blue Star generator sets are provided with a means to lift the unit from the skid base. There are two basic types of lifting devices (See Figure 1 in the Appendices). Smaller units are provided with holes in the skid base by which to attach chain hooks. Larger units are provided with removable lifting brackets for chain attachment. In both instances, the use of chain spreader bars or equipment to suit the particular situation is required to prevent the lifting chains from damaging the unit during lifting. Due to the vast amount of variation in units, lifting equipment and circumstances; the safest means to lift the equipment without damage is at the sole discretion of the lifting equipment operator. The use of the individual engine and generator lifting devices shown on the diagrams are NOT to be used to lift the entire engine generator set. These devices were designed to lift only their respective component and not the complete unit. Lifting a complete unit by means of the engine and generator lifting devices will be done solely at the lifting equipment operator’s discretion and assumed risk.
See Figure 1 in the Appendices for typical lifting devices drawing.
MOUNTING PAD CONSTRUCTION Blue Star Engine Generator Sets should be installed on a concrete pad that is properly sized to support the weight load of the unit and all associated accessories that will be installed with it as well as reduce transmitted vibration to acceptable levels. The weight of your particular unit can be found on the unit specification sheet provided in the operator’s manual provided with the unit. If your unit is equipped with a sub-base fuel tank, you must include the weight of the fuel tank and fuel in your weight calculations. CAUTION: The design criteria presented within this guide are general guidelines only. Check local building codes and ordinances for proper composition, design criteria and clearances. Consult a structural engineering firm for assistance with the design and certification of any supporting structure that is not placed directly on the ground. CAUTION: The unit dimensions listed on the model specification sheets provided in the operators manuals are general dimensions for open type units. The overall dimensions of any particular unit can vary greatly depending on the configuration and accessories ordered. If in doubt about the physical size of any particular unit, contact your local Blue Star Power Systems Inc representative for unit specific drawings prior to proceeding. 8|Page
Common specifications require 2500 PSI concrete, reinforced with eight gauge wire mesh or #6 reinforcing bars on 12 inch centers. The minimum recommended thickness of the pad can be calculated by using the formula below. If the weight per Ft³ of the specific concrete being used is unknown, use 145 pounds per Ft³, (which is a general average) for the calculations below. To reduce vibration transmission to the surrounding areas, a sub-surface layer of sand or gravel should be used. Consult a qualified structural engineer for recommendations. The overall width and length of the mounting pad should be a minimum of 12 inches longer and wider than the skid base of the unit being mounted. It is normally desirable to extend the mounting pad three to six inches above the surrounding concrete or grade for ease of service and cleaning.
Formula for calculating minimum mounting pad thickness:
See Figure 2 in the Appendices for Typical Indoor Genset Installation.
MOUNTING AND VIBRATION ISOLATION Also see vibration isolation requirements in subsequent sections relative to fuel, exhaust and electrical. Noise and vibration are normal by-products of any internal combustion engine driven generator. Vibration reducing mounts are generally used to secure the engine generator set to the concrete mounting pad. The purpose of such mounts is to reduce the amount of noise and vibration that is transmitted to the mounting pad during unit operation. Installations within buildings that have adjacent areas designated for other uses should be reviewed by a structural engineer to ensure that transmitted noise and vibration are reduced to unobjectionable levels. There are typically two types of vibration reducing mounts used: Pad type vibration mounts, which are simple and effective for most applications, are placed between the engine generator set base frame and the concrete mounting pad. They are sized according to the weight of the unit and accessories and should be placed at each mounting point designed into the generator set skid base. To allow the vibration isolation pads to function properly, the nuts on the anchor bolts holding the unit to the mounting pad should be left loose and “double-nutted” as opposed to being tightened down. Refer to the illustration below.
9|Page
.
Pad Type Vibration Mount
Expanding Anchor Bolt
Spring type vibration mounts are designed for a higher level of vibration and noise isolation for critical installations. If your particular generator set was provided with spring type mounts, please refer to the operator’s manual provided with the unit for installation details for the particular mount that was provided.
Spring Type Vibration Mount
COOLING SYSTEMS AND AIR REQUIREMENTS CAUTION: In cold climate areas, the high volume of outside air that will be drawn into the generator room can quickly reduce temperatures within the room to sub-freezing levels. All water piping and other equipment subject to damage by freezing temperatures should be relocated or properly insulated to prevent damage. The cooling system is one of the most critical aspects of any generator set installation. Careful planning must be exercised to insure that adequate ventilation will be available during operation under all possible climatic conditions. Cooling systems can range in complexity from the simplest and most common “unit mounted radiator” to the most elaborate, remote mounted radiator, heat exchanger or heat recovery system. It would be inconceivable to properly cover all possible cooling system applications in a guide of this type. For that reason, only unit mounted radiator cooling systems will be described within. Please consult your local Blue Star Power Systems representative for design, application and installation assistance for all cooling system applications other than unit mounted radiator cooling.
10 | P a g e
Installation considerations for unit mounted radiator cooling systems: Prevailing wind: should be a key factor in deciding which direction to discharge the cooling air that will be exhausted out through the unit mounted radiator. Wind pressure may reduce the amount of air the engine mounted cooling fan can discharge through the unit mounted radiator, causing poor performance or overheating. Consider which direction the wind is usually out of during the hottest days of the year, when the cooling system will require the maximum amount of cooling airflow possible. Noise: The fans required to move air through a unit mounted radiator cooling system will produce a fair amount of noise. Consider positioning the radiator exhaust in a direction less subject to objectionable noise levels. Hot air discharge: At times, the cooling air discharged through a unit mounted radiator cooling system can reach levels that could damage shrubs, bushes and plantings. This is of particular a concern if the unit will be operated for extended periods of time during high ambient temperature periods. Choose the placement direction accordingly. Recirculation of cooling air: The most common cause of unit overheating is cooling air recirculation. When hot air that’s discharged through the radiator is allowed to re-circulate back into the cooling air intake means and through the radiator again, the cooling air can exceed the temperature capabilities of the cooling system causing overheating. If at all possible, the cooling air intake and discharge means should be located on opposing walls or be drawn from and exhausted to opposing directions. Excessive external static pressure within the cooling system: The location of the unit relative to the cooling air intake and exhaust should be such that the need for air ducting is kept to a minimum. For proper operation, all extended air ducting should be sized to maintain the total cooling system external restriction to less than 0.50 inches H₂O. Indoors, the radiator discharge must be ducted with flexible material when installing to the wall opening.
See Figure 1 in the Appendices for Typical Unit Mounted Radiator Installation Sizing cooling air inlet and exhaust openings for unit mounted radiator cooling systems: Adequate cooling air flow is critical to the proper operation of any engine generator set. These recommendations are presented in terms of “effective opening” which is the amount of open area of which air is allowed to flow through a device. Air intake: As a general rule, the “effective opening” of any device used as an air intake means to the engine generator set should be a minimum of 75% larger in “effective opening” than the units’ radiator core . (See example) Air exhaust: As a general rule, the “effective opening” of any device placed in front of the unit mounted radiator as an air discharge device should be a minimum of 50% larger in “effective opening” than the radiator core itself. The device and the radiator core duct adapter should be connected by ductwork of minimal length, and shall be fitted with a flexible section installed at the radiator end. 11 | P a g e
FORMULA:
Next, the louver dimensions (In2) can be converted to ft2 by dividing the ‘Required Louver Size’ by 144. Louvers can then be chosen based on the physical layout of the room and what’s available for louver sizes, so long as the length x width is equal to the ‘Required Louver Size’ in Ft².
See Figure 2 in the Appendices for drawing of typical fixed louver installation. Various types of air intake and exhaust devices: Fixed Blade Louvers: Generally used as air intake devices. The angled stationary blades allow cooling air to flow into a room or enclosure while keeping out the elements and debris. A bird/rodent screen should be installed on the back (inside) of the louver to prevent pest activity within the generator room. Gravity Operated Louvers: Can only be used as air exhaust devices. The hinged louver blades are held open by the discharge airflow during unit operation and fall shut by gravity when not in operation. The use of ductwork to prevent cooling air recirculation is an absolute must when using gravity exhaust louvers. Motor Operated Intake Louvers: Perform the same basic function as fixed intake louvers except that they close to keep out the elements when the unit is not in operation. The desired mode of operation is such that the louver motor is “energized to close” and opens when power is removed. Motor Operated Exhaust Louvers: Differ from motor operated intake louvers as the blades open to a full 90 position to allow the higher velocity, exhausted air to flow with less restriction. The desired mode of operation is such that the louver motor is “energized to close” and opens when power is removed. CAUTION: Care should be taken to verify the mode of operation of the motorized louver being installed (Either energize to close or energize to open) to insure that power is supplied or removed as needed in all modes of operation. IE: During periods of test/exercise, actual power failure, simulated power failure Etc. Improper control sequence/wiring could cause the louvers to remain closed while the unit is in operation causing an overheat condition, shutdown or damage to the unit or accessories. In some extreme cold climatic applications, the use of thermostatically controlled louvers may be used to reduce problems associated with fuel system icing/gelling, engine overcooling Etc. Contact your Blue Star Power Systems Representative for assistance in these applications.
12 | P a g e
EXHAUST SYSTEMS The purpose of the exhaust system is to safely discharge the engine combustion exhaust gasses to a safe area outside of the building or structure. WARNING: Engine combustion exhaust fumes are deadly. Never allow the exhaust outlet termination to be positioned such that exhaust gasses will be directed toward any air entry routes (doors, windows, air intake vents, Etc) of an occupied building. When choosing the location for the discharge termination, do not direct it towards anything that could catch fire or be damaged by high temperatures.
See Figure 3 in the Appendices for a Typical Exhaust Systems Drawing Exhaust system consideration checklist: A. Exhaust outlet terminations are not located upwind or near any building air intakes. B. A flexible piping section of suitable design is used to prevent the transmission of vibration to the exhaust piping which is extended beyond what was provided with the unit from the factory. C. The exhaust piping materials are suitable for the temperatures expected and as published for the particular unit. These temperatures can sometimes exceed 1200°F (649°C). D. Extended piping is adequately sized to prevent excessive engine exhaust system back pressure as published for the particular unit. Consult your Blue Star Power Systems representative for assistance in the design of lengthy or elaborate exhaust system requirements. E. Exhaust piping components are properly insulated to prevent operator exposure to excessive temperatures. F. Ventilated wall thimbles, piping sleeves or other suitable fire-proof materials are used where piping passes through building materials as per all state and local codes. G. Exhaust pipe termination includes a rain cap or other suitable means to prevent the entrance of rain, debris and pests when not in operation. H. All exhaust system components and extended piping beyond what was provided with the unit from the factory is adequately supported to prevent damage to these components during operation. I. The overall exhaust system is oriented to provide a slight downward slope away from the engine to prevent condensation from draining back into the engine.
FUEL SYSTEMS General: The fuel delivery system must be adequately sized and properly installed to provide an ample supply of fuel for starting and running the unit throughout the duration of any emergency event. Prior to connecting the fuel lines, ensure that the fuel connections are free of dirt, grease, water or other foreign matter that could damage the engine. 13 | P a g e
The components required for a complete fuel system will vary depending on the fuel type, unit location and applicable state and local codes. The aforementioned is to be used only as a guide. It is the fuel system installers’ responsibility to ensure that the overall fuel delivery system is of a safe and code compliant design.
DIESEL FUEL SYSTEMS The following components comprise a typical diesel fuel delivery system: A. B. C. D. E. F. G.
Main fuel storage tank, sized for the desired length of run time. Main fuel tank fill pipe with a suitable cap. Main fuel tank vent line. Fuel supply line with a foot/check valve. Fuel return line. Fuel storage “Day Tank” with transfer pump if required. Fuel level switches as required for controls.
Main Fuel Storage Tank: The ideal location for the main fuel storage tank is as close to the unit as possible. Provided that applicable building and fire codes permit, the tank could be located within the same, or in an adjoining room to the unit. If this is not feasible, the tank should be located in a suitable location according to applicable state and local codes. The fuel level in the main tank should be at the same height as the engines fuel transfer pump inlet. If located within the generator room, the tank should be placed on the same general level as the unit, but lower than the engine’s fuel injectors. If the tank must be placed at a level above or below this, a separate priming or float tank may be required. When the main fuel storage tank can be located close to the unit and the vertical “fuel lift” is five feet or less, the engines’ fuel pump may be adequate for supplying fuel to the engine without additional means. If the horizontal run is excessive or the vertical lift exceeds five feet, a fuel “Day Tank” and fuel transfer pump will be required. All fuel storage tanks must be vented to a safe area to allow air and other gasses to escape to atmosphere. The vent termination must be plumbed to a level above the highest point in the system to prevent spillage in the event of an overfill situation. The vent pipe termination should be suitable to prevent dust, dirt, moisture and pests from entering the tank.
GASEOUS FUEL SYSTEMS Gaseous fuel systems should be sized and installed by qualified/authorized personnel only. Fuel piping shall be rigidly supported along its entire length and protected against damage from vibration. An AGA or UL approved flexible connector should be installed at the fuel inlet to the unit to prevent the transmission of vibration to the fuel piping. Gaseous fuel systems are grouped into four basic types. 14 | P a g e
1. 2. 3. 4.
Natural Gas LP - Vapor Withdrawal LP – Liquid Withdrawal LP/NG Dual Fuel
Each fuel system type is covered below. Natural Gas Fuel Systems: Natural gas is a vapor fuel that is supplied primarily by utilities. The BTU content of the natural gas available in most locations is 1000 BTU/Ft³. If the BTU content at the site location is below 1000 BTU/Ft³ the unit may have to be derated accordingly. The local gas utility will provide fuel piping from the gas main to the site location. A primary gas regulator should be provided by the utility. It is the responsibility of the gas utility to ensure that adequate volume and gas pressure are available at all times to insure proper operation. Consult the unit specification sheet located in the Operation & Maintenance Manual provided with your particular unit for the required fuel type, volume, and pressure requirements. LP – Vapor Withdrawal Fuel Systems: Liquefied Petroleum Gas is a liquid fuel that is supplied primarily by fuel distributors. Vapor Withdrawal is the most common type of LP fuel system. The LP fuel within the tank is vaporized within the tank and is drawn under pressure from the top of the tank, above the level of the fuel. The BTU content of LP Gas is 2500 BTU/Ft³. The local gas provider will provide fuel piping from the storage tank to the site location. A primary gas regulator should be provided by the fuel provider. It is the responsibility of the fuel provider to ensure that adequate volume and gas pressure are available at all times to insure proper operation. Consult the unit specification sheet located in the Operation & Maintenance Manual provided with your particular unit for the required fuel type, volume, and pressure requirements.
See Figure 4 in the Appendices for SINGLE FUEL NG/LP VAPOR WITHDRAWL Drawing LP – Liquid Withdrawal Fuel Systems: Liquefied Petroleum Gas is a liquid fuel that is supplied primarily by fuel distributors. Liquid Withdrawal is the most commonly used type of LP fuel system when large volumes of fuel are required. The LP fuel within the tank is drawn under pressure (in the liquid form) from the bottom of the tank, below the level of the fuel and is converted to vapor by a fuel converted mounted on the engine. The BTU content of LP Gas is 2500 BTU/Ft³. The local gas provider will provide fuel piping from the storage tank to the site location. It is the responsibility of the fuel provider to ensure that adequate volume and gas pressure are available at all times to insure proper operation. Consult the unit specification sheet located in the Operation & Maintenance Manual provided with your particular unit for the required fuel type, volume, and pressure requirements. Fire regulations prohibit the installation or entrance of high pressure or liquid LP fuel piping into an occupied building or enclosure.
See Figure 5 in the Appendices for SINGLE FUEL LP LIQUID WITHDRAWL Drawing 15 | P a g e
LP/NG Dual Fuel Systems: Dual fuel systems allow for Natural gas to be used as the primary fuel and LP gas to be used as a backup should the natural gas supply be interrupted. There are two types of dual fuel systems available. Manual changeover systems which require qualified personnel to manually open and close valves and switches to change fuels and automatic changeover systems which monitor the primary fuel pressure and changeover automatically should the pressure be reduced to an unacceptable level. Consult the operation and Maintenance Manual that was provided with your particular unit for further instruction, system type, and volume and pressure requirements.
See Figure 6 in the Appendices for DUAL FUEL NG/LP VAPOR WITHDRAWL AUTO CHANGEOVER Drawing See Figure 7 in the Appendices for DUAL FUEL NG/LP LIQUID WITHDRAWL AUTO CHANGEOVER Drawing Gas Fuel System Design Considerations: Gas piping shall not be used as a grounding means for electrical equipment. The fuel system should incorporate a manual fuel lock-off valve to allow for maintenance of the system. Refer to the typical installation drawings below for recommended fuel system components. All gas piping should be sized to maintain adequate volume and pressure at the engine fuel inlet while operating under full load. Overall length of run and number of elbows and fittings must be taken into consideration.
General Guidelines for Determining Pipe Size for Gaseous Vapor Fuel Systems 1. Obtain the engine fuel consumption in cubic feet per hour at 100% load from the unit model specification sheet for the type of fuel used. 2. Refer to the correction factor chart below to determine the proper correction factor for the type of fuel being used.
Correction Factors For Fuel Specific Gravity Fuel Type Natural Gas Air Propane Butane
Specific Gravity 0.65 1.00 1.50 2.10
Correction Factor 0.962 0.775 0.633 0.535
16 | P a g e
3. Divide the fuel consumption from step 1 by the appropriate correction factor to obtain the corrected flow rate. 4. Determine the “straight pipe equivalent length” for all of the fittings in the piping system from the chart below.
Equivalent Length of Straight Pipe for Valves and Fittings (in Feet) Screwed Fittings
Elbows
Tees
Valves Strainer
5. 6. 7. 8.
Pipe Size (Nominal) 1/4
3/8
1/2
3/4
1
1 1/4
1 1/2
2
2 1/2
3
4
Regular 90˚
2.3
3.1
3.6
4.4
5.2
6.6
7.4
8.5
9.3
11.0
13.0
Long Radius 90˚
1.5
2.0
2.2
2.3
2.7
3.2
3.4
3.6
3.6
4.0
4.6
Regular 45˚
0.3
0.5
0.7
0.9
1.3
1.7
2.1
2.7
3.2
4.0
5.5
Line Flow
0.8
1.2
1.7
2.4
3.2
4.6
5.6
7.7
9.3
12.0
17.0
Branch Flow
2.4
3.5
4.2
5.3
6.6
8.7
9.9
12.0
13.0
17.0
21.0
Globe
21.0
22.0
22.0
24.0
29.0
37.0
42.0
54.0
62.0
79.0
110.0
Gate
0.3
0.5
0.6
0.7
0.8
1.1
1.2
1.5
1.7
1.9
2.5
Angle
12.8
15.0
15.0
15.0
17.0
18.0
18.0
18.0
18.0
18.0
18.0
4.1
4.6
5.0
6.6
7.7
18.0
20.0
27.0
29.0
34.0
42.0
Add the “equivalent length” to the total length of straight pipe within the system. From the table below, choose the column with the nearest “total” pipe length. Move down the column until the capacity figure in cubic feet per hour is encountered. Move horizontally to the left to obtain the suggested pipe size.
Gaseous Fuel Pipe Capacities in Cubic Feet Per Hour Pipe Size (Inches)
1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
Total Equivalent Length of Pipe in Feet
10 20 30 40 43 29 24 20 95 65 52 45 175 120 97 82 360 250 200 170 680 465 375 320 1400 950 770 660 2100 1460 1180 990 3950 2750 2200 1900 6300 4350 3520 3000 11000 7700 6250 5300 23000 15800 12800 10900
50 18 40 73 151 385 580 900 1680 2650 4750 9700
60 16 36 66 138 260 490 810 1520 2400 4300 8800
70 15 33 61 125 240 460 750 1400 2250 3900 8100
80 14 31 57 118 220 460 690 1300 1050 3700 7500
90 13 29 53 110 205 430 650 1220 1950 3450 7200
100 150 200 12 10 8 27 22 19 50 40 35 103 84 72 195 160 135 400 325 280 620 500 430 1150 950 800 1850 1500 1280 3250 2650 2280 6700 5500 4600
See following page for an example 17 | P a g e
Example: Engine Generator set fuel consumption at 100% load running on natural gas equals 1600 Cubic feet per hour. The correction factor for natural gas is 0.962. Therefore 1600 ÷ 0.962 = 1633 (adjusted flow rate). Reading down the 100 foot pipe length column in the capacity table until a capacity equal to or greater than 1633 is obtained, which is 1850. Reading across to the left, we see that 2 ½ inch piping will be required.
BATTERIES AND STARTING SYSTEMS Engine starting batteries need to supply adequate current and voltage to the engine starter motor as indicated on the specific model specification sheet located in the operation and maintenance manual provided with the unit. If the unit has one battery, the DC system voltage is 12VDC Nominal. If the unit has two or four batteries, the DC system voltage is 24VDC Nominal. When supplied, all lead acid batteries are shipped pre filled with electrolyte unless specified otherwise. After installation, coat battery terminal connections with anti-corrosion compound to minimize corrosion. Check battery electrolyte level and ensure all vent caps are in place and secure weekly.
Servicing of batteries are to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When replacing batteries, use the same number and the following type batteries: Vented Lead Acid Engine Starting. Refer to the specific unit specification sheet provided in the operator manual with the particular unit for the battery size. CAUTION – Do not dispose of battery or batteries in a fire. The battery is capable of exploding. CAUTION – Do not open or mutilate the battery or batteries. Released electrolyte has been known to be harmful to the skin and eyes and to be toxic. CAUTION – A battery presents a risk of electrical shock and high short circuit current. The following precautions are to be observed when working on batteries: 1) Remove watches, rings, or other metal objects, 2) Use tools with insulated handles, 3) Wear rubber gloves and boots, 18 | P a g e
4) Do not lay tools or metal parts on top of batteries, 5) Disconnect charging source prior to connecting or disconnecting battery terminals, and
The installation of the engine generator shall provide enough ventilation to ensure that gases generated by vented batteries during charging, or caused by equipment malfunction are removed. CAUTION – The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed: 1) Wear full eye protection and protective clothing, 2) Where electrolyte contacts the skin, wash it off immediately with water, 3) Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention. 4) Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried. CAUTION – Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed: 1) DO NOT SMOKE when near batteries, 2) DO NOT cause flame or spark in battery area, and 3) Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
ELECTRICAL REQUIREMENTS AC Output Connections: Verify that the generator output voltage and phase as listed on the unit nameplate match the system voltage and phase to which it is to be connected. All wiring must be sized and installed in accordance with all applicable electrical code requirements and UL2200 requirements (See “Wire Sizing Guidelines” below). All conductors must be sized, insulated and supported in an approved manner. Wire Sizing Guidelines (Based on UL2200 Requirements): 19 | P a g e
(Reference Section 12.1.3 & Table 62.3 of UL2200 Standard) Load connection wires to circuit breaker / genset should be sized based on UL2200 requirements. The requirements are as follows: Formula: Genset rated output * 115% 0.88 (40C ambient correction) Example: 100A Rated Output * 115% 0.88 (40C ambient correction)
= 130.68181 Amps (Round up to 131 Amps)
Note: If mainline circuit breaker is rated below calculated amps of formula, use calculated amps for wire sizing. If mainline circuit breaker is rated above calculated amps of formula, use circuit breaker rating for wire sizing. Wire Sizing Selection Pre UL2200: Use 75C column of NEC (Table 310-16) (Even when using 90C or greater wire) Wire selection must have amperage rating above calculated amps or circuit breaker, whichever is greater. A suitable earth ground must be connected to the grounding terminal marked with the symbol shown below:
All conduits terminating at the generator connection points must incorporate a flexible section to eliminate the transmission of vibration. Refer to output circuit breaker nameplate data for wire sizing/type and pressure terminal torque values. The tightening torque tables shown below are to be used as a guide.
Tightening torque for pressure wire connectors having screws
20 | P a g e
Tightening torque for pressure wire connectors having internal drive socket head screws
Accessory Wiring: It is recommended that all accessories requiring power be wired to a local panel being supplied by the load side of the transfer switch. This ensures that the accessories will be powered by whichever electrical source is available.
21 | P a g e
All accessory wiring should per Class 1 wiring methods and should be run in conduits separate of the generator output conductors. AC and DC accessory circuits should also be run in separate conduits. Verify that the nameplate voltage of the accessories match the system voltage that will be supplying them. Refer to the electrical wiring diagrams provided in the Operation and Maintenance Manual provided with the particular unit for further wiring details.
AUTOMATIC TRANSFER SWITCHES Automatic transfer switch installation should be provided by a licensed electrician. Refer to the detailed wiring diagrams and installation instructions that are provided with the equipment.
1) Unbalanced load capability when the output has a neutral conductor.
22 | P a g e
The Appendices
Typical Lifting Devices
Typical Indoor Genset Installation
23 | P a g e
Typical Exhaust Systems
Single Fuel NG/LP Vapor Withdrawl
24 | P a g e
Single Fuel LP Liquid Withdrawl
Dual Fuel NG/LP Vapor Withdrawl Auto Changover
25 | P a g e
Dual Fuel NG/LP Liquid Withdrawl Auto Changeover
26 | P a g e
ENGINEERING GUIDE Warranty Information
Engine Generator Set Two (2) Year 2000 Hour Limited Warranty Your Blue Star Power Systems Inc. product has been designed and manufactured with care by people with many years of experience. Blue Star Power Systems Inc. warrants to the original consumer (“Purchaser”) that the product is free from defects in materials and/or workmanship for the period of time outlined below. If the product should prove defective within the time period outlined below, it will be repaired, adjusted or replaced at the option of Blue Star Power Systems Inc., provided that the product, upon inspection by Blue Star Power Systems Inc., has been properly installed, maintained and operated in accordance with Blue Star Power Systems Inc.’s Installation and Operating Manuals. This warranty does not apply to malfunctions caused by physical damage, misuse, improper installation, repair or service by unauthorized persons, or normal wear and tear. Blue Star Power Systems Inc. product warranty period: Engine generator set: Parts and Labor for two (2) years from the date of factory invoice or 2000 hours (whichever occurs first). Accessories (installed on the engine generator set or shipped loose): Parts and Labor for one (1) year from the date of factory invoice or 2000 hours (whichever occurs first). Transfer Switches: If purchased with a generator set (same order number): Parts and Labor for two (2) years from the date of factory invoice or 2000 hours (whichever occurs first). The start of the warranty period can be adjusted to the date of unit start-up (limited to 180 days from invoice date) provided that the following information is provided to Blue Star Power Systems Inc. at the time of start-up. (1) A copy of the Blue Star Power Systems, Inc start-up validation checklist must be properly and completely filled out and returned to Blue Star Power Systems, Inc. within 30 days of start-up. (2) The engine manufacturer’s engine registration form must be completed and returned to the engine manufacturer as stated in the instructions with the registration form. To obtain warranty service: Contact your nearest Blue Star Power Systems Inc. Service Representative. For assistance in locating your nearest authorized service representative, contact Blue Star Power Systems Inc., Attention: Service Department (see contact information below). Warranty service may be performed by authorized Blue Star Power Systems Inc. service providers only. Service work performed by unauthorized persons will void all warranties. Blue Star Power Systems Inc. shall not be liable for any claim in amount greater than the purchase price of the product. In no event shall Blue Star Power Systems Inc. be held liable for any special, indirect, consequential or liquidated damages. THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, OR OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, OR WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. The following items and/or circumstances are excluded from this limited warranty: Engine Fuel
starting batteries: The battery manufacturers’ warranty applies. Consult your local battery supplier for warranty service.
system and/or governing system adjustments performed during start-up.
Normal
maintenance items: Consumable items such as belts, filters and hoses.
Adjustments Loose
and tune–ups performed during start-up or thereafter.
connections (electrical and mechanical) not found during start-up.
Equipment Shipping
modifications made without the written consent of Blue Star Power Systems Inc. will void all warranties.
damage of any type. All equipment is shipped F.O.B. factory and risk of loss transfers to the carrier once loaded for shipment. It
is the responsibility of the receiving party to sign for the receipt of, and note any shipping damage to the equipment. Freight damage claim filing is the responsibility of the receiving party. In the rare event that damage occurs during shipment, Blue Star Power Systems, Inc. will not warrant any damage to the unit resulting from shrink wrap. Any
special access fees, requirements or after hours scheduling to gain access to the equipment for warranty service purposes.
Owner
requested rental generators used while warranty work is being performed.
Damages Any
Improper Diesel All
caused by acts of nature, such as lightning, wind, flood, or earthquake.
damage due to situations beyond the control of the manufacturing and/or workmanship of the product. installation or operation as outlined in the Installation and Operation Manuals.
engine “Wet Stacking” due to lightly loaded diesel engines.
travel labor and mileage on portable equipment must be approved before any work is performed.
Terms of warranty shall be deemed made and executed in Lake Crystal, Blue Earth County, Minnesota. Venue for all legal proceedings shall be in Blue Earth County, Minnesota.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Engine Generator Set Five (5) Year 3000 Hour Comprehensive Warranty Your Blue Star Power Systems Inc. product has been designed and manufactured with care by people with many years of experience. Blue Star Power Systems Inc. warrants to the original consumer (“Purchaser”) that the product is free from defects in materials and/or workmanship for the period of time outlined below. If the product should prove defective within the time period outlined below, it will be repaired, adjusted or replaced at the option of Blue Star Power Systems Inc., provided that the product, upon inspection by Blue Star Power Systems Inc., has been properly installed, maintained and operated in accordance with Blue Star Power Systems Inc.’s Installation and Operating Manuals. This warranty does not apply to malfunctions caused by physical damage, misuse, improper installation, repair or service by unauthorized persons, or normal wear and tear. Blue Star Power Systems Inc. product warranty period: Engine generator set: Parts and Labor for five (5) years from the date of factory invoice or 3000 hours (whichever occurs first). Accessories (installed on the engine generator set or shipped loose): Parts and Labor for one (1) year from the date of factory invoice or 2000 hours (whichever occurs first). Transfer Switches: If purchased with a generator set (same order number): Parts and Labor for two (2) years from the date of factory invoice or 2000 hours (whichever occurs first). The start of the warranty period can be adjusted to the date of unit start-up (limited to 180 days from invoice date) provided that the following information is provided to Blue Star Power Systems Inc. at the time of start-up. (1) A copy of the Blue Star Power Systems, Inc start-up validation checklist must be properly and completely filled out and returned to Blue Star Power Systems, Inc. within 30 days of start-up. (2) The engine manufacturer’s engine registration form must be completed and returned to the engine manufacturer as stated in the instructions with the registration form. To obtain warranty service: Contact your nearest Blue Star Power Systems Inc. Service Representative. For assistance in locating your nearest authorized service representative, contact Blue Star Power Systems Inc., Attention: Service Department (see contact information below). Warranty service may be performed by authorized Blue Star Power Systems Inc. service providers only. Service work performed by unauthorized persons will void all warranties. Blue Star Power Systems Inc. shall not be liable for any claim in amount greater than the purchase price of the product. In no event shall Blue Star Power Systems Inc. be held liable for any special, indirect, consequential or liquidated damages. THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, OR OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, OR WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. The following items and/or circumstances are excluded from this limited warranty: Engine Fuel
starting batteries: The battery manufacturers’ warranty applies. Consult your local battery supplier for warranty service.
system and/or governing system adjustments performed during start-up.
Normal
maintenance items: Consumable items such as belts, filters and hoses.
Adjustments Loose
and tune–ups performed during start-up or thereafter.
connections (electrical and mechanical) not found during start-up.
Equipment Shipping
modifications made without the written consent of Blue Star Power Systems Inc. will void all warranties.
damage of any type. All equipment is shipped F.O.B. factory and risk of loss transfers to the carrier once loaded for shipment. It
is the responsibility of the receiving party to sign for the receipt of, and note any shipping damage to the equipment. Freight damage claim filing is the responsibility of the receiving party. In the rare event that damage occurs during shipment, Blue Star Power Systems, Inc. will not warrant any damage to the unit resulting from shrink wrap. Any
special access fees, requirements or after hours scheduling to gain access to the equipment for warranty service purposes.
Owner
requested rental generators used while warranty work is being performed.
Damages Any
Improper Diesel All
caused by acts of nature, such as lightning, wind, flood, or earthquake.
damage due to situations beyond the control of the manufacturing and/or workmanship of the product. installation or operation as outlined in the Installation and Operation Manuals.
engine “Wet Stacking” due to lightly loaded diesel engines.
travel labor and mileage on portable equipment must be approved before any work is performed.
Terms of warranty shall be deemed made and executed in Lake Crystal, Blue Earth County, Minnesota. Venue for all legal proceedings shall be in Blue Earth County, Minnesota.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Engine Generator Set Five (5) Year 3000 Hour Limited Warranty Your Blue Star Power Systems Inc. product has been designed and manufactured with care by people with many years of experience. Blue Star Power Systems Inc. warrants to the original consumer (“Purchaser”) that the product is free from defects in materials and/or workmanship for the period of time outlined below. If the product should prove defective within the time period outlined below, it will be repaired, adjusted or replaced at the option of Blue Star Power Systems Inc., provided that the product, upon inspection by Blue Star Power Systems Inc., has been properly installed, maintained and operated in accordance with Blue Star Power Systems Inc.’s Installation and Operating Manuals. This warranty does not apply to malfunctions caused by physical damage, misuse, improper installation, repair or service by unauthorized persons, or normal wear and tear. Blue Star Power Systems Inc. product warranty period: Engine generator set: Parts and Labor for two (2) years from the date of factory invoice or 2000 hours (whichever occurs first). Warranty coverage for years three (3) thru five (5) or up to 3000 hours is parts only. Accessories (installed on the engine generator set or shipped loose): Parts and Labor for one (1) year from the date of factory invoice or 2000 hours (whichever occurs first). Transfer Switches: If purchased with a generator set (same order number): Parts and Labor for two (2) years from the date of factory invoice or 2000 hours (whichever occurs first). The start of the warranty period can be adjusted to the date of unit start-up (limited to 180 days from invoice date) provided that the following information is provided to Blue Star Power Systems Inc. at the time of start-up. (1) A copy of the Blue Star Power Systems, Inc start-up validation checklist must be properly and completely filled out and returned to Blue Star Power Systems, Inc. within 30 days of start-up. (2) The engine manufacturer’s engine registration form must be completed and returned to the engine manufacturer as stated in the instructions with the registration form. To obtain warranty service: Contact your nearest Blue Star Power Systems Inc. Service Representative. For assistance in locating your nearest authorized service representative, contact Blue Star Power Systems Inc., Attention: Service Department (see contact information below). Warranty service may be performed by authorized Blue Star Power Systems Inc. service providers only. Service work performed by unauthorized persons will void all warranties. Blue Star Power Systems Inc. shall not be liable for any claim in amount greater than the purchase price of the product. In no event shall Blue Star Power Systems Inc. be held liable for any special, indirect, consequential or liquidated damages. THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, OR OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, OR WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. The following items and/or circumstances are excluded from this limited warranty: Engine Fuel
starting batteries: The battery manufacturers’ warranty applies. Consult your local battery supplier for warranty service.
system and/or governing system adjustments performed during start-up.
Normal
maintenance items: Consumable items such as belts, filters and hoses.
Adjustments Loose
and tune–ups performed during start-up or thereafter.
connections (electrical and mechanical) not found during start-up.
Equipment Shipping
modifications made without the written consent of Blue Star Power Systems Inc. will void all warranties.
damage of any type. All equipment is shipped F.O.B. factory and risk of loss transfers to the carrier once loaded for shipment. It
is the responsibility of the receiving party to sign for the receipt of, and note any shipping damage to the equipment. Freight damage claim filing is the responsibility of the receiving party. In the rare event that damage occurs during shipment, Blue Star Power Systems, Inc. will not warrant any damage to the unit resulting from shrink wrap. Any
special access fees, requirements or after hours scheduling to gain access to the equipment for warranty service purposes.
Owner
requested rental generators used while warranty work is being performed.
Damages Any
Improper Diesel All
caused by acts of nature, such as lightning, wind, flood, or earthquake.
damage due to situations beyond the control of the manufacturing and/or workmanship of the product. installation or operation as outlined in the Installation and Operation Manuals.
engine “Wet Stacking” due to lightly loaded diesel engines.
travel labor and mileage on portable equipment must be approved before any work is performed.
Terms of warranty shall be deemed made and executed in Lake Crystal, Blue Earth County, Minnesota. Venue for all legal proceedings shall be in Blue Earth County, Minnesota.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Engine Generator Set One (1) Year 1500 Hour Prime Power Limited Warranty Your Blue Star Power Systems Inc. product has been designed and manufactured with care by people with many years of experience. Blue Star Power Systems Inc. warrants to the original consumer (“Purchaser”) that the product is free from defects in materials and/or workmanship for the period of time outlined below. If the product should prove defective within the time period outlined below, it will be repaired, adjusted or replaced at the option of Blue Star Power Systems Inc., provided that the product, upon inspection by Blue Star Power Systems Inc., has been properly installed, maintained and operated in accordance with Blue Star Power Systems Inc.’s Installation and Operating Manuals. This warranty does not apply to malfunctions caused by physical damage, misuse, improper installation, repair or service by unauthorized persons, or normal wear and tear. Blue Star Power Systems Inc. product warranty period: Engine generator set: Parts and Labor for one (1) year from the date of factory invoice or 1500 hours (whichever occurs first). Accessories (installed on the engine generator set or shipped loose): Parts and Labor for one (1) year from the date of factory invoice or 1500 hours (whichever occurs first). Transfer Switches: If purchased with a generator set (same order number): Parts and Labor for two (2) years from the date of factory invoice or 2000 hours (whichever occurs first). The start of the warranty period can be adjusted to the date of unit start-up (limited to 180 days from invoice date) provided that the following information is provided to Blue Star Power Systems Inc. at the time of start-up. (1) A copy of the Blue Star Power Systems, Inc start-up validation checklist must be properly and completely filled out and returned to Blue Star Power Systems, Inc. within 30 days of start-up. (2) The engine manufacturer’s engine registration form must be completed and returned to the engine manufacturer as stated in the instructions with the registration form. To obtain warranty service: Contact your nearest Blue Star Power Systems Inc. Service Representative. For assistance in locating your nearest authorized service representative, contact Blue Star Power Systems Inc., Attention: Service Department (see contact information below). Warranty service may be performed by authorized Blue Star Power Systems Inc. service providers only. Service work performed by unauthorized persons will void all warranties. Blue Star Power Systems Inc. shall not be liable for any claim in amount greater than the purchase price of the product. In no event shall Blue Star Power Systems Inc. be held liable for any special, indirect, consequential or liquidated damages. THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, OR OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, OR WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. The following items and/or circumstances are excluded from this limited warranty: Engine Fuel
starting batteries: The battery manufacturers’ warranty applies. Consult your local battery supplier for warranty service.
system and/or governing system adjustments performed during start-up.
Normal
maintenance items: Consumable items such as belts, filters and hoses.
Adjustments Loose
and tune–ups performed during start-up or thereafter.
connections (electrical and mechanical) not found during start-up.
Equipment Shipping
modifications made without the written consent of Blue Star Power Systems Inc. will void all warranties.
damage of any type. All equipment is shipped F.O.B. factory and risk of loss transfers to the carrier once loaded for shipment. It
is the responsibility of the receiving party to sign for the receipt of, and note any shipping damage to the equipment. Freight damage claim filing is the responsibility of the receiving party. In the rare event that damage occurs during shipment, Blue Star Power Systems, Inc. will not warrant any damage to the unit resulting from shrink wrap. Any
special access fees, requirements or after hours scheduling to gain access to the equipment for warranty service purposes.
Owner
requested rental generators used while warranty work is being performed.
Damages Any
damage due to situations beyond the control of the manufacturing and/or workmanship of the product.
Improper Diesel All
caused by acts of nature, such as lightning, wind, flood, or earthquake. installation or operation as outlined in the Installation and Operation Manuals.
engine “Wet Stacking” due to lightly loaded diesel engines.
travel labor and mileage on portable equipment must be approved before any work is performed.
Terms of warranty shall be deemed made and executed in Lake Crystal, Blue Earth County, Minnesota. Venue for all legal proceedings shall be in Blue Earth County, Minnesota.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
Engine Generator Set One (1) Year 4500 Hour Prime Power Limited Warranty Your Blue Star Power Systems Inc. product has been designed and manufactured with care by people with many years of experience. Blue Star Power Systems Inc. warrants to the original consumer (“Purchaser”) that the product is free from defects in materials and/or workmanship for the period of time outlined below. If the product should prove defective within the time period outlined below, it will be repaired, adjusted or replaced at the option of Blue Star Power Systems Inc., provided that the product, upon inspection by Blue Star Power Systems Inc., has been properly installed, maintained and operated in accordance with Blue Star Power Systems Inc.’s Installation and Operating Manuals. This warranty does not apply to malfunctions caused by physical damage, misuse, improper installation, repair or service by unauthorized persons, or normal wear and tear. Blue Star Power Systems Inc. product warranty period: Engine generator set: Parts and Labor for one (1) year from the date of factory invoice or 4500 hours (whichever occurs first). Accessories (installed on the engine generator set or shipped loose): Parts and Labor for one (1) year from the date of factory invoice or 1500 hours (whichever occurs first). Transfer Switches: If purchased with a generator set (same order number): Parts and Labor for two (2) years from the date of factory invoice or 2000 hours (whichever occurs first). The start of the warranty period can be adjusted to the date of unit start-up (limited to 180 days from invoice date) provided that the following information is provided to Blue Star Power Systems Inc. at the time of start-up. (1) A copy of the Blue Star Power Systems, Inc start-up validation checklist must be properly and completely filled out and returned to Blue Star Power Systems, Inc. within 30 days of start-up. (2) The engine manufacturer’s engine registration form must be completed and returned to the engine manufacturer as stated in the instructions with the registration form. To obtain warranty service: Contact your nearest Blue Star Power Systems Inc. Service Representative. For assistance in locating your nearest authorized service representative, contact Blue Star Power Systems Inc., Attention: Service Department (see contact information below). Warranty service may be performed by authorized Blue Star Power Systems Inc. service providers only. Service work performed by unauthorized persons will void all warranties. Blue Star Power Systems Inc. shall not be liable for any claim in amount greater than the purchase price of the product. In no event shall Blue Star Power Systems Inc. be held liable for any special, indirect, consequential or liquidated damages. THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, OR OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, OR WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. The following items and/or circumstances are excluded from this limited warranty: Engine Fuel
starting batteries: The battery manufacturers’ warranty applies. Consult your local battery supplier for warranty service.
system and/or governing system adjustments performed during start-up.
Normal
maintenance items: Consumable items such as belts, filters and hoses.
Adjustments Loose
and tune–ups performed during start-up or thereafter.
connections (electrical and mechanical) not found during start-up.
Equipment Shipping
modifications made without the written consent of Blue Star Power Systems Inc. will void all warranties.
damage of any type. All equipment is shipped F.O.B. factory and risk of loss transfers to the carrier once loaded for shipment. It
is the responsibility of the receiving party to sign for the receipt of, and note any shipping damage to the equipment. Freight damage claim filing is the responsibility of the receiving party. In the rare event that damage occurs during shipment, Blue Star Power Systems, Inc. will not warrant any damage to the unit resulting from shrink wrap. Any
special access fees, requirements or after hours scheduling to gain access to the equipment for warranty service purposes.
Owner
requested rental generators used while warranty work is being performed.
Damages Any
damage due to situations beyond the control of the manufacturing and/or workmanship of the product.
Improper Diesel All
caused by acts of nature, such as lightning, wind, flood, or earthquake. installation or operation as outlined in the Installation and Operation Manuals.
engine “Wet Stacking” due to lightly loaded diesel engines.
travel labor and mileage on portable equipment must be approved before any work is performed.
Terms of warranty shall be deemed made and executed in Lake Crystal, Blue Earth County, Minnesota. Venue for all legal proceedings shall be in Blue Earth County, Minnesota.
Blue Star Power Systems, Inc. | 52146 Ember Rd, Lake Crystal, MN 56055 | Phone + 1 507 726 2508 | www.bluestarps.com
ENGINEERING GUIDE Contact Information Blue Star Power Systems, Inc. 52146 Ember Rd, Lake Crystal, MN 56055 Phone + 1 507 726 2508 | www.bluestarps.com
View more...
Comments